manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Control Unit
  8. •
  9. System Sensor M500RAP User manual

System Sensor M500RAP User manual

1 I56-6789-001
04/26/2022
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The M500RAP Relay Control Module is intended for use in intelligent, two-
wire systems where the individual address of each module is selected using
the built-in rotary switches. It allows a compatible control panel to switch
discrete contacts by code command. The relay contains two isolated sets of
Form-C contacts, which operate as a DPDT switch and are rated in accordance
with the table in the manual. Circuit connections to the relay contacts are
not supervised by the module. The module also has a panel controlled LED
indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
system control panel only.
FIGURE 1. CONTROLS, INDICATORS, AND TERMINAL DEFINITIONS
RELAY COMMON 2
NORMALLY CLOSED 2
NORMALLY OPEN 2
RELAY COMMON 1
NORMALLY CLOSED 1
NORMALLY OPEN 1
COMMUNICATION
LINE (NEGATIVE)
COMMUNICATION
LINE (POSITIVE)
C2241-01
Note: For legacy terminal designations, see Figure 4.
I56-6789-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5 mA (LED on)
Average Operating Current: 230μA direct poll; 255μA group poll
EOL Resistance: Not used
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.675" H x 4.275" W x 1.4" D (119 mm H x 108 mm W x 36 mm D) (Mounts to a 4" square by 21
/8" deep box.)
Accessories: SMB500 Series Electrical Box
NOTE: The control module is manufactured using two configurations. Both variants offer the same functionality. Reference the section of the manual that reflects
the terminal alignment on the module you are using.
MOUNTING
The M500RAP mounts directly to 4-inch square electrical boxes. (See Figure
2). The box must have a minimum depth of 21
/8inches (54 mm). Surface
mounted electrical boxes (SMB500-WH) are available from System Sensor.
The module can also mount to the DNR(W) duct housing.
FIGURE 2. MODULE MOUNTING
C2250-00
M500RAP Relay Control Module
RELAY CONTACT RATINGS
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
3825 Ohio Avenue, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
2 I56-6789-001
©2022 System Sensor. 04/26/2022
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer). See Figure 2.
Wire should be stripped to the appropriate length (recommended strip length
is 1/4" to 3/8") (6 mm to 10 mm). Exposed conductor should be secured under
the clamping plate and should not protrude beyond the terminal block area.
FIGURE 3. RELAY MODULE WIRING DIAGRAM
SIGNAL LINE CIRCUIT(SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
FROM PANEL OR
PREVIOUS DEVICE
RELAY COMMON 2
NORMALLY CLOSED 2
NORMALLY OPEN 2
RELAY COMMON 1
NORMALLY CLOSED 1
NORMALLY OPEN 1
MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS
RELAY MODULE
TO NEXT
DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
(-)
(+)
(-)
(+)
(-)
(+)
C2251-00
FIGURE 4. RETROFIT TERMINAL DESIGNATIONS FOR LEGACY M500RAP
COMM 2
NORMALLY CLOSED 2
NORMALLY OPEN 2
COMM 1
NORMALLY CLOSED 1
COMMUNICATION
LINE (NEGATIVE)
COMMUNICATION
LINE (POSITIVE)
UNUSED
NORMALLY OPEN 1
C1071-01
NOTE: Refer to pages 3 and 4 of this instruction manual for complete information regarding the legacy M500RAP configuration.
CAUTION
Caution: Do not loop wire under terminals. Break wire run to provide supervi-
sion of connections.
NOTE: Dispose electronic waste following national and/or local regulations.
WARNING
All relay switch contacts are shipped in the standby state (open) state, but
may have transferred to the activated (closed) state during shipping. To en-
sure that the switch contacts are in their correct state, modules must be made
to communicate with the panel before connecting circuits controlled by the
module.
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which is
found to be defective in materials or workmanship under normal use and service during
the three year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: Honeywell, 12220 Rojas Drive, Suite 700, El Paso
THREE-YEAR LIMITED WARRANTY
TX 79936 USA. Please include a note describing the malfunction and suspected cause of
failure. The Company shall not be obligated to replace units which are found to be defec-
tive because of damage, unreasonable use, modifications, or alterations occurring after
the date of manufacture. In no case shall the Company be liable for any consequential
or incidental damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential dam-
ages, so the above limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary from state to state.
System Sensor® is a registered trademark of Honeywell International, Inc.
3 I56-6789-001
04/26/2022
I56-6789-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
M500RAP Relay Control Module
(Legacy M500RAP)
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5 mA (LED on)
Average Operating Current: 300 μA, 1 communication every 5 seconds
EOL Resistance: Not used
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.675" H x 4.275" W x 1.4" D (119 mm H x 108 mm W x 36 mm D) (Mounts to a 4" square by 21
/8" deep box.)
Accessories: SMB500 Electrical Box; CB500 Barrier
NOTE: The control module is manufactured using two configurations. Both variants offer the same functionality. Reference the section of the manual that reflects
the terminal alignment on the module you are using.
RELAY CONTACT RATINGS
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The M500RAP Relay Control Module is intended for use in intelligent, two-
wire systems, where the individual address of each module is selected using
the built-in rotary decade switches. It allows a compatible control panel to
switch discrete contacts by code command. The relay contains two isolated
sets of Form-C contacts, which operate as a DPDT switch and are rated in
accordance with the table in the manual. Circuit connections to the relay con-
tacts are not supervised by the module. The module also has a panel con-
trolled LED indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed com-
patible system control panels only.
FIGURE 1. CONTROLS AND INDICATORS:
C0925-01
MOUNTING
The M500RAP mounts directly to 4˝ square electrical boxes (see Figure 2A).
The box must have a minimum depth of 21
/8”. Surface mounted electrical
boxes (SMB500) are available from System Sensor.
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
FIGURE 2A. MODULE MOUNTING FIGURE 2B.
WITH BARRIER:
ISOLATED
QUA DRANT
C0926-01
C0927-01
FIGURE 3. RELAY MODULE WIRING DIAGRAM
MODULE
FROM PANEL OR
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
(+)
(–)
CONTROL
CONNECT MODULES TO LISTED COMPATIBLE
RELAY COMMON 1
RELAY COMMON 2
NORMALLY CLOSED 1
NORMALLY OPEN 2
NORMALLY CLOSED 2
MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS
NORMALLY OPEN 1
CONTROL PANELS ONLY
PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
UNUSED
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
IF ANY WIRING TO TERMINALS 4 – 10 IS NONPOWER
LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500
INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST
BE PLACED OVER THE POWER LIMITED TERMINAL
INFORMATION ON THE NAMEPLATE LABEL.
C0924-03
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
System Sensor CB500 Module Barrier must be used to meet UL requirements
for the separation of power-limited and nonpower-limited terminals and wir-
ing. The barrier must be inserted into a 4”× 4”× 21
/8” junction box, and the
control module must be placed into the barrier and attached to the junction
box (Figure 2A). The power-limited wiring must be placed into the isolated
quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer),as shown in Fig-
ure 2A.
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
4 I56-6789-001
©2022 System Sensor. 04/26/2022
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which is
found to be defective in materials or workmanship under normal use and service during
the three year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: Honeywell, 12220 Rojas Drive, Suite 700, El Paso
THREE-YEAR LIMITED WARRANTY
TX 79936 USA. Please include a note describing the malfunction and suspected cause of
failure. The Company shall not be obligated to replace units which are found to be defec-
tive because of damage, unreasonable use, modifications, or alterations occurring after
the date of manufacture. In no case shall the Company be liable for any consequential
or incidental damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential dam-
ages, so the above limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary from state to state.

Other System Sensor Control Unit manuals

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor CZ-6 User manual

System Sensor

System Sensor CZ-6 User manual

System Sensor M500FP User manual

System Sensor

System Sensor M500FP User manual

System Sensor EM-1MI User manual

System Sensor

System Sensor EM-1MI User manual

System Sensor MDL3 Series User manual

System Sensor

System Sensor MDL3 Series User manual

System Sensor M500SA User manual

System Sensor

System Sensor M500SA User manual

System Sensor i3 Series User manual

System Sensor

System Sensor i3 Series User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor CR-6 Instruction Manual

System Sensor

System Sensor CR-6 Instruction Manual

System Sensor M502M User manual

System Sensor

System Sensor M502M User manual

System Sensor M500DMR User manual

System Sensor

System Sensor M500DMR User manual

System Sensor M500S User manual

System Sensor

System Sensor M500S User manual

System Sensor M502M User manual

System Sensor

System Sensor M502M User manual

System Sensor SC-6 User manual

System Sensor

System Sensor SC-6 User manual

System Sensor M902M User manual

System Sensor

System Sensor M902M User manual

System Sensor Supervised Control Module M500S User manual

System Sensor

System Sensor Supervised Control Module M500S User manual

System Sensor SC-6 User manual

System Sensor

System Sensor SC-6 User manual

System Sensor I4 Series User manual

System Sensor

System Sensor I4 Series User manual

System Sensor SpectrAlert MDL User manual

System Sensor

System Sensor SpectrAlert MDL User manual

System Sensor M501MAP User manual

System Sensor

System Sensor M501MAP User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor MDL3W User manual

System Sensor

System Sensor MDL3W User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor RR1 User manual

System Sensor

System Sensor RR1 User manual

Popular Control Unit manuals by other brands

Espressif Systems ESP32-S3-WROOM-2 user manual

Espressif Systems

Espressif Systems ESP32-S3-WROOM-2 user manual

Zamel EXTA EDM-01 instruction manual

Zamel

Zamel EXTA EDM-01 instruction manual

Pittway SYSTEM SENSOR M500FP Installation and maintenance instructions

Pittway

Pittway SYSTEM SENSOR M500FP Installation and maintenance instructions

DMP Electronics 714-D22 installation guide

DMP Electronics

DMP Electronics 714-D22 installation guide

SpeedTurtle Easy Flash Module 3.0 user manual

SpeedTurtle

SpeedTurtle Easy Flash Module 3.0 user manual

SEW-Eurodrive BST Series operating instructions

SEW-Eurodrive

SEW-Eurodrive BST Series operating instructions

Kentec Electronics XT+ operating instructions

Kentec Electronics

Kentec Electronics XT+ operating instructions

Kuhse KEA 101 NSTR Service manual

Kuhse

Kuhse KEA 101 NSTR Service manual

DTM System CHRONO quick start guide

DTM System

DTM System CHRONO quick start guide

Fike FAV Installation and maintenance instructions

Fike

Fike FAV Installation and maintenance instructions

Laserworld RED-3000/658 user manual

Laserworld

Laserworld RED-3000/658 user manual

Watts LFM127-3 Installation, operation and maintenance

Watts

Watts LFM127-3 Installation, operation and maintenance

LUMINELL DL Series user manual

LUMINELL

LUMINELL DL Series user manual

StepperOnline MA860H user manual

StepperOnline

StepperOnline MA860H user manual

B&R 8BVI0014HWD0.000-1 datasheet

B&R

B&R 8BVI0014HWD0.000-1 datasheet

BFT PERSEO CBE quick start guide

BFT

BFT PERSEO CBE quick start guide

Mini-Circuits U2C-1SP2T-63VH user guide

Mini-Circuits

Mini-Circuits U2C-1SP2T-63VH user guide

Wecon LX3V-4AD Wiring diagram

Wecon

Wecon LX3V-4AD Wiring diagram

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.