manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Control Unit
  8. •
  9. System Sensor MOD400R User manual

System Sensor MOD400R User manual

M400-02-01 1 I56-511-02
MOD400R Test Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
General Description
The MOD400R Test Module is a tool testing the relative sen-
sitivity of 100, 200, 300, 400, and 500 Series smoke detec-
tors only. It CANNOT be used on 800 Series detectors. It
consists of a test module and interface cord for connecting
the module to the detector being tested.
This battery powered module is equipped with two color-
coded banana jacks for the connection of any analog or
digital DC voltmeter having a sensitivity of 10 kΩ/V or
greater. As an added convenience, two adhesive-backed
Velcro®
strips are also supplied for attaching the module to
the meter being used during testing.
Test module function is under the control of a 3-position
and a 2-position slide switch on the side of the unit. Vari-
ous combinations of positions of these two switches enable
the module to test conventional and analog ionization and
photoelectronic smoke detectors as well as checking the
battery. In addition, the 3-position switch, SW1, has a cen-
ter-OFF position for turning off the module. Therefore, con-
serve battery life by always setting this switch to OFF when
the module is not in use.
MOD400R Setup
1. Connect a voltmeter having a sensitivty of 10 kΩ/V or
greater to the banana jacks on the side of the
MOD400R. Be sure to connect the positive test lead to
the red jack and the negative lead to the black.
2. Connect the interface cord to the RJ-11 telephone jack on
the bottom edge of the module.
3. Test the MOD400R battery as described in BATTERY
TESTING.
Smoke Detector Testing
Conventional Ion
1. Prepare the MOD400R for testing by performing the pro-
cedure in MOD400R SETUP.
2. Set the voltmeter to measure at least 3 VDC.
3. Make sure that power is applied to the detector to be
tested.
4. Set SW1 to its A position and the 2-position switch, SW2,
to CONV.
5. See Figure 1. Insert the test plug into the test module
socket on the detector.
The voltmeter should display a voltage that falls in the
MOD400(R) RANGE printed on the label on the back of
A78-2075-00
CAUTION
Failure to insert and retract this plug in the direction shown
may result in damage to the pins. Handle with care. Inspect
pins regularly for damage to ensure proper operation.
the detector. This corresponds to the NOMINAL SENS.
(sensitivity) on the label.
If the voltmeter displays a voltage outside the
MOD400(R) RANGE, it indicates that the detector re-
quires cleaning or repair.
6. Disconnect the MOD400R from the detector and set SW1
to OFF.
Conventional Photoelectronic Detectors
1. Prepare the MOD400R for testing by performing the pro-
cedure in MOD400R SETUP.
2. Set the voltmeter to measure at least 3 VDC.
3. Make sure that power is applied to the detector to be
tested.
4. Set SW1 to its B position and the 2-position switch, SW2,
to CONV.
5. See Figure 1. Insert the test plug into the test module
socket on the detector.
The voltmeter should display a voltage that falls in the
MOD400(R) RANGE printed on the label on the back of
Figure 1:
M400-02-01 2 I56-511-02
© System Sensor 1996
Three-Year Limited Warranty
System Sensor warrants its enclosed MOD400R to be free from defects in
materials and workmanship under normal use and service for a period of
three years from date of manufacture. System Sensor makes no other ex-
press warranty for this MOD400R. No agent, representative, dealer, or em-
ployee of the Company has the authority to increase or alter the
obligations or limitations of this Warranty. The Company’s obligation of
this Warranty shall be limited to the repair or replacement of any part of
the MOD400R which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing
with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
the detector. This corresponds to the NOMINAL SENS.
(sensitivity) on the label.
If the voltmeter displays a voltage outside the
MOD400(R) RANGE, it indicates that the detector re-
quires cleaning or repair.
6. Disconnect the MOD400R from the detector and set SW1
to OFF.
Intelligent Sensors
NOTE: The MOD400R can be used to test the sensitivity of
only those sensors connected to control panels that
do NOT use drift compensation.
1. Prepare the MOD400R for testing by performing the pro-
cedure in MOD400R SETUP.
2. Set the voltmeter to measure at least 3 VDC.
3. Make sure that power is applied to the sensor to be
tested.
4. Set SW1 to its B position and the 2-position switch, SW2
to INT.
5. See Figure 1. Insert the test plug into the test module
socket on the detector.
The voltmeter should display a voltage that falls in the
MOD400(R) RANGE printed on the label on the back of
the sensor. This corresponds to the NOMINAL SENS.
(sensitivity) on the label.
If the voltmeter displays a voltage outside the
MOD400(R) RANGE, it indicates that the sensor re-
quires cleaning or repair.
6. Disconnect the MOD400R from the detector and set SW1
to OFF.
Battery Testing
The MOD400R operates from a single 9 volt alkaline bat-
tery whose life expectancy is approximately one year. How-
ever, it should be tested before each use of the MOD400R to
ensure accurate sensitivity measurements.
To test the battery:
1. Make sure that the MOD400R is NOT connected to any
detector or sensor.
2. Set a voltmeter having a sensitivity of at least 10 kΩ/V to
measure 9 VDC.
3. Connect the meter to the banana jacks on the side of the
MOD400R. Be sure to connect the positive lead to the
red jack and the negative lead to the black.
4. Set SW1 to its A position and read the meter. It should
indicate at least 5.5 VDC. If it does not, replace the 9 volt
alkaline battery.
The MOD400R is designed to “... assure that each smoke detector is within
its listed and marked sensitivity range ...” per NFPA 72. The MOD400R
CANNOT, however, initiate a detector/sensor alarm. Therefore, the
MOD400R meets only part of NFPA 72 testing standards.
Slight fluctuations in readings may be experienced on any device at any
given time and do not indicate a defect or sensitivity shift, provided the
reading is within the specified range. These fluctuations are to be ex-
pected.
WARNING
The Limitations of the MOD400R
The MOD400R and its associated smoke detectors/sensors contain elec-
tronic parts and, though they are designed to last over 10 years, any of
these components can fail at any time. Therefore, it is recommended to
test your smoke detectors/sensors per NFPA 72 at least semiannually.
Regular cleaning and testing of your fire detection system will measurably
reduce your product liability risks and minimize nuisance alarms.

Other System Sensor Control Unit manuals

System Sensor I4 Series User manual

System Sensor

System Sensor I4 Series User manual

System Sensor MDl Series User manual

System Sensor

System Sensor MDl Series User manual

System Sensor RR2 User manual

System Sensor

System Sensor RR2 User manual

System Sensor CZ-6 User manual

System Sensor

System Sensor CZ-6 User manual

System Sensor M502M User manual

System Sensor

System Sensor M502M User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor M500SAP User manual

System Sensor

System Sensor M500SAP User manual

System Sensor RR1 User manual

System Sensor

System Sensor RR1 User manual

System Sensor Supervised Control Module M500S User manual

System Sensor

System Sensor Supervised Control Module M500S User manual

System Sensor 500 Series User manual

System Sensor

System Sensor 500 Series User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor CR-6 Instruction Manual

System Sensor

System Sensor CR-6 Instruction Manual

System Sensor M500FP User manual

System Sensor

System Sensor M500FP User manual

System Sensor i3 Series User manual

System Sensor

System Sensor i3 Series User manual

System Sensor SpectrAlert MDL User manual

System Sensor

System Sensor SpectrAlert MDL User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor SC-6 User manual

System Sensor

System Sensor SC-6 User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor EM-1MI User manual

System Sensor

System Sensor EM-1MI User manual

System Sensor M500FP User manual

System Sensor

System Sensor M500FP User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor M502M User manual

System Sensor

System Sensor M502M User manual

System Sensor M501MAP User manual

System Sensor

System Sensor M501MAP User manual

Popular Control Unit manuals by other brands

Espressif Systems ESP32-S3-WROOM-2 user manual

Espressif Systems

Espressif Systems ESP32-S3-WROOM-2 user manual

Zamel EXTA EDM-01 instruction manual

Zamel

Zamel EXTA EDM-01 instruction manual

Pittway SYSTEM SENSOR M500FP Installation and maintenance instructions

Pittway

Pittway SYSTEM SENSOR M500FP Installation and maintenance instructions

DMP Electronics 714-D22 installation guide

DMP Electronics

DMP Electronics 714-D22 installation guide

SpeedTurtle Easy Flash Module 3.0 user manual

SpeedTurtle

SpeedTurtle Easy Flash Module 3.0 user manual

SEW-Eurodrive BST Series operating instructions

SEW-Eurodrive

SEW-Eurodrive BST Series operating instructions

Kentec Electronics XT+ operating instructions

Kentec Electronics

Kentec Electronics XT+ operating instructions

Kuhse KEA 101 NSTR Service manual

Kuhse

Kuhse KEA 101 NSTR Service manual

DTM System CHRONO quick start guide

DTM System

DTM System CHRONO quick start guide

Fike FAV Installation and maintenance instructions

Fike

Fike FAV Installation and maintenance instructions

Laserworld RED-3000/658 user manual

Laserworld

Laserworld RED-3000/658 user manual

Watts LFM127-3 Installation, operation and maintenance

Watts

Watts LFM127-3 Installation, operation and maintenance

LUMINELL DL Series user manual

LUMINELL

LUMINELL DL Series user manual

StepperOnline MA860H user manual

StepperOnline

StepperOnline MA860H user manual

B&R 8BVI0014HWD0.000-1 datasheet

B&R

B&R 8BVI0014HWD0.000-1 datasheet

BFT PERSEO CBE quick start guide

BFT

BFT PERSEO CBE quick start guide

Mini-Circuits U2C-1SP2T-63VH user guide

Mini-Circuits

Mini-Circuits U2C-1SP2T-63VH user guide

Wecon LX3V-4AD Wiring diagram

Wecon

Wecon LX3V-4AD Wiring diagram

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.