manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Control Unit
  8. •
  9. System Sensor SpectrAlert MDL User manual

System Sensor SpectrAlert MDL User manual

Other System Sensor Control Unit manuals

System Sensor i3 Series User manual

System Sensor

System Sensor i3 Series User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor CZ-6 User manual

System Sensor

System Sensor CZ-6 User manual

System Sensor Supervised Control Module M500S User manual

System Sensor

System Sensor Supervised Control Module M500S User manual

System Sensor M500S User manual

System Sensor

System Sensor M500S User manual

System Sensor M210EA-CZ User manual

System Sensor

System Sensor M210EA-CZ User manual

System Sensor M500RAP User manual

System Sensor

System Sensor M500RAP User manual

System Sensor M902M User manual

System Sensor

System Sensor M902M User manual

System Sensor RR2 User manual

System Sensor

System Sensor RR2 User manual

System Sensor CR-6 Instruction Manual

System Sensor

System Sensor CR-6 Instruction Manual

System Sensor M502MA User manual

System Sensor

System Sensor M502MA User manual

System Sensor MDl Series User manual

System Sensor

System Sensor MDl Series User manual

System Sensor EM-1SRI User manual

System Sensor

System Sensor EM-1SRI User manual

System Sensor M502M User manual

System Sensor

System Sensor M502M User manual

System Sensor 500 Series User manual

System Sensor

System Sensor 500 Series User manual

System Sensor M500SA User manual

System Sensor

System Sensor M500SA User manual

System Sensor MDL3 Series User manual

System Sensor

System Sensor MDL3 Series User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor 500 Series User manual

System Sensor

System Sensor 500 Series User manual

System Sensor SC-6 User manual

System Sensor

System Sensor SC-6 User manual

System Sensor MOD400R User manual

System Sensor

System Sensor MOD400R User manual

System Sensor MDL3W User manual

System Sensor

System Sensor MDL3W User manual

System Sensor M500FP User manual

System Sensor

System Sensor M500FP User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Specifications
Input Voltage Range: DC or Full Wave Rectified
9 to 33 Volts
Maximum Load on Loop: 3 A
Current:
Operating Temperature: 0°C to 49°C (32°F to 120°F)
Listings: UL S4011, S5512
Note for Strobes – Do not exceed: 1) 9-17.5 or 17-33 voltage range limits when the MDL module is used; 2) Maximum
number of strobe lights and/or maximum line impedance specified in the strobe product installation manual; and 3) Max-
uimum line impedence as required by the fire alarm control manufacturer.
D900-14-00 1 I56-0983-015R
MDL Module
For use with the following series models:
P2RX, P2WX, P4RX, P4WX, SRX, SWX, SCRX, SCWX, HRX, HWX, CHX, CHRX, CHWX, CHSRX, CHSWX,
PC2RX, PC2WX, PC4RX, PC4WX, H12/24X, HC12/24X, PA400X, S1224MCX, SC24XX, P1224MCX, PC24XX,
SP2C24XX, SP2R1224MCX, SP2W1224MCX, CH24MCX, MHR(A), MHW(A), MHRZA, MHWZA
Refer to System Sensor product installation manuals for model specifications.
U.S. Patent Nos. 5,850,178 and 5,598,139
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
General Description
The MDL Module is designed to work with the SpectrAlert
series of notification appliances to provide a means of
synchronizing the temporal-coded horns and chimes, syn-
chronizing the one-second flash timing of the strobe, and
silencing the horns and chimes of the horn/strobe and
chime/strobes combination over a two-wire circuit while
leaving the strobes active.
NOTICE: This manual shall be left with the owner/user of
this equipment.
Module Configuration
Each MDL module has the capability of connecting two
Style Y (Class B) circuits or one Style Z (Class A) circuit.
The zone output(s) from the panel are connected to the zone
input(s) of the MDL module and the zone output(s) from
the MDL module are connected to the notification loop(s).
Supervision is accomplished in the module by a direct con-
nection between the zone input and the zone output of each
of the two zone circuits connected to the normal end-of-line
device. The FACP “sees” the EOL device through the MDL
module. When either or both outputs from the module are
wired to the SpectrAlert products, the horns or chimes and
strobes in both zones will be synchronized.
The MDL module can be configured so that more than two
zones can be synchronized by the interconnection of the
slave input and output (see Figures 1 and 2).
Zone 1 Input: This input powers the MDL module. This
input must have voltage present from the FACP
before anything will work. This also supplies
voltage to Zone 1 output.
Zone 2 Input: This input only supplies voltage to Zone 2
output. Note: If Zone 1 input is not powered,
the notification devices attached to the Zone 2
output will not be powered.
Horn Control: This input enables the horns on the SpectrAlert
notification appliances. Voltage present means
horns are enabled. No voltage present means
horns are disabled.
Slave In: Connects to Master MDL Module slave out.
Slave Out: Connects to Slave MDL slave in.
Voltage Average Peak In-rush
DC FWR DC FWR DC FWR
12 V 10mA 12mA 30mA 31mA 87mA 122mA
24 V 12mA 15mA 35mA 37mA 198mA 262mA
CAUTION
When MDL module is used, supply volt-
age range at 12 volts: 9 to 17.5 VDC; at 24
volts: 17 to 33 VDC
I56-0983-015R
firealarmresources.com
Figure 1: Single MDL Using Sync Error (for panels
with the capability to check for sync error)
NOTE: If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.
TEMP. JUMPER OFF
NAC2
NAC1
FACP
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL
ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
SEPARATE
MONITORING
INPUT
EOL
A0262-00
Figure 2:
NOTE: If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.
TO NEXT
SPECTRALERT
DEVICE OR
EOL
NAC3
NAC2
MASTER MODULE
SLAVE MODULE
NAC1
TO NEXT
SPECTRALERT
DEVICE OR
EOL
All SpectrAlert horns,
horn/strobes, and strobes
will operate in sync.
NAC2
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORNS SILENCED OVER TWO WIRE CIRCUIT
MASTER MODULE HORN CONTROL CONNECTS
TO INTERRUPTABLE POWER SOURCE
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL
TEMP JUMPER OFF
ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
TEMP JUMPER OFF
FACP #1
FACP #2
TO NEXT
SPECTRALERT
DEVICE OR
EOL
TO NEXT
SPECTRALERT
DEVICE OR
EOL
NAC1
(+)
(–)
EOL
A0182-00
D900-14-00 2 I56-0983-015R
Synchronize SpectrAlert Horns, Chimes and Strobes
• Each module can power two 3-amp circuits wired in
class B or one 3-amp circuit powered as Class A.
•Each module will synchronize 2 zones.
• Additional modules can be added and may be syn-
chronized to all other modules by interconnecting the
“slave” input and output terminals between modules.
CAUTION
Horn control wiring must be contained within common en-
closure of module.
CAUTION
Slave Out – Slave In wiring must be contained within either
the common enclosure of modules or enclosures within 20
feet of each other with wiring inside conduit.
CAUTION
If Zone 1 input is not powered or fails during alarm, the
notification devices attached to the Zone 2 output will not
be powered.
Controlling Sounder On/Off Over 2-Wires Using Mod-
ule Horn Control
•Connect the current source to the horn or chime control
input. If a zone output is used for the source, you must
use an EOL on the horn control input terminal.
• When multiple modules are used, the horn or chime
control circuits can be wired in parallel. If wired in par-
allel and a zone output is used from panel, use an EOL
on the last module for supervision.
CAUTION
Horn/chime control wiring must be contained within com-
mon enclosure of module.
CAUTION
Slave Out – Slave In wiring must be contained within either
the common enclosure of modules or enclosures within 20
feet of each other with wiring inside conduit.
CAUTION
If Zone 1 input is not powered or fails during alarm, the
notification devices attached to the Zone 2 output will not
be powered.
Special Considerations
A latching relay contact is provided in case the synchro-
nizing signal to the notification devices is interrupted. The
output can be wired so that a trouble signal will be annun-
ciated at the panel. If the synchronization pulse fails in the
MDL module, the strobes will shut off.
firealarmresources.com
Figure 5: Wiring for Coded Supplies
HORN
POWER
STROBE
POWER
MULTI CODE
SOURCE
ANY SPECTRALERT
HORN STROBE
TO NEXT
HORN POWER
OR EOL
SPECTRALERT
HORN ONLY
}
TO NEXT
DEVICE
OR EOL
}
MDL
HC
Z1
IN OUT
NOTE: Horn/chime control must be powered for horn/
strobes to operate the horn portion.
NOTE: SpectrAlert horn-only/chime-only and horn/strobe
or chime/strobe devices must be set non-temporal for
multi-code sourcing.
Temporal Coding on horns that produce a continuous
tone (Non-SpectrAlert Horns)
See Figure 6
•Program module to provide temporal coding by inserting
jumper plug per instructions.
• Connect only sounders producing a continuous tone to
the module zone output(s).
CAUTION
Strobes cannot be used on a module providing temporal coding
to horns. Strobes must be wired for independent operation.
NOTE: Temporal jumper should be inserted across both
pins only on non-SpectrAlert products that are to be pow-
ered for temporal sound output.
Figure 6:
NOTE: If zone 1 output of module is connected to strobes or
horn/strobes, or chime/strobes zone 1 input supply power
must be continuous for proper operation.
Horns will be Temporal
coded and in sync.
TEMP. JUMPER ON
TO NEXT
DEVICE OR
EOL
TO NEXT
DEVICE OR
EOL
NAC2
NAC1
FACP
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
MA12/24D
OR PA400
HORN
ONLY
MA12/24D
OR PA400
HORN
ONLY
NOTE: The MDL Module is factory set with the sync error
contacts in the open state. These contacts may close during
shipping. Approximately two seconds after power-up, these
contacts will open.
NOTE: This contact could be wired to a separate monitor-
ing input at FACP.
Figure 3:
NOTE: If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.
MASTER MODULE
SLAVE MODULE
TO NEXT
DEVICE OR
EOL
TO NEXT
DEVICE OR
EOL
All SpectrAlert horns,
horn/strobes, and strobe
only devices will
operate in sync.
NOTE: The panel (or FACP) must be capable of providing Style Z (Class A)
notification (or NAC) circuitry. Consult with panel manufacturer.
NAC2
NAC1
FACP
NAC3 OUT
NAC4 RETURN
TO NEXT
DEVICE OR
EOL
TO NEXT
DEVICE OR
EOL
STYLE Z
(CLASS A)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
2 STYLE Y (CLASS B)
1 STYLE Z (CLASS A)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
Temp. Jumper Off
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
ZONE 2
OUT
SLAVE
OUT
Temp. Jumper Off
SYNC
ERROR
Figure 4: Multiple Devices Using Sync Error
NOTE: If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.
TEMP. JUMPER OFF
NAC2
NAC1
FACP
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL
ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
SEPARATE
MONITORING
INPUT
TEMP. JUMPER OFF
NAC4
NAC3
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORN
CONTROL
ZONE 1
OUT
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
MODULE 1
MODULE 2
EOL
D900-14-00 3 I56-0983-015R
A0263-00
A0265-00
A0186-00
A0181-00
firealarmresources.com
D900-14-00 4 I56-0983-015R
©2005 System Sensor
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in materi-
als and workmanship under normal use and service for a period of three years
from date of manufacture. System Sensor makes no other express warranty
for the enclosed product. No agent, representative, dealer, or employee of the
Company has the authority to increase or alter the obligations or limitations
of this Warranty. The Company’s obligation of this Warranty shall be limited
to the replacement of any part of the product which is found to be defective
in materials or workmanship under normal use and service during the three
year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to replace units which are found to be
defective because of damage, unreasonable use, modifications, or alterations
occurring after the date of manufacture. In no case shall the Company be
liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage
is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you specific
legal rights, and you may also have other rights which vary from state to state.
The sounder and/or strobe will not work without power. The sounder/strobe
gets its power from the fire/security panel monitoring the alarm system. If power
is cut off for any reason, the sounder/strobe will not provide the desired audio or
visual warning.
The sounder may not be heard. The loudness of the sounder meets (or exceeds)
current Underwriters Laboratories’ standards. However, the sounder may not alert
a sound sleeper or one who has recently used drugs or has been drinking alcoholic
beverages. The sounder may not be heard if it is placed on a different floor from the
person in hazard or if placed too far away to be heard over the ambient noise such
as traffic, air conditioners, machinery or music appliances that may prevent alert
persons from hearing the alarm. The sounder may not be heard by persons who are
hearing impaired.
The signal strobe may not be seen. The electronic visual warning signal uses an
extremely reliable xenon flash tube. It flashes at least once every three seconds and
exceeds current Underwriters Laboratories standards for private mode viewing. The
visual warning signal is suitable for direct viewing and must be installed within an
area where it can be seen by building occupants. The strobe must not be installed in
direct sunlight or areas of high light intensity (over 60 foot candles) where the visual
flash might be disregarded or not seen. The strobe may not be seen by the visually
impaired and is not intended to meet American Disabilities Act (ADA) requirements.
The signal strobe may cause seizures. Individuals who have positive photic re-
sponse to visual stimuli with seizures, such as persons with epilepsy, should avoid
prolonged exposure to environments in which strobe signals, including this strobe,
are activated.
The signal strobe cannot operate from coded power supplies. Coded power sup-
plies produce interrupted power. The strobe must have an uninterrupted source of dc
power in order to operate correctly. System Sensor recommends that the sounder and
signal strobe always be used in combination so that the risks from any of the above
limitations are minimized.
WARNING
The Limitations of Sounder/Strobes
A
A
Figure 6: Mounting Diagram
1. Complete field wiring.
2. Mount unit to 411/16˝ backbox with screws A.
A0266-00
Please refer to insert for the Limitations of Fire Alarm Systems
firealarmresources.com