
3
Swegon reserves the right to alter specifications. 20151013 www.swegon.com
WISE
2
3
1
Electrical connections.
All the connections are wired to the CONNECT Adapt con-
nection box. From there, the Master air diffuser is connected
by means of the LINK Adapt (RJ45) cable included in the
delivery. The slave air diffusers, if required, are connected
by means of the same type of cable to their respective slave
contacts. If there are more than 2 slave air diffusers, a SPLIT
Link Adapt should be used for further connection to the last
slave air diffuser. See Figure 7. If SPLIT Link Adapt is used, the
maximum length of LINK Adapt from the connection box to
the last air diffuser is 15 meters. If ADAPT is to be connected
through Modbus communication, this should be done with
the LINK Modbus (RJ12) cable. The maximum length of
SPLIT Link Modbus is 10 meters from the connection box to
the last air diffuser. Use double CONNECT Adapts if longer
distances are required. All cables and contacts are different
so that they will not be confused or incorrectly connected.
Electrical data
ADAPT is supplied with power via the connection box. See
the wiring diagram in figure 7 or relevant diagram from the
Swegon Templates application, containing details for the
specific installation. It is important that cables with appro-
priate cross-sectional area, transformers of correct size and
power supply cables of correct length are selected. This
can for example be carried out with the dimensioning tool
“Cable and Transformer Design”, available for download
from www.swegon.com (the application is available in
english and swedish language versions).
Supply voltage 24 V AC ±10 %
Max. power consumption (controller only) 3 VA
Cable rating (controller only) 0.6 A
Ambient temperature 0-50 °C
Figure 6. Air diffuser connections.
1. Connection for LINK Adapt cable (RJ45)
2. Connection for the LINK Modbus cable (RJ12).
3. Direct 24 V connection if a connection box is not used and the
air diffuser will be completely “stand alone”.
Figure 5. Commissioning with TUNE Adapt.
24 V
Modbus
2Swegon reserves the right to alter specifications. 20151013 www.swegon.com
WISE
Maintenance
The exterior surface of the ADAPT air diffusers can be
cleaned whenever necessary using lukewarm water with
dishwashing detergent added.
The duct system is accessible through the air diffuser and
the commissioning box.
Commissioning
All the ADAPT Air diffusers are delivered preset into com-
missioning mode, which means that the air diffuser is set to
max. airflow by override control.
When the ADAPT air diffuser is in commissioning mode, the
LED is orange. Below follows the various LED indications:
• Steady green LED: Normal operation, the air diffuser is
operating normally.
• Flashing green LED: The air diffuser has just been
powered on and calibration is in progress.
• Steady red LED: Function failure, see separate docu-
mentation in the TUNE Adapt manual.
• Steady orange LED: The commissioning mode, max.
airflow
• Flashing orange LED: Other commissioning modes
and all the override control situations of the feedback
control system.
More information about the commissioning process itself
can be found in the Project Manual for the Wise system and
in the TUNE Adapt manual.
Figure 4. Lighting fixtures or similar objects must not be installed
beneath the diffuser as this disrupts the presence detection and
room temperature measurement.