SS-460-001 1 I56-3194-000
M500SA Supervised Control Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5
1-800-SENSOR2, FAX: 905-812-0771-
www.systemsensor.ca
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
M500SA Supervised Control Modules are intended for use in intelligent, two-
wire systems, where the individual address of each module is selected using
the built-in rotary decade switches. This module is used to switch an external
power supply, which can be a DC power supply or an audio amplifier (up
to 80 VRMS), to notification appliances. It also supervises the wiring to the
connected loads and reports their status to the panel as NORMAL, OPEN,
or SHORT CIRCUIT. The M500SA has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator. This
module can be used to replace an M500CA module that has been configured
for supervised wiring operation.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed com-
patible system control panels only.
FIGURE 1. CONTROLS AND INDICATORS:
C0909-01
MOUNTING
The M500SA mounts directly to 4-inch square electrical boxes (see Figure
2A). The box must have a minimum depth of 21/8inches. Surface mounted
electrical boxes (SMB500) are available from System Sensor.
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5mA (LED On)
Operating Current: 350 µA max., 1 communication every 5 seconds 47k EOL resistor; 485 µA max. (Communicating, NAC Shorted)
Maximum NAC Line Loss: 4 VDC
External Supply Voltage (between Terminals T3 and T4)
Maximum (NAC): Regulated 24VDC
Maximum (Speakers): 70.07 V RMS, 50 W
Max. NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41/2˝ H × 4˝ W × 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box; CB500 Barrier
FIGURE 2A. MODULE MOUNTING FIGURE 2B:
WITH BARRIER:
ISOLATED
QUADRANT
C1050-00
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. When using control modules in nonpower limited applications,
the System Sensor CB500 Module Barrier must be used to meet UL require-
ments for the separation of power-limited and nonpower-limited terminals and
wiring. The barrier must be inserted into a 4˝×4˝×21/8˝ junction box, and the
control module must be placed into the barrier and attached to the junction
box (Figure 2A). The power-limited wiring must be placed into the isolated
quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in Fig-
ure 2A.
SS-460-001 2 I56-3194-000
FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y:
(+)
(+)
(+)
(+)
(+)
(+)
47K EOL
RESISTOR
ELR-47K
ULC LISTED EOL RELAY
SHOWN ENERGIZED
24 VDC COIL EOLR-1A
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE RUN TO
PROVIDE SUPERVISION OF CONNECTIONS.
TO NEXT CONTROL MODULE OR END-OF-LINE RELAY.
ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT
REQUIRE EXTERNAL WIRING. REFER TO PANEL MANUAL.
24 VDC POWER SUPPLY
ISOLATED, REGULATED, POWER
LIMITED PER NFPA 70. LISTED FOR
FIRE PROTECTION WITH BATTERY
BACKUP.
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO
LISTED COMPATIBLE CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED AND
POWER LIMITED
CONTROL
MODULE
FROM PANEL
OR PREVIOUS
DEVICE
TO NEXT
DEVICE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED
TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN
A SEPARATE ZONE.
(−)
(−)
(−)
(−)(−)
(−)
C0913-05
FIGURE 4. TYPICAL FAULT TOLERANT NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Z:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
ALL WIRING SHOWN IS SUPERVISED AND
POWER LIMITED
MODULE POLARITIES ARE
SHOWN IN ALARM
EOL RESISTOR IS
INTERNAL AT
TERMINALS
8 & 9
ULC LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1A
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT. SOME
CONTROL PANELS HAVE RELAY BUILT IN
AND DO NOT REQUIRE EXTERNAL
WIRING. REFER TO PANEL MANUAL.
CONTROL
MODULE
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX. TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM PANEL
OR
PREVIOUS
DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK
WIRE RUN TO PROVIDE SUPERVISION OF
CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED, POWER
LIMITED PER NFPA 70. LISTED FOR FIRE
PROTECTION WITH BATTERY BACKUP.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED
TO THAT ZONE AND DOES NOT RESULT IN A FAULT
IN A SEPARATE ZONE.
C0914-05
SS-460-001 3 I56-3194-000
FIGURE 5. TYPICAL WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Y:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 &
11. BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
WIRES MUST BE SUPERVISED
PER ULC
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
FROM PANEL OR
PREVIOUS DEVICE
CONTROL
MODULE
47K EOL
RESISTOR
ELR-47K
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION.
REFER TO THE RELAY CONTACT RATING TABLE FOR
MAXIMUM LOAD.
TO NEXT
DEVICE
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT CONTROL MODULE LAST
MODULE MUST RETURN WIRES FOR
SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
AMPLIFIER MUST PROVIDE WIRING
SUPERVISION PER NFPA.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0915-03
FIGURE 6. TYPICAL FAULT TOLERANT WIRING FOR SPEAKER SUPERVISION AND SWITCHING, NFPA STYLE Z:
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
ALL WIRING SHOWN IS SUPERVISED AND
POWER LIMITED
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
WIRES MUST BE SUPERVISED
PER ULC
CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY
FROM PANEL
OR PREVIOUS
DEVICE
CONTROL
MODULE
SPEAKERS MUST BE LISTED FOR FIRE
PROTECTION. REFER TO THE RELAY
CONTACT RATING TABLE FOR MAXIMUM
LOAD.
47K EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT CONTROL MODULE LAST
MODULE MUST RETURN WIRES FOR
SUPERVISION
SUPERVISION
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION.
AUDIO AMPLIFIER, 70.7 Vrms MAX.
AMPLIFIER MUST PROVIDE WIRING
SUPERVISION PER NFPA.
AUDIO CIRCUIT
DO NOT LOOP WIRE AROUND TERMINALS 10 & 11.
BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
BYPASS CAPACITORS: 100µ
A2143-20 NONPOLARIZED
<10µA LEAKAGE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0916-03
SS-460-001 4 I56-3194-000
©2007 System Sensor
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed module to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this module. No
agent, representative, dealer, or employee of the Company has the authority to increase
or alter the obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the module which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Repair Department,
RA #__________, 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5. Please
include a note describing the malfunction and suspected cause of failure. The Company
shall not be obligated to repair or replace units which are found to be defective because
of damage, unreasonable use, modifications, or alterations occurring after the date of
manufacture. In no case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault. Some states
do not allow the exclusion or limitation of incidental or consequential damages, so the
above limitation or exclusion may not apply to you. This Warranty gives you specific legal
rights, and you may also have other rights which vary from state to state.
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

Other System Sensor Control Unit manuals

System Sensor i3 Series User manual

System Sensor

System Sensor i3 Series User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor M502M User manual

System Sensor

System Sensor M502M User manual

System Sensor SC-6 User manual

System Sensor

System Sensor SC-6 User manual

System Sensor EM-1MI User manual

System Sensor

System Sensor EM-1MI User manual

System Sensor RR1 User manual

System Sensor

System Sensor RR1 User manual

System Sensor EM-1SRI User manual

System Sensor

System Sensor EM-1SRI User manual

System Sensor SC-6 User manual

System Sensor

System Sensor SC-6 User manual

System Sensor SpectrAlert MDL User manual

System Sensor

System Sensor SpectrAlert MDL User manual

System Sensor MDl Series User manual

System Sensor

System Sensor MDl Series User manual

System Sensor Supervised Control Module M500S User manual

System Sensor

System Sensor Supervised Control Module M500S User manual

System Sensor M502MA User manual

System Sensor

System Sensor M502MA User manual

System Sensor M210EA-CZ User manual

System Sensor

System Sensor M210EA-CZ User manual

System Sensor SC-6 User manual

System Sensor

System Sensor SC-6 User manual

System Sensor M500DMR User manual

System Sensor

System Sensor M500DMR User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor M500M User manual

System Sensor

System Sensor M500M User manual

System Sensor M210EA-CZR User manual

System Sensor

System Sensor M210EA-CZR User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

System Sensor M210E User manual

System Sensor

System Sensor M210E User manual

System Sensor 500 Series User manual

System Sensor

System Sensor 500 Series User manual

System Sensor M902M User manual

System Sensor

System Sensor M902M User manual

System Sensor CZ-6 User manual

System Sensor

System Sensor CZ-6 User manual

System Sensor IM-10 User manual

System Sensor

System Sensor IM-10 User manual

Popular Control Unit manuals by other brands

GEM 532Z operating instructions

GEM

GEM 532Z operating instructions

Vag EKN Operation and maintenance instructions

Vag

Vag EKN Operation and maintenance instructions

Puls YR40.482 installation manual

Puls

Puls YR40.482 installation manual

GEA DHV DN65/50 KVS 16 operating instructions

GEA

GEA DHV DN65/50 KVS 16 operating instructions

agiliti Adapt Quick reference guide

agiliti

agiliti Adapt Quick reference guide

PVA MV250 Operation manual

PVA

PVA MV250 Operation manual

ABB 615 Series ANSI manual

ABB

ABB 615 Series ANSI manual

Triax TDH 800 user guide

Triax

Triax TDH 800 user guide

rada Pulse Series product manual

rada

rada Pulse Series product manual

KSB AMTRONIC R1300 User instructions

KSB

KSB AMTRONIC R1300 User instructions

Huawei MU609T manual

Huawei

Huawei MU609T manual

CALEFFI LEGIOMIX 600094A Installation and commissioning manual

CALEFFI

CALEFFI LEGIOMIX 600094A Installation and commissioning manual

Sun Microsystems Sun Blade X6270 Safety and compliance guide

Sun Microsystems

Sun Microsystems Sun Blade X6270 Safety and compliance guide

Hikmicro Mini2 quick start guide

Hikmicro

Hikmicro Mini2 quick start guide

Siemens multiranger 200 Application guide

Siemens

Siemens multiranger 200 Application guide

Laird BL600-SA Hardware integration guide

Laird

Laird BL600-SA Hardware integration guide

Hypex Electronics UcD Supply HG Mono user manual

Hypex Electronics

Hypex Electronics UcD Supply HG Mono user manual

BYD P6K Series INSTALLATION MANUAL AND USER MANUAL

BYD

BYD P6K Series INSTALLATION MANUAL AND USER MANUAL

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.