Swegon Actionair ThermShield FD User manual

INSTALLATION GUIDE
ThermShield Standard Installation Method
(Square/Rectangular)
Applies to...
• Actionair ThermShield FD
Health and safety
• This process must be undertaken by competent per-
sons. More than one person may be required to ensure
the safe handling of large dampers and other materi-
als. Use must be made of access equipment to ensure
unsafe practices are not used to approach walls or dif-
cult access areas.
• Standard site PPE should be used (minimum steel toe
cap boots, hard hat); together with any protective
eyewear, gloves and masks, when drilling or cutting is
being undertaken. The latter should also be used when
handing the wall construction materials, as dened by
the material suppliers. If loud equipment is being used,
hearing protection should be used.
• All waste materials should be collected and disposed of
as dened by the relevant supplier.
• Actuators: All wiring should be carried out in accor-
dance with the wiring details provided by the IEE and
BS regulations and by a competent person. Care must
be taken when installing and inspecting dampers, as
they are likely to close without warning due to loss of
electrical power or a temperature rise in the ductwork.
This is their prime function. Do not insert any items,
ngers or limbs between the blades. Larger dampers
must be handled in accordance with current regula-
tions and good practice due to weight.
Contents
Applies to... .......................................... 1
Health and safety .................................. 1
CE Installation Method Overview ..................... 2
Fire damper installation openings..................... 3
Rigid wall installation (mortar sealing)............. 4
Rigid wall installation (mineral wool sealing) .. 5
Rigid wall installation (Fire Batt) ....................... 6
Flexible wall installation (mortar sealing) ........ 7
Flexible wall installation (mineral wool
sealing) ................................................................ 8
Flexible wall installation (Fire Batt)................... 9
Rigid floor/ceiling installation (mortar
sealing) .............................................................. 10
Rigid floor/ceiling installation (Fire Batt) ....... 11
Suspension for mortarless floor installation .. 12
Suspension for mortarless ceiling installation 13
Suspension for mortarless installation close to
ceiling................................................................. 14
Battery assembly installation 2x2 ................... 15
Battery assembly installation (floor/ceiling)
2x2 ..................................................................... 16
Battery assembly installation 1x2 ................... 17
Minimal seperation damper installation......... 18
Periodic maintenance............................ 20
Actuators............................................21
Wiring Diagrams .................................. 24
Dimensional Data................................. 26
Inspection and handover check sheet........ 28

ThermShield Standard Square/Rectangular Installation Guide
2Swegon reserves the right to alter specications. 20210615 - L00010
Application Installation Method
Rigid wall installation (mortar sealing) Page
Rigid wall installation (mineral wool sealing) Page
Rigid wall installation (Fire Batt) Page
Flexible wall installation (mortar sealing) Page
Flexible wall installation (mineral wool sealing) Page
Flexible wall installation (Fire Batt) Page
Rigid oor/ceiling installation (mortar sealing) Page
Rigid oor/ceiling installation (Fire Batt) Page
Suspension for mortarless oor installation Page
Suspension for mortarless ceiling installation Page
Suspension for mortarless installation close to ceiling Page
Battery assembly installation x & X Page
Battery assembly installation (oor/ceiling) x & X Page
Battery assembly installation x Page
Minimal separation distance installation Page
• For full classications please refer to our Declaration
of Performance (DoP), which can be found on our
website.
• The methods in this manual should be followed to
ensure a CE-marked installation.
• The instructions are based on the tested method using
Actionair ThermShield re/smoke dampers.
• Our ThermShield dampers are designed to be
used with re separating elements to maintain re
compartments. The ThermShield is an actuated failsafe
close damper with low smoke leakage, often referred
to in the industry as a Fire/Smoke damper.
• Under the Fire Damper Product standard BS EN 15650
our Fire Damper products are tested to BS EN 1366-2
and classied under BS EN 13501-3.
CE Installation Method Overview

3
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
Fire damper installation
openings
The FD25 / FD40 re damper is always tested in
standardised support frames (both in a concrete wall and
in a exible wall) in accordance with EN 1366-2: 2015
table 3/4/5. The results obtained are valid for all similar
support frames which have a thickness and / or density
and / or re resistance similar or greater than the one of
the tests.
The duct connected to the re damper must be
supported or hung in such a way that the damper does
not carry its weight. The damper must not support
any part of the surrounding construction or wall which
could cause damage and consequent damper failure.
It is recommended to connect the damper to a exible
connection on either end of the damper.
The damper driving mechanism can be placed on either
side of the wall, however it needs to be placed so as to
ensure easy access during inspection.
The gap in the installation opening between the re
damper and the wall/ceiling can be increased by up
to 50% of the gap area, or decreased to the smallest
dimension (B + 60 x H + 60)
• The installation must comply with the tests that were
performed during certication
• Avoid any obstruction of the moving blade by the con-
nected ducts
• The class of air-tightness is maintained in case the
installation of the damper is made in accordance with
the technical manual
• General operating temperature: 50 °C max
• For indoor use only
All dampers can be installed with the blade axis in a
horizontal position or a vertical position in all installation
types except installation remote from the wall and battery
installation. The re damper must be installed into a re
partition structure in such a way that the damper blade
in its closed position is located inside this structure.
To help you nd the suspension plane, a bendable xing
bracket is provided on the damper body and the red tape
is placed on the casing to mark the location of the wall
limit (distance from wall limit to the end of re damper
is 125mm). This does not apply for Applique / MF2 kit
installations.
Check the operation of the re damper before
commencing the installation!
WALL LIMIT
125 mm

ThermShield Standard Square/Rectangular Installation Guide
4Swegon reserves the right to alter specications. 20210615 - L00010
Rigid wall installation
(mortar sealing)
Damper blade must be closed during the installation!
The wall is composed of concrete blocks (minimum
density of 550 kg/m³) or reinforced concrete (minimum
density of 2200 kg/m³) and with a minimum thickness of
100 mm. Installation material: mortar.
1. Prepare opening in the wall according to B (H) + 80
mm or more (up to 50% more). Insert re damper into
wall to the wall limit mark (7) on the damper and bend
the xing bracket (1) 90°.
2. Fix the re damper to the wall with the screws. Bracket
screw hole is 6 mm in diameter.
3. Fill the space between the damper and the wall with
mortar. (2).
Minimum seperation between re dampers, either next
to each other or ceiling/wall, should be 30 mm between
them. See page 18.
* Build the support for installation according to the
drawing
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
12 3
2
7
1

5
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
Rigid wall installation
(mineral wool sealing)
Damper blade must be closed during the installation!
The wall is composed of concrete blocks (minimum
density of 550 kg/m³) or reinforced concrete (minimum
density of 2200 kg/m³) and with a minimum thickness of
100 mm.
Installation material: mineral wool, covered with
plasterboard cover boards.
1. Prepare opening in the wall according to B (H) + 80
mm or more (up to 50% more). Insert re damper into
wall to the wall limit mark (7) on the damper and bend
the xing bracket (1) 90°(bracket screw hole is 6 mm in
diameter).
2. Fix the re damper to the wall with the screws (refer to
page 15).
3. Fill the space between casing and wall with mineral
wool (3).
4. Cover the wool with gypsum boards (4) (12,5 mm
thick).
12 3
Minimum seperation between re dampers, either next
to each other or ceiling/wall, should be 30 mm between
them. See page 18.
Ensure that the damper is sufciently supported!
4
1
7
3

ThermShield Standard Square/Rectangular Installation Guide
6Swegon reserves the right to alter specications. 20210615 - L00010
Rigid wall installation
(Fire Batt)
Damper blade must be closed during installation!
The wall is composed of concrete blocks (minimum
density of 550 kg/m³) or reinforced concrete (minimum
density of 2200 kg/m³) and with a minimum thickness of
100 mm.
Installation material: mineral wool ≥ 140 kg/m³, re
protection coating.
1. Recommended wall opening for re damper
installation is B(H) + 200 mm, but openings from B(H)
+ 80…300mm can also be used.
2. Insert re damper into wall to the wall limit mark (7)
on the damper and bend the xing bracket (1) 90°.
Close space between casing and wall with two layers
of mineral wool (5) (density 140 kg/m³ or more, 50
mm thick, coated on one side). Seal the connections of
mineral wool with wall and damper with intumescent
(6) re resistant sealant. Mineral wool and damper
casing must be coated with 2mm thick re protection
coating. Damper casing should be coated up to prole
anges.
Ensure that the damper is sufciently supported!
123
1
5
6
7

7
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
1
2
4
7
Flexible wall installation
(mortar sealing)
Damper blade must be closed during the installation!
The wall is composed of 2x2 plasterboard boards, 12,5
mm thick, installed on a steel frame construction. The
interior of the wall is lled with mineral wool (≥ 100 kg/
m³).
Installation material: gypsum plaster or mortar, covered
with cover boards. The minimum thickness of the wall is
100 mm.
1. Prepare opening in the wall according to B (H) +
80 mm or more (up to 50% more), and build the
subframe according to the drawing. Bend the xing
bracket (1) 90°. Place the damper in the opening up to
the wall limit mark (7) on the damper.
2. Fix the damper to the wall using self-tapping screws
Ø3,5x45 mm (bracket screw hole is 6 mm in diameter).
3. Fill the space between the damper and the wall with
mortar sealing (2). Cover the mortar with (4) gypsum
boards (12,5 mm thick).
* Build the support for mortar installation according to
the drawing.
Test the operation of the damper blade!
Minimum seperation between re dampers, either next
to each other or ceiling/wall, should be 30 mm between
them. See page 18.
Ensure that the damper is sufciently supported!
625 625
> 440
625 625
> 440
625 625
> 440
123

ThermShield Standard Square/Rectangular Installation Guide
8Swegon reserves the right to alter specications. 20210615 - L00010
625 625
> 440
Flexible wall installation
(mineral wool sealing)
Damper blade must be closed during the installation!
The wall is composed of 2x2 plasterboard boards, 12,5
mm thick, installed on a steel frame construction. The
interior of the wall is lled with mineral wool (≥ 100 kg/
m³).
Installation material: mineral wool covered with cover
boards. The minimum thickness of the wall is 100 mm.
1. Prepare opening in the wall according to B (H) + 80
mm or more (up to 50% more), and build the sub-
frame according to the drawing. Bend the xing
bracket (1) 90°. Place the damper in the opening up to
the wall limit mark (7) on the damper.
2. Fix the damper to the wall using self-tapping screws
Ø3,5x45 mm (bracket screw hole is 6 mm in diameter).
3. Fill the space between the damper and the wall with
mineral wool (≥100 kg/m³) (3). Cover the mineral wool
with gypsum boards (12,5 mm thick) (4) and x them
with self-tapping screws Ø3,5x45 mm.
Minimum seperation between re dampers, either next
to each other or ceiling/wall, should be 30 mm between
them. See page 18.
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
13
7
4
625 625
> 440
625 625
> 440
12 3

9
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
Flexible wall installation
(Fire Batt)
Damper blade must be closed during installation!
The wall is composed of 2x2 plasterboard boards,
12,5mm thick, installed on a steel frame construction. The
interior of the wall is lled with mineral wool (≥ 100 kg/
m³).
Installation material: mineral wool (≥ 140 kg/m³) and re
protection coating. The minimum thickness of the wall is
100mm.
1. Recommended wall opening for re damper
installation is B(H) + 200mm, but openings from B(H) +
80…300mm can also be used. Bend the xing bracket
(1) 90°.
2. Insert re damper into wall to the wall limit mark (7) on
the damper.
3. Fill the space between casing and wall, close with two
layers of mineral wool (5) (density 140 kg/m³ or more,
50 mm thick, coated on one side).
Seal the connections of mineral wool with intumescent
(6) re resistant sealant. Mineral wool and damper casing
must be coated with 2mm thick re protection coating.
Damper casing should be coated up to prole anges.
Minimum seperation between re dampers, either next
to each other or ceiling/wall, should be 30 mm between
them. See page 18.
**Fire Batt installations adjacent to ceiling or wall require
a suspension for the re damper.
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
1
5
6
7
1 2 3

ThermShield Standard Square/Rectangular Installation Guide
10 Swegon reserves the right to alter specications. 20210615 - L00010
Rigid floor/ceiling
installation (mortar
sealing)
Damper blade must be closed during installation!
The oor/ceiling is composed of concrete blocks
(minimum density of 550 kg/m³) or reinforced concrete
(minimum density of 2200 kg/m³) and with a minimum
thickness of 100mm.
Installation material: gypsum plaster or mortar.
1. Prepare opening in the wall according to B (H) + 80mm
or more (up to 50% more), insert the damper to the limit
mark (7) on the damper and bend the xing bracket (1)
90° (bracket screw hole is 6 mm in diameter).
2. Fix the damper to the oor/ceiling using screws.
3/3*. Fill the space between the damper and the oor/
ceiling with mortar. (2)
Test the operation of the damper blade!
1
2
7
* Build the support for installation according to the
drawing.
Ensure that the damper is sufciently supported!
*Installation in oor
1234

11
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
51
67
*Installation in oor
Rigid floor/ceiling
installation (Fire Batt)
Damper blade must be closed during installation!
The oor/ceiling is composed of concrete blocks
(minimum density of 550 kg/m³) or reinforced concrete
(minimum density of 2200 kg/m³) and with a minimum
thickness of 100mm.
Installation material: mineral wool ≥ 140 kg/m³, re
protection coating.
1.Recommended oor/ceiling opening for re damper
installation is B(H)+ 200mm, but openings from B(H)+
80…300mm can also be used.
2. Insert re damper into ceiling to the wall limit mark (7)
on the damper.
Fill the space between casing and ceiling with two layers
of mineral wool (5) (density 140 kg/m³ or more, 50mm
thick, coated on one side).
3/3*. Connections of mineral wool should be sealed
with (6) intumescent re resistant sealant. Mineral wool
and damper casing must be coated with 2mm thick re
protection coating. Damper casing should be coated up to
prole anges.
* Fire Batt oor/ceiling installations require a suspension
for the re damper.
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
*Installation in ceiling
1234

ThermShield Standard Square/Rectangular Installation Guide
12 Swegon reserves the right to alter specications. 20210615 - L00010
Suspension for
mortarless floor
installation
Damper blade must be closed during installation!
Suspension systems are required for the dry mortarless
installation of the re damper with mineral wool in
oor slabs. Fire dampers can be suspended from solid
oor slabs using adequately sized threaded rods. Load
the suspension system only with the weight of the re
damper. Ducts must be suspended separately.
1. Suspension strut should be connected with drop rods
(8/10mm) to the oor. It is used to support the damper
and ease the installation.
2. Support steel C proles by 90 mm high piece of
aerated concrete or similar rigid material.
3. Suspend the re damper to the steel C proles.
Close the space between casing and oor with Firestop
board (Firebatt) 2x50mm (≥ 140 kg/m3) and coat the
damper casing.
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
27mm
18mm
min. 200 min. 200
A
(350)
90
100
min. 100
B+400
H+400
H
100
125
1234

13
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
27mm
18mm
Detail A
Suspension for
mortarless ceiling
installation
Damper blade must be closed during installation!
Suspension systems are required for the dry mortarless
installation of the re damper with mineral wool in
ceiling slabs. Fire dampers can be suspended from solid
ceiling slabs using adequately sized threaded rods. Load
the suspension system only with the weight of the re
damper. Ducts must be suspended separately.
1. Suspension strut should be connected with drop rods
(8/10mm) to the ceiling slab above. It is used to support
the damper and ease the installation.
2. Support steel C proles by 90mm high peace of
aerated concrete or similar rigid material.
3. Suspend the re damper to the steel C proles.
Close the space between casing and oor/ceiling with
Firestop board (Firebatt) 2x50mm (≥ 140 kg/m3) and coat
the damper casing.
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
(350)
90
100
min. 100
B+400
H+400
H
100
125
min. 200 min. 200
A
1234

ThermShield Standard Square/Rectangular Installation Guide
14 Swegon reserves the right to alter specications. 20210615 - L00010
61
3
7
Suspension for
mortarless installation
close to ceiling
Damper blade must be closed during installation!
Suspension systems are required for the dry mortarless
installation of the re damper with mineral wool in solid
walls and exible walls. Fire dampers can be suspended
from solid ceiling slabs using adequately sized threaded
rods. Load the suspension system only with the weight of
the re damper. Ducts must be suspended separately.
1. Prepare opening in the wall according to H + 130mm
and B + 200mm or more and install threaded rods (8 mm)
to the ceiling above.
2. Insert re damper into wall to the wall limit mark (7)
on the damper and bend the xing bracket (1) 90°. (screw
hole is 6mm in diameter). Fix the C prole on the drop
rods using M8 screws.
3. Close the space between casing and wall with mineral
wool (≥ 140 kg/m³) (3). Connections of mineral wool
should be sealed with intumescent re resistant sealant
(6). Mineral wool and damper casing must be coated
with 2mm.
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
18mm
27mm
12 3

15
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
(1) Accessories (2) Type (3) Length
FD-A - CF60 800
(1)
(2)
Fire damper accessories
FD-A
Type
CF60 - Connecting frame 60mm
CF100 - Connecting frame 100mm
CP60- Connecting plate 60mm
CP100- Connecting plate 100mm
(3) Connecting frame length
200 ... 1200[mm]
Battery assembly
installation 2x2 & 2X1
Damper blade must be closed during installation!
The wall is composed of concrete blocks (minimum
density of 550 kg/m³) or reinforced concrete (minimum
density of 2200 kg/m³) and with a minimum thickness of
100mm.
Maximum dimension of a single unit in a 2 X 2 battery
installation:
2X2 grid: 1200x800mm
*For battery installation 2x2 use 8x connecting frames
and 2x connecting plate.
1. Prepare a hole of dimensions 2B + 140 mm and 2H
+ 140mm ll the bottom with mortar/gypsum in 50mm
height.
2. Place two lower dampers in the opening, and x
dampers to the wall using screws (only 2 sides facing
aerated concrete). Place the vertical part from the
installation kit to the dampers on both sides, and attach it
using the self-tapping screws.
3. Fill the space between the dampers and the wall with
mortar/gypsum, and ll the space between the dampers
with mineral wool (100 kg/m³ of density or higher). Place
two upper dampers and x the dampers to the wall using
the screws (only 2 sides facing aerated concrete).
4. Place the vertical part and two horizontal parts from
the installation kit to the dampers on both sides, and
attach it using the self-tapping screws every 150mm.
Fill the gap between dampers and wall on upper side
with mortar/gypsum and the installation is complete.
Test the operation of the damper blade!
Ensure that the damper is sufciently supported!
1234

ThermShield Standard Square/Rectangular Installation Guide
16 Swegon reserves the right to alter specications. 20210615 - L00010
Battery assembly
installation (floor/
ceiling) 2x2 & 2X1
Damper blade must be closed during installation!
The oor/ceiling is composed of concrete blocks
(minimum density of 550 kg/m³) or reinforced concrete
(minimum density of 2200 kg/m³) and with a minimum
thickness of 100mm.
Maximum dimension of re dampers:
2X2 grid: 1200x800mm
*For battery installation 2x2 use 8x connecting frame and
2x connecting plate.
1. Prepare a hole of dimensions 2B + 140mm and 2H +
140mm and set all U proles to a height of 118mm (use
blocks of aerated concrete to keep distance between
ceiling and proles).
2. Arrangement of steel C proles (27x18mm).
3. Place the dampers in the openings to the wall limit
mark (7) and bend the xing bracket 90° (1). Put them
on U proles and x using the self-tapping screws every
150mm. Fix the dampers and proles to the ceiling using
the screws for concrete. Place four connection proles
from the installation kit to the dampers on both sides
and attach it using the self-tapping screws.
4. Fill the space between the dampers with mineral wool
(100 kg/m³ of density or higher) and then ll the space
between
Ensure that the damper is sufciently supported!
7
1
(1) Accessories (2) Type (3) Length
FFD-A - CF60 - 800
(1)
(2)
Fire damper accessories
FD-A
Type
CF60 - Connecting frame 60mm
CF100 - Connecting frame 100mm
CP60- Connecting plate 60mm
CP100- Connecting plate 100mm
(3) Connecting frame length
200 ... 1200 [mm]
118
42
wall
Floor/ceiling
18mm
27mm
118
42
wall
118
42
wall
1234

17
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
150 150 150
150 150 150
150 150 150
Battery assembly
installation 1x2
Damper blade must be closed during installation!
The wall is composed of blocks of aerated concrete
(minimum density 550 kg/m³) and with a minimum
thickness of 100mm.
Maximum dimension of re dampers:
1X2 grid: 1500x800mm
*For battery installation 1x2 use 2x connecting frame.
1. Prepare a hole of dimensions B + 80mm and 2H + 140
mm. Fix the dampers to the wall using the screws and ll
the space between the dampers and the wall with mortar.
2. Place the installation kit to the dampers.
3. Attach the installation kit to the dampers using the self-
tapping screws every 150mm.
4. Fill the space between the dampers with mineral wool
(100 kg/m³ of density).
Ensure that the damper is sufciently supported!
(1) Accessories (2) Type (3) Length
FD-A - CF60 - 800
(1)
(2)
Fire damper accessories
FD-A
Type
CF60 - Connecting frame 60mm
CF100 - Connecting frame 100mm
CP60- Connecting plate 60mm
CP100- Connecting plate 100mm
Connecting frame length
200 ... 1200[mm]
150 150 150
1234

ThermShield Standard Square/Rectangular Installation Guide
18 Swegon reserves the right to alter specications. 20210615 - L00010
60
30
60
120
30
Material compliant
with the classication
from DOP
Mineral wool 350mm
wide (140 kg/m³)
* Minimal distances from another damper or wall/ceiling.
Minimal separation
distance installation
Damper blade must be closed during installation!
1. Prepare opening in the wall according to page 3.
B (H) + 80mm or more (Firebatt installation- build the
subframe according to the drawing.
Fire damper can be installed with minimal distance of
30mm between wall/ceiling and 60mm from other
dampers.
2. Insert the re dampers into the wall and ll the space
between the casings with mineral wool (140kg/m³) up to
anges.
Fill the space between the wall/ceiling with mineral wool
(140kg/m³) up to anges.
3. Fill the rest of the wall openings in accordance with the
relevant installation method.
*Examples for Firebatt installation
Ensure that the damper is sufciently supported!
1234

19
20210615 - L00010 Swegon reserves the right to alter specications.
ThermShield Standard Square/Rectangular Installation Guide
FD25 FD40
Flexible Wall Subframe
When installing the re dampers in the exible walls it
is necessary to make a metal subframe onto which the
damper will be xed with screws. Subframe should be
prepared according to the drawings below.
Support for Installation with Mortar
In re damper installations with mortar, it may be
necessary to use wooden supports to prevent the casing
from deforming while mortar is setting.
Before lling the gap between wall and re damper, close
the damper blade and install the wooden supports as
seen in the drawings below.
Place the wooden support as close as possible to the re
damper blade!
Ensure that the damper is sufciently supported!
(B+80)
(H+80)
(B+80)/2
(B+80)
(H+80)

ThermShield Standard Square/Rectangular Installation Guide
20 Swegon reserves the right to alter specications. 20210615 - L00010
Periodic Maintenance
Manufacturer Recommended Service
Intervals
• After commissioning and handover (see DW145 check
sheet), in order to remain compliant with 15650:2010,
we recommend that you follow a regular service and
inspection programme to ensure correct operation
of dampers in the event the damper is required to
actuate.
• In addition to regular physical inspections (in
accordance with 15650:2010) we recommend using a
dedicated damper control panel with a digital reporting
mechanism (such as an Actionpac LNS system) to
frequently monitor and report on regular remote
damper testing.
• Ensure maintenance is performed in line with the latest
best practice and relevant local or specialist guidance.
• Our recommended service intervals for life safety
products are as follows:
Interval Action Competence
6 Months Check Actuator Wiring (if appli-
cable) for Damage
Specialist
Persons
6 Months Check Limit Switch Wiring (if
applicable) for Damage
Specialist
Persons
6 Months Check Damper Cleanliness, Clean
and Lubricate if necessary.
Specialist
Persons
6 Months Check Condition of Blades and
Seals, report and rectify if neces-
sary.
Specialist
Persons
6 Months Check for blade obstructions Specialist
Persons
6 Months Check Damper Release Me-
chanism (through activation or
release of the ETR or Thermal
Fuse Device)
Specialist
Persons
6 Months Check damper is left in normal
operational position after inspec-
tion.
Specialist
Persons
Monthly Complete actuation of damper
from control panel (if installed)
and check all faults. Consult spe-
cialist persons to investigate any
reported faults.
Facility Ma-
nager
• *Specialist Persons: A recognised and experienced
person with prior experience in the inspection and
assessment of the functional safety of smoke and re
damper products. If in doubt, please consult with our
technical support team for advice. To talk about our
OEM maintenance inspections, contact our nationwide
service team.
BS EN 15650:2010 - Ventilation for Buildings
- Fire Dampers
• Section 8.3 states regular testing/ inspection should
be undertaken to meet regulatory requirements, or at
intervals not exceeding six months.
• A comprehensive example of the maintenance
procedure is given in Annex D of the standard. Some
automatic systems may allow more frequent testing
(48hr or less) and this may be required by a national
standard.
Approved Document B, Volume 2
• Clause 10.12 states adequate means of access must be
provided to allow inspection, testing and maintenance
of both re damper and its actuating mechanism.
BS 9999:2017 - Code of Practice for the Fire
Safety in the Design, Management and Use
of Buildings - Annex I
Smoke Control Systems
• For means of escape states actuation of the system
should be simulated once a week. It should be ensured
that any fans and powered exhaust ventilators operate
correctly, smoke dampers close (or open in some
systems), natural exhaust ventilators open, automatic
smoke curtains move into position, etc.
Three Monthly
• In addition to the checks recommended in V.2, V.3 and
V.4, the actuation of all smoke control systems should
be simulated once every three months. All zones should
be separately tested and it should be ensured that any
fans and powered exhaust ventilators operate correctly,
smoke dampers close (or open in some systems) etc.
Yearly
• In addition to the following checks should be made
for annual inspections and tests of the following to
be carried out by competent persons, for any defects
to be logged and the necessary action taken, and for
certicates of testing to be obtained.
– Fire detection and re alarm systems;
– Self-contained luminaires with sealed batteries, if more
than 3 years old;
– Sprinkler, drencher and watermist systems;
– Smoke ventilators and smoke control systems;
– Fire dampers
BS 9999:2017 - Code of Practice for the Fire
Safety in the Design, Management and Use
of Buildings - Annex W
• Maintenance of air conditioning and ventilation
equipment including air lters, motors, re dampers
and their controls, smoke detectors and alarms is
of paramount importance both in preventing re
and in ensuring that measures taken to mitigate
its consequences are effective when needed.
Arrangements should be made for all re dampers to
be tested by a competent person on completion of the
installation and at regular intervals not exceeding 2
years. They are to be repaired or replaced immediately
if found to be faulty. Spring operated re dampers
should be tested annually and re dampers in dust
laden and similar atmospheres should be tested much
more frequently, at periods suited to the degree of
pollution.
Other manuals for Actionair ThermShield FD
1
Table of contents
Other Swegon Fire And Smoke Damper manuals

Swegon
Swegon REACT Pa User manual

Swegon
Swegon BLBd Guide

Swegon
Swegon Actionair A60 User manual

Swegon
Swegon Actionair CSS Series User manual

Swegon
Swegon Actionair SmokeShield PTC User manual

Swegon
Swegon SIRI a Guide

Swegon
Swegon actionair DWFX-C User manual

Swegon
Swegon Actionair ThermShield MF User manual

Swegon
Swegon actionair FireShield User manual

Swegon
Swegon SAFEGARDSYSTEMS FD 25 User manual