SUPMEA P300 User manual

User's Manual
Pressure transmitter
U-SUP-P300/P400-EN3
Supmea Automation Co.,Ltd.
www.supmea.com
Headquarters
5th floor,Building 4,Singapore Hangzhou Science Technology Park,
No. 6 street,Hangzhou Economic Development Area,
Hangzhou 310018,China
Singapore
2 Venture Drive #11-30 Vision Exchange Singapore

I
Preface
Thank you for purchasing pressure transmitter. Please read this
manual carefully before operating and using it correctly to avoid
unnecessary losses caused by false operation.
Note
Modification of this manual’s contents will not be
notified as a result of some factors, such as function
upgrading.
We try our best to guarantee that the manual content
is accurate, if you find something wrong or incorrect,
please contact us.
This product is forbidden to use in explosion-proof
occasions.
Version
U-SUP-P300/P400-EN3

II
Disclaimer
The company does not make any guarantees for the
terms outside the scope of this product warranty.
This company is not responsible for damage to the
instrument or loss of parts or unpredictable damage
caused directly or indirectly by improper operation of
the user.
No.
Name
Quantity
Note
1
Pressure transmitter
1
2
Manual
1
3
Certificate
1
After opening the box, please confirm the package contents
before starting the operation.If you find that the model and
quantity are incorrect or there is physical damage in
appearance, please contact us.

III
Contents
Chapter 1 Introduction.................................................................... 1
Chapter 2 Characteristics...............................................................2
Chapter 3 Dimension...................................................................... 3
Chapter 4 Parameter...................................................................... 8
Chapter 5 Wiring............................................................................10
5.1 DIN connector type........................................................... 10
5.2 Cable connector type....................................................... 12
Chapter 6 Function & Setting(P400)...........................................13
6.1 Display................................................................................13
6.2 Definition............................................................................ 14
6.3 Monitoring menu............................................................... 15
Chapter 7 Installation.................................................................... 22
Chapter 8 Safety instructions.......................................................24
Chapter 9 Cautions....................................................................... 25
Chapter 10 Warranty & After-sales Service...............................26

Chapter 1 Introduction
www.supmea.com
1
Chapter 1 Introduction
Imported high precision and high stability pressure sensitive
chips are selected for diffused silicon pressure transmitter.
Sensitive chips are fabricated by advanced micro-mechanical
etching process, which forms Wheatstone bridge by diffusing
four high-precision resistors with temperature compensation on
silicon wafers. Because of piezoresistive effect, there are some
changes on the resistance values of the four bridge arm
resistance, so as to make the bridge unbalanced, and then the
sensor outputs an electric signal corresponding to the change
of pressure. The output electric signal is compensated by
amplification and non-linear correction circuit, which generates
voltage and current signals which correspond linearly to the
input pressure.

Chapter 2 Characteristics
www.supmea.com
2
Chapter 2 Characteristics
(1) Compact structure and easy to install.
(2) Advanced diaphragm/oil-filled isolation technology.
(3) High stability and reliability.
(4) Seismic resistance and anti-radio frequency
interference.
(5) 316L stainless steel isolation diaphragm structure.
(6) High precision, all stainless steel structure.
(7) Micro-amplifier, voltage and current signal output.
(8) Strong anti-interference and long-term stability.
(9) Variety of process connections are available.
(10) Wide range of measurement. It can measure absolute
pressure, gauge pressure and sealing reference
pressure.
(11) Anti-vibration and anti-impact.

Chapter 3 Dimension
www.supmea.com
3
Chapter 3 Dimension
P300
DIN connector type
M12 connector type

Chapter 3 Dimension
www.supmea.com
4
Cable connector type (Current voltage output)
Cable connector type (RS485 output)

Chapter 3 Dimension
www.supmea.com
5
DIN connector type
(RS485 output)
P310

Chapter 3 Dimension
www.supmea.com
6
P300G ●PX300
P400 without display

Chapter 3 Dimension
www.supmea.com
7
P400 with display
P400G

Chapter 4 Parameter
www.supmea.com
8
Chapter 4 Parameter
Power Supply
P300:
(4~20)mA output:(10~32)V;
(0~10)V output:(12~32)V;
RS485 output:(8~32)V;
P400 with display:
(4~20) mA output:(12~32)V;
(4~20) mA+RS485 output:(10~32)V
P400 without display:
(4~20) mA output:(9~32)V
Output
(4~20)mA;(1~5)V;
(0~10)V;(0~5)V;RS485
Accuracy
0.2%、0.25%、0.5%
Measurement range
-0.1…0…60Mpa
Pressure type
gauge pressure, adiabatic pressure
and sealed pressure
Compensation
temperature
-10℃~70℃
Working temperature
-20℃~85℃
Medium temperature
-20℃~85℃
Storage temperature
-40℃~85℃
Zero-point
temperature drift
±0.3%FS/10℃

Chapter 4 Parameter
www.supmea.com
9
Sensitivity
temperature drift
±0.3%FS/10℃
Overload pressure
(0.035~10)MPa (150%FS)
(10~60)MPa (125%FS)
Long-term stability
±0.2%FS/year
Response time
RS485 output≤100ms(up to 90%
FS)
Current and Voltage output≤10ms
(up to 90%FS)
Insulation
20MΩ/250VDC
Ingress protection
IP65
Load Resistance
(U-9V)/0.02A

Chapter 5 Wiring
www.supmea.com
10
Chapter 5 Wiring
5.1 DIN connector type
Wiring of DIN connector type as follows:
P300/ P310/ P300G/PX300
Current output
Voltage output
Power
24V
485A
485B 1 Power +
2 Power -
3 RS485 A
RS485 B
RS485 output
RS485 output

Chapter 5 Wiring
www.supmea.com
11
P400/P400G
Current output
Voltage output
RS485 output

Chapter 5 Wiring
www.supmea.com
12
5.2 Cable connector type
Wiring of cable connector type as follows:
Current:
Red Wire: 24V +
Green Wire: Current Output
Voltage:
Red Wire: 24V +
Green Wire: 24V -
Yellow Wire: Voltage Output
RS485:
Red Wire:24V +
White Wire:24V -
Green Wire:RS485+
Yellow Wire:RS485-

Chapter 6 Function & Setting (P400)
www.supmea.com
13
Chapter 6 Function & Setting(P400)
6.1 Display
The main display area and the sub-display area of the screen
have a variety of display functions.There are three kinds of
display on the main screen, namely pressure value display,
percentage display and current display.The sub-display has
two different options: temperature display and no display.The
temperature value comes from the temperature sensor on the
circuit board, and the display switch can be carried out at any
time. The way each click is displayed depends on the mode
value that the software saved at the end.The display mode set
on the panel will be cleared after the next power failure.

Chapter 6 Function & Setting (P400)
www.supmea.com
14
6.2 Definition
"M"
(1) Press "on" to enter the password setting in the
measurement mode.
(2) Press and hold for 5 seconds in the measurement
mode to enter the principal variable reset (i.e., PV reset).
(3) In the setting mode, press the keys for a second to
enable parameter modification, and the modified
parameter flashes. Press the keys again to confirm
parameter modification, and the modified parameter stops
flickering.
"S"
(1) Press shortly in the measurement mode to modify the
display mode.
(2) Press and hold in the measurement mode for 5

Chapter 6 Function & Setting (P400)
www.supmea.com
15
seconds to enter the filling function (the calibration
transmitter is full, which will involve the accuracy and
performance. Do not operate in the case of no standard
source).
(3) In setting mode, add one function for setting
parameters, and long time continuous shift plus one.
"Z"
(1) Press shortly in the measurement mode to modify the
display mode.
(2) Press and hold for 5 seconds in the measurement
mode to enter the zero function (to calibrate the
transmitter zero point).
(3) In the setting mode, for setting parameter
displacement and reduce function, to shift or subtract one
continuously in a long time.
6.3 Monitoring menu
There are two types of access codes, depending on the size of
the transmitter.
(1) 4~20mA output: the entry password is "00001", and the
display unit, display resolution and display mode can be set.
(2) RS485/RS485&4~20mA output: the entry password is
"00016", which can be set as shown in table 1.
Function setting (4~20mA output)
Loc: password input menu, range can be set (19999 ~ 99999),

Chapter 6 Function & Setting (P400)
www.supmea.com
16
menu prompt "PIN".
Set the password to enter the menu. If you enter the
password incorrectly or there is no keys operation within
30 seconds, you will automatically return to the
measurement mode.
Unt: user unit Settings, settable range (0 to 18), menu prompt
for setting each unit.
19 types of unit settings, respectively "MPa", "KPa", "Pa",
"bar", "mbar", "PSI", "mH2O", "mmH2O", "InH2O", "ftH2O",
"mHg", "mmHg", "InHg", "Kg/cm2," "ATM", "Torr", "m", "cm",
"mm".
Dot: display precision setting, settable range(0 ~ 4), menu
prompt is the current pressure unit
The display resolution is the decimal digits of decimal
places displayed in the measurement mode. Users can set
it according to the requirements of field use. It is not better
to display more decimal places, and the stability of the
display value should be given priority. At the same time,
this menu value will be limited by the maximum transmitter
display value during calibration. If the set number of
decimal points is out of the 5-bit display range when the
maximum display value of the transmitter is displayed, the
set number of decimal points will be limited to the range
where the maximum display value can be displayed
normally.
For example: the calibration range of transmitter is 0.0000 ~
20.000MPa;then the setting range of display precision is (0
This manual suits for next models
5
Table of contents
Other SUPMEA Measuring Instrument manuals

SUPMEA
SUPMEA SUP-1158S User manual

SUPMEA
SUPMEA SUP-2100H Series User manual

SUPMEA
SUPMEA SUP-P260-M4 User manual

SUPMEA
SUPMEA Y290 User manual

SUPMEA
SUPMEA U-LWGY-SUP-EN2 User manual

SUPMEA
SUPMEA SUP-1158-J User manual

SUPMEA
SUPMEA SUP-PTU300 User manual

SUPMEA
SUPMEA 6000f User manual

SUPMEA
SUPMEA U-0003NR-EN1 User manual

SUPMEA
SUPMEA PH-5014 User manual
Popular Measuring Instrument manuals by other brands

Fuji Electric
Fuji Electric ZPA instruction manual

KERN&SOHN
KERN&SOHN PROMAT MAP 80K1 operating instructions

Reed Instruments
Reed Instruments R7700 instruction manual

Keithley
Keithley 485 Quick reference guide

Triplett Corporation
Triplett Corporation 630 Type 5 instruction manual

MRC
MRC HT-3027SD Operation manual