1 I56-2877-006R
06-10
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MP120K 120 VAC Adapter Mounting Plate
SPECIFICATIONS
General Specifications
Standard Operating Temperature: –40°F to 151°F (–40°C to 66°C)
Humidity Range: 10 to 93% non-condensing (indoor products)
Nominal Voltage: Regulated 120 VAC
Operating Voltage Range: 96-132 VAC
Current Draw From AC Line: 150 mA max.
MP120K may be used with any of the following products, at all horn and strobe settings:
P2R, P2RH, P2RK, P2RHK, P2W, P2WH, SR, SRH, SRK, SRHK, SW, SWH, PC2R, PC2RH, PC2RK, PC2RHK, PC2W, PC2WH, SCR, SCRH, SCRK, SCRHK, SCW,
SCWH, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P, P2R-P, P2W-P, P2RH-P, P2WH-P, SCR-P, SCW-P, SCRH-P, SCWH-P, PC2R-P, PC2W-P, PC2RH-P, PC2WH-P,
SR-SP, SRH-SP, P2R-SP, P2RH-SP, SCW-SP, SCWH-SP, PC2W-SP, PC2WH-SP, CHR, CHW, CHSR, CHSW
GENERAL DESCRIPTION
The MP120K mounting plate is designed to allow the use of 120 VAC to power
SpectrAlert Advance horns, strobes, horns/strobes, chimes, and chime/
strobes. The MP120K consists of a SpectrAlert Advance mounting plate that
has been fitted with a power supply that converts 120VAC to nominal 24V
FWR.
The MP120K must be installed using a 120 VAC power source. This unit
can only be used for non-synchronous applications; it will NOT work with
SpecrtAlert Sync•Circuit Modules.
NOTICE: This manual shall be left with the owner/user of this equipment.
WIRING
This module has pig-tail wires and is intended to be wired without rigid con-
nections inside a standard electrical box.
Horn Horn/strobe Strobe Only
Two Wire System
An
y Mix of Models
Wired for Tandem
Operation
120 VAC
Power
A0356-00
I56-2877-006R
FIGURE 1. NON-SYNCHRONIZED DEVICES; ANY COMBINATION OF MODELS POWERED BY A 2-WIRE CIRCUIT.
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
firealarmresources.com
2 I56-2877-006R
©2016 System Sensor. 06-10
MOUNTING
FIGURE 2.
MOUNTING (WALL OR CEILING)
1. For indoor applications, attach the mounting plate as shown in Figure 2.
The mounting plate is compatible only with 4 × 4 electrical boxes.
2. Connect field wiring. (For indoor models only)
3. If the product is not to be installed at this point, use the paint cover to
prevent contamination of the mounting plate.
4. To attach product to mounting plate, remove the paint cover, then hook
tabs on the product housing into the grooves on mounting plate.
5. Then, swing product into position to engage the pins on the product with
the terminals on the mounting plate. Make sure that the tabs on the back
of the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front
of the product housing. For tamper resistance, the standard captivated
mounting screw may be replaced with the enclosed Torx screw.
K SERIES MOUNTING
1. K Series products may be used indoors or outdoors. They must be in-
stalled using the proper SpectrAlert Advance weatherproof back box. Do
not attempt to use boxes other than the ones supplied with the product.
2. The plastic weatherproof back box is equipped with removable side
flanges for mounting. The back box may be secured directly to the wall
or ceiling using the flanges (plastic and metal back boxes) or by using
the knockout plugs(plastic back boxes). Knockout plugs are provided to
mount directly to the wall or ceiling or to a 1900 weatherproof electrical
box, see figure 3
3. The wall mount box must be mounted with its internal post in the lower
left corner, as shown in Figure 3.
4. Threaded holes are provided in the sides of the box for ¾ inch conduit
adapters. Knockout plugs in the back of the box can be used for ¾ inch
rear entry. Unused holes must be sealed. Plugs are provided with the box
for this purpose.
5. It is the responsibility of the installer to make sure that all openings and
connections are sealed properly. Outdoor installations that are protected
from direct exposure to rain are still subject to condensation or leakage
through hidden areas, such as a soffit.
6. Water may pool on the back box due to condensation or direct exposure
to rain or snow. Use watertight fittings for all wiring connections, includ-
ing the knockout plugs on the back of the box. When using plastic plugs
to fill unused threaded holes, apply teflon tape and/or silicone sealant to
reduce the chance of leakage.
7. Attach the mounting plate to the weatherproof back box using the four
unpainted screws supplied.
8. Follow steps 1 – 6 of the indoor mounting instructions to wire and attach
the product.
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this product. No
agent, representative, dealer, or employee of the Company has the authority to increase
or alter the obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the replacement of any part of the product which is found
to be defective in materials or workmanship under normal use and service during the
three year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: Honeywell, 12220 Rojas Drive, Suite 700, El Paso
TX 79936, USA. Please include a note describing the malfunction and suspected cause
of failure. The Company shall not be obligated to replace units which are found to be
defective because of damage, unreasonable use, modifications, or alterations occurring
after the date of manufacture. In no case shall the Company be liable for any consequen-
tial or incidental damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential dam-
ages, so the above limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary from state to state.
FCC STATEMENT
SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equip-
ment is operated in a commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own expense.
Please refer to insert for the Limitations of Fire Alarm Systems
A0357-00
A0418-03
4 X 4 X 2 1/8 BACK BOX
120V WIRES 120V MOUNTING PLATE MP120K
FIGURE 3.
firealarmresources.com

Other System Sensor Security Sensor manuals

System Sensor SpectrAlert DS2475WAR User manual

System Sensor

System Sensor SpectrAlert DS2475WAR User manual

System Sensor 5600 Series User manual

System Sensor

System Sensor 5600 Series User manual

System Sensor Accuflow LFD20 User manual

System Sensor

System Sensor Accuflow LFD20 User manual

System Sensor 4451HT User manual

System Sensor

System Sensor 4451HT User manual

System Sensor WFDNA Series Technical specifications

System Sensor

System Sensor WFDNA Series Technical specifications

System Sensor ED-TI User manual

System Sensor

System Sensor ED-TI User manual

System Sensor B801RA User manual

System Sensor

System Sensor B801RA User manual

System Sensor ECO1005ABLINK User manual

System Sensor

System Sensor ECO1005ABLINK User manual

System Sensor B210LPA User manual

System Sensor

System Sensor B210LPA User manual

System Sensor SPECTRAlert H12/24K User manual

System Sensor

System Sensor SPECTRAlert H12/24K User manual

System Sensor EBR User manual

System Sensor

System Sensor EBR User manual

System Sensor CO1224 User manual

System Sensor

System Sensor CO1224 User manual

System Sensor 1112/24D User manual

System Sensor

System Sensor 1112/24D User manual

System Sensor Innovair DH200PL User manual

System Sensor

System Sensor Innovair DH200PL User manual

System Sensor 9440X FAAST User manual

System Sensor

System Sensor 9440X FAAST User manual

System Sensor B210LP User manual

System Sensor

System Sensor B210LP User manual

System Sensor WFDN Series User manual

System Sensor

System Sensor WFDN Series User manual

System Sensor 885-WP User manual

System Sensor

System Sensor 885-WP User manual

System Sensor B110LPA User manual

System Sensor

System Sensor B110LPA User manual

System Sensor ECO1002 User manual

System Sensor

System Sensor ECO1002 User manual

System Sensor 1451 User manual

System Sensor

System Sensor 1451 User manual

System Sensor B110RLP User manual

System Sensor

System Sensor B110RLP User manual

System Sensor B401BR User manual

System Sensor

System Sensor B401BR User manual

System Sensor WFD20 User manual

System Sensor

System Sensor WFD20 User manual

Popular Security Sensor manuals by other brands

3M 600 Series datasheet

3M

3M 600 Series datasheet

EDTM RD1850 Operator's manual

EDTM

EDTM RD1850 Operator's manual

PNI SAFE HOUSE DUAL GAS 250 user manual

PNI

PNI SAFE HOUSE DUAL GAS 250 user manual

Texecom Premier Elite MR Long Range installation manual

Texecom

Texecom Premier Elite MR Long Range installation manual

Triple Plus CLM-FDAMAP-1-00 quick start guide

Triple Plus

Triple Plus CLM-FDAMAP-1-00 quick start guide

Bosch Blue Line Q1 installation instructions

Bosch

Bosch Blue Line Q1 installation instructions

Bircher Reglomat PrimeMotion B Original instructions

Bircher Reglomat

Bircher Reglomat PrimeMotion B Original instructions

teko Astra-3321 user guide

teko

teko Astra-3321 user guide

Somogyi home HS 71 Instructions for use

Somogyi

Somogyi home HS 71 Instructions for use

Gemini 807 manual

Gemini

Gemini 807 manual

Pfeiffer ASM 340 operating instructions

Pfeiffer

Pfeiffer ASM 340 operating instructions

Rohm BH1730FVC-TR Technical notes

Rohm

Rohm BH1730FVC-TR Technical notes

Aritech 700 series Installation sheet

Aritech

Aritech 700 series Installation sheet

Kanlux AKER JQ-30 manual

Kanlux

Kanlux AKER JQ-30 manual

Onan Mobile GenSet Service manual

Onan

Onan Mobile GenSet Service manual

STEINEL 067304 manual

STEINEL

STEINEL 067304 manual

B+B Sensors PIR-STD Operation manual

B+B Sensors

B+B Sensors PIR-STD Operation manual

Orbis ISIMAT INSTRUCTIONS ON USE

Orbis

Orbis ISIMAT INSTRUCTIONS ON USE

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.