Swegon PARAGON VAV d Guide

PARAGON VAV d
Installation – Commissioning – Maintenance 22/11/2021
Art. 942428072
Content
Application area.................................................. 2
General....................................................................... 2
Contents..................................................................... 2
Protective equipment .................................................. 2
Electrical safety ........................................................... 2
Handling..................................................................... 2
Installation .................................................................. 2
Disposal...................................................................... 2
Cleaning ..................................................................... 2
Service/maintenance ................................................... 2
Product warranty ........................................................ 2
Dimensions and weight...................................... 3
Installation .......................................................... 4
Cutout dimensions...................................................... 4
Suspension ................................................................. 5
Water connection ....................................................... 7
Connecting water ....................................................... 7
Water connection, CCO-valve ..................................... 8
Air connection ............................................................ 9
Connection dimensions air.......................................... 9
Supply and extract air ............................................... 10
Supply air.................................................................. 10
Extract air ................................................................. 10
Mounting grills ..........................................................11
Wiring diagram......................................................... 13
Maintenance...................................................... 15
Symbols
Warning/Caution!

PARAGON VAV
2Swegon reserves the right to alter specications. 22/11/2021
Application area
The product is a comfort module designed for demand-
controlled indoor climate. The product is used to ventilate,
cool and heat the room exactly as needed.
The product may not be used for anything other than its
intended use.
General
Read through the entire instructions for use
before you install/use the product and save
the instructions for future reference. It is not
permissible to make changes or modify this
product other than those specified in this document.
Contents
1 PARAGON VAV
1 Instructions for use
Protective equipment
Always use appropriate personal protective
equipment for the work in question, in the
form of gloves, respirators, protective glasses
and helmets during handling, installation,
cleaning and service/maintenance.
Electrical safety
Permitted voltage, see Electrical data.
It is not permissible to insert foreign objects
into the product’s contactor connections or
ventilation openings; risk for short circuiting.
24 V isolation transformer to be connected should comply
with the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the
product and the power supply source.
Disconnect the power supply when working on products
that are not required to run.
Always follow the local/national rules for who shall be
permitted to carry out this type of electrical installation.
Handling
Always use appropriate transport and lifting devices when
the product is to be handled to reduce ergonomic loads.
The product must be handled with care.
Cleaning
Ideally the product should be cleaned twice a year by
vacuuming the coil to remove loose dust. In fibre dense
environments as hotels and ward rooms a first vacuuming
after three months is recommended and thereafter an
interval of 1-2 times a year. This is due to the fact that new
textiles often loose a lot of fibres in the beginning of their
life cycle.
A simple visual inspection of connections is recommended
when cleaning.
On painted surfaces such as grills: Avoid aggressive cleaning
agents which may harm painted surfaces. Normally a mild
soap or alcohol solution is fully adequate for cleaning. See
also the maintenance section in this instructions for use.
Cleaning of electrical components
• If needed, use a dry cloth to clean the components.
• Never use water, detergent and cleaning solvent or a
vacuum cleaner.
Service/maintenance
• In connection with a service, mandatory ventilation
inspection or cleaning of the ventilation system, check
that the general condition of the products looks ok. Pay
particular attention to the suspension, cables and that
they sit firmly in place.
• It is not permissible to open or repair electrical components.
• If you suspect that the product or a component is defective,
please contact Swegon.
• A defective product or component must be replaced by
an original spare part from Swegon.
Product warranty
The product warranty or service agreement will not be in
effect/will not be extended if: (1) The product is repaired,
modified or changed, unless such repair, modification
or change has been approved by Swegon AB; or (2) the
serial number on the product has been made illegible or is
missing.
Installation
• Moist, cold and aggressive environments must be
avoided
• Assemble the product according to this instruction and
applicable industry regulations
• Install the product for easy access during service/
maintenance
• Avoid installing the product near a heat source
• Check to make sure that the product does not have
any visible defects
• Check that the product is properly secured after it has
been installed
• Secure cables with cable ties
• Check that all cables are properly secured in place after
installation
Disposal
Waste must be handled according to local regulations.

3
22/11/2021 Swegon reserves the right to alter specications.
PARAGON VAV
823/1123/1423
722
190
153
800/1100/1400
593
187
162
789/1089/1389
722
438
131 153
c-c 222,5
189
153
769/1069/1369
578
200
121
Dimensions and weight
Weight
PARAGON VAV 800
Length Type Dim. Dry weight* (kg) Water volume (l)
mm Øwithout
grills
incl.
grills
cooling heating
800 R A 125 14.0 16.9 1.39
800 L A 125 14.0 16.9 1.38
800 R B 125 14.0 16.9 1.39 0.38
800 L B 125 14.0 16.9 1.38 0.37
800 R X 125 14.0 16.9 1.39
800 L X 125 14.0 16.9 1.38
PARAGON VAV 1100
Length Type Dim. Dry weight* (kg) Water volume (l)
mm Øwithout
grills
incl.
grills
cooling heating
110 0 R A125 18.8 22.6 1.93
110 0 L A125 18.8 22.6 1.92
110 0 R B125 18.8 22.6 1.93 0.52
110 0 L B125 18.8 22.6 1.92 0.51
110 0 R X125 18.8 22.6 1.93
110 0 L X125 18.8 22.6 1.92
PARAGON VAV 1400
Length Type Dim. Dry weight* (kg) Water volume (l)
mm Øwithout
grills
incl.
grills
cooling heating
1400 R A125 23.0 27.6 2.47
1400 L A125 23.0 27.6 2.46
1400 R B125 23.0 27.6 2.47 0.65
1400 L B125 23.0 27.6 2.46 0.64
1400 R X125 23.0 27.6 2.47
1400 L X125 23.0 27.6 2.46
*excl. weight for:
Control equipment: 0,84 kg

PARAGON VAV
4Swegon reserves the right to alter specications. 22/11/2021
Cutout dimensions
Installation
23,5 315
92,5 92,5
25,6
23,5
315
92,5
92,5
25,6
91
569 (+ 0-20) 153
153
121,4
205
0
378
405
91
569 (+ 0-20) 153
153
121,4
205
0
378
405
805 / 1105 / 1405 ±10
785 / 1085 / 1385
±10
>40
>70
390 ±10
>193
>250
140 ±10

5
22/11/2021 Swegon reserves the right to alter specications.
PARAGON VAV
Suspension
23,5
8,5
11,7
6
222,5 146,6
15
Ø125
L A B
800 778,2 222,5
1100 1078,2 222,5
1400 1378,2 222,5
c / c = B
c / c = A
823 / 1123 / 1423
> 722 >250
>250 >250

PARAGON VAV
6Swegon reserves the right to alter specications. 22/11/2021
M8 4 x

7
22/11/2021 Swegon reserves the right to alter specications.
PARAGON VAV
Water connection
Water connection on right side (R).
A1 = Cooling water, supply
A2 = Cooling water, return
B1 = Heating water, supply
B2 = Heating water, return
Water connection on left side (L).
A1 = Cooling water, supply
A2 = Cooling water, return
B1 = Heating water, supply
B2 = Heating water, return
Cooling and heating on right side "R", all sizes
Cooling "R", all sizes
Cooling and heating on left side "L" all sizes
Cooling "L" all sizes
23,5 315
92,5 92,5
25,6
A1 A2 B1
B2
A1 A2
A1 A2 B1
B2
A1 A2
23,5
8,5
11,7
6
222,5 146,6
Ø125
15
Water dimensions
Standard variant with factory fitted valves:
Length Cooling Heating
(mm) Return Return
800, 1100, 1400 DN15 external
thread
DN15 external
thread
Standard variant without factory fitted valves:
Length Cooling Heating
(mm) Supply and return Supply and return
800, 1100, 1400 Plain pipe Plain pipe
(Cu) Ø 12 x 1,0 mm (Cu) Ø 12 x 1,0 mm
Connecting water
Connect the water pipes using push-on couplings or
compression ring couplings when the product is ordered
without valves. Note that compression ring couplings
require support sleeves inside the pipes.
Do not use solder couplings to connect the water pipes.
High temperatures can damage the unit’s existing soldered
joints. Flexible connecting hoses for water are available for
flat-end pipes and valves, and can be ordered separately.
Water connection on right side "R" Water connection on left side "L"

PARAGON VAV
8Swegon reserves the right to alter specications. 22/11/2021
Water connection on back side "B".
A1 = Cooling water, supply
A2 = Cooling water, return
B1 = Heating water, supply
B2 = Heating water, return
D
B1
B2
505050
A1
A2
C
Water connection - CCO-valve.
A1 = Cooling water, supply
A2 = Cooling water, return
B1 = Heating water, supply
B2 = Heating water, return
C = CCO valve
D = Flexible hose
Water connection, CCO-valve
A1
A2
B1 B2
Water connection on back side "B"

9
22/11/2021 Swegon reserves the right to alter specications.
PARAGON VAV
Air connection
All variants have an air connection Ø125.
The standard variant has the air connection centered on
the back of the product for easy access from both ends
and back.
The suite variant, which is only available in length 1400
mm, has two parallel air connections on the back (2x
Ø125).
Suite
PARAGON suite, view from the back
Standard
PARAGON standard, view from the back
Connection dimensions air
Variant Length Air connetion
(mm) 1 x Ø 125 2 x Ø 125
1: Standard 800, 1100, 1400 Yes No
2: Suite 1400 No Yes

PARAGON VAV
10 Swegon reserves the right to alter specications. 22/11/2021
Supply and extract air
Supply air kit Extract air kit

11
22/11/2021 Swegon reserves the right to alter specications.
PARAGON VAV
Supply air kit Extract air kit
Mounting grills
Click!
Click!

PARAGON VAV
12 Swegon reserves the right to alter specications. 22/11/2021
RU Connections
RJ 12 12-40 VDC power supply
RJ 12 RS-485 bus connection
RJ 12 RS-485 bus connection
RJ 12 Ground for 12-40 VDC power supply
Ain Analog input, 0-10V
GND Ground
NTC External 10k NTC temperature measurement
Memory card slot. User panel software
is possible to update via Micro sd card.
Technical data, RU
Display Capacitive touch TFT Display QVGA
2.3”
Display resolution 320x240
External memory MicroSD card
Communication Modbus RTU via RS-485
Temperature
sensors
Internal 10K NTC sensor, external
NTC sensor option
Operating tempe-
rature
+5 ... +40°C
IP class IP20
Dimensions 88 x 88 x 35
Operating voltage 12-40 VDC
Power needs 0.5 W
Symbols and settings
Stand-by The screen goes into standby mode after 20sec and
is activated again by tapping the screen (if standby
function has been configured to be activated). In
stand-by mode, you can choose to display blank
screen, current temperature, temperature setting
value or symbol.
If display is in stand by mode, touch the screen to
switch the display from sleep mode to active mode.
(If the stand-by function is configurated to be disab-
led, the display is in active mode all the time.)
TEMP: Measured temperature. In that mode, first
+/- button pressing change the value to setpoint
and second pressing adjust the setpoint.
After a while, it changes back to showing temperature.
SET: Room temperature setting value. Change the set-
ting value by selecting + or -.
Informative indication. Cooling is ON.
Informative indication. Heating is ON.
Room unit, RU
Room temperature adjuster RU with integrated tempera-
tur sensor and digitalt color display.
To be mounted on the top of a connection box.
Micro SD-card reader
RU display
Frame
Mounting bracket
The room unit has a digital color-touch display where you
adjust the indoor climate by increasing or decreasing the
temperature in the room. The display shows the current
operating mode in the room (heating / cooling). There
is also a Menu in the upper right corner where you can
access more functions / parameters. The sensor module is
connected to the controller using the RJ 12 cable.

13
22/11/2021 Swegon reserves the right to alter specications.
PARAGON VAV
Wiring diagram
Wiring diagram for accessories
24V
G0G
grey
black
blue (US=black)
brown (US=white)
brown (US=white)
blue (US=black)
|1 2|3 4|5 6|7 8| 9 10 11 12 |
|13 14 15 |1617 18 |19 20 21 |
| 22 | 23 | 24 | 25 |
black
black
white
brown
white
y24V
brown
blue
black Y- control signal / styrsignal 0-10V DC
RoHS
Temperature sensor/
Window contact
Valve actuator,
cooling
Valve actuator,
heating
Key card
Condensation
sensor
CO2sensor
24 V AC / DC
Cabel
USB-RJ12
Cable adapter
Pressure sensor
(Modbus)
Adapter
3xRJ12
Adapter
3xRJ12
Motor
Sensor module
VOC-sensor
A
A. Connection when a VOC sensor is used
Inputs Outputs
ModBus Motor
Inputs Outputs
ModBus Motor
Max 48 VA
Max 48 VA
Max 48 VA
The outputs on the regulator

PARAGON VAV
14 Swegon reserves the right to alter specications. 22/11/2021
RS 485type Belden 9842
Modular6/6 RJ12
Modular 6/6 RJ12
22 23 24 25
Modular
6/6 RJ12
| 12 | 3 4 | 5 6 |7 8 |9 10 11 12 |
|13 14 15 |16 17 18| 19 20 21 |
| 22 | 23 | 24 | 25 |
| 12 | 3 4 | 5 6 |7 8 |9 10 11 12 |
|13 14 15 |16 17 18| 19 20 21 |
| 22 | 23 | 24 | 25 |
MB id 8
Master
MB id 4
Master
22 23 24 25
Modular
6/6 RJ12
1 2 3 4
MB2
5678
MB1
Next Zone
CONTROL Zone
MB id 1
Super WISE
1 2 312 3
Zone
Room
| 12 | 3 4 | 5 6 |7 8 |9 10 11 12 |
|13 14 15
|
16
17
18 | 19 20 21|
| 22 | 23 | 24 | 25 |
MB id 4
Master
22 23 24 25
Modular6/6 RJ12
Modular6/6 RJ12
22 23 24 25
Modular
6/6 RJ12
| 12 | 3 4 | 5 6 |7 8 |9 10 11 12 |
|13 14 15
|
16
17
18 | 19 20 21|
| 22 | 23 | 24 | 25 |
| 12 | 3 4 | 5 6 |7 8 |9 10 11 12 |
|13 14 15 |16 17 18| 19 20 21 |
| 22 | 23 | 24 | 25 |
MB id 1
Slave id 1
MB id 4
Master
22 23 24 25
Room
Room
RK 0,75
Modular
6/6 RJ12
20
19
B
A
GND
GND B A
GND B A
9
10
AGND B
AGND B
RK 0,75
GND B A

15
22/11/2021 Swegon reserves the right to alter specications.
PARAGON VAV
Maintenance

PARAGON VAV
16 Swegon reserves the right to alter specications. 22/11/2021
Click!
Click!