EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Security Sensor
  8. •
  9. System Sensor B110RLP User manual

System Sensor B110RLP User manual

Other System Sensor Security Sensor manuals

System Sensor 5600 Series User manual

System Sensor

System Sensor 5600 Series User manual

System Sensor B200SA User manual

System Sensor

System Sensor B200SA User manual

System Sensor B501 User manual

System Sensor

System Sensor B501 User manual

System Sensor B501B-FTX User manual

System Sensor

System Sensor B501B-FTX User manual

System Sensor 22051TLE-RF User manual

System Sensor

System Sensor 22051TLE-RF User manual

System Sensor DH400 User manual

System Sensor

System Sensor DH400 User manual

System Sensor 2151 User manual

System Sensor

System Sensor 2151 User manual

System Sensor B224RB User manual

System Sensor

System Sensor B224RB User manual

System Sensor ISO524-1 User manual

System Sensor

System Sensor ISO524-1 User manual

System Sensor WFD Series User manual

System Sensor

System Sensor WFD Series User manual

System Sensor B112LP User manual

System Sensor

System Sensor B112LP User manual

System Sensor B801RA User manual

System Sensor

System Sensor B801RA User manual

System Sensor WFDTNRN User manual

System Sensor

System Sensor WFDTNRN User manual

System Sensor B401BR User manual

System Sensor

System Sensor B401BR User manual

System Sensor 5451EIS User manual

System Sensor

System Sensor 5451EIS User manual

System Sensor B401R User manual

System Sensor

System Sensor B401R User manual

System Sensor B501AP User manual

System Sensor

System Sensor B501AP User manual

System Sensor B404B User manual

System Sensor

System Sensor B404B User manual

System Sensor DH400ACDC User manual

System Sensor

System Sensor DH400ACDC User manual

System Sensor InnovAir DH100ACDCI User manual

System Sensor

System Sensor InnovAir DH100ACDCI User manual

System Sensor 9440X FAAST User manual

System Sensor

System Sensor 9440X FAAST User manual

System Sensor WFDT User manual

System Sensor

System Sensor WFDT User manual

System Sensor EBR User manual

System Sensor

System Sensor EBR User manual

System Sensor RTS151KEYA User manual

System Sensor

System Sensor RTS151KEYA User manual

Popular Security Sensor manuals by other brands

THORLABS PDA10JT user guide

THORLABS

THORLABS PDA10JT user guide

Waeco UV-DETECT operating manual

Waeco

Waeco UV-DETECT operating manual

Intermatic IOS-DSIMF manual

Intermatic

Intermatic IOS-DSIMF manual

urmet domus 1083 manual

urmet domus

urmet domus 1083 manual

Siemens AZL66 Series manual

Siemens

Siemens AZL66 Series manual

BTI Profiline Multi Finder operating instructions

BTI

BTI Profiline Multi Finder operating instructions

Challenger SL01 instruction manual

Challenger

Challenger SL01 instruction manual

DMP Electronics 1122INT installation guide

DMP Electronics

DMP Electronics 1122INT installation guide

Rielta Ladoga MK-RK installation guide

Rielta

Rielta Ladoga MK-RK installation guide

Mirion Technologies ACCURAD PRD user manual

Mirion Technologies

Mirion Technologies ACCURAD PRD user manual

Bosch DS835 installation instructions

Bosch

Bosch DS835 installation instructions

Lamptime ST05C instructions

Lamptime

Lamptime ST05C instructions

Ubiquiti MFI-MSC quick start guide

Ubiquiti

Ubiquiti MFI-MSC quick start guide

Subsite 910R Support

Subsite

Subsite 910R Support

Satel OPAL Pro manual

Satel

Satel OPAL Pro manual

Aleph XC-1XTEU manual

Aleph

Aleph XC-1XTEU manual

Pima LARIS QUAD installation instructions

Pima

Pima LARIS QUAD installation instructions

Solinst 301 user guide

Solinst

Solinst 301 user guide

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

D150-04-00 1 I56-596-03R
B110RLP Plug-in Detector Base
For use with the following smoke detectors:
In US : 1151, 2151
In Canada: 1151A, 2151A
In Europe: 1151E, 2151E
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which
provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications. Copies of
this manual are available at no charge from System Sensor.
(For installations in Canada, please refer to CAN4-S524,
Standard for the Installation of Fire Alarm Systems, and
CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
Specifications
Base Diameter: 6.2 inches (157 mm)
Base Height: 0.95 inches (24 mm)
Weight: 0.3 lb. (130 g)
Mounting: 4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2 inch octagon box. Min. Depth–1.5 inches
Operating Temperature Range: 0° to +49°C (32° to 120°F)
Operating Humidity Range: 10% to 93% Relative Humidity
Electrical Ratings — includes base and detector
System Voltage: 24 VDC
Maximum Ripple Voltage: 4 Volts peak to peak
Start-up Capacitance: 0.02 µF Maximum
Standby Ratings: 17 VDC Minimum; 32 VDC Maximum
120 µA Maximum
Alarm Ratings: 10 mA Minimum at 10.5 VDC; 62 mA Maximum at 32 VDC
(If used, the RA400 remote lamp operates within specified detector alarm currents.)
Maximum Alarm Impedance: 1050Ω
Minimum Alarm Impedance: 516Ω
Reset Voltage: 2.50 VDC Minimum
Reset Time: 0.3 Seconds Maximum
Start-up Time: 34.0 Seconds Maximum
General Description
The B110RLP plug-in detector base is used with System
Sensor model 1151 and 1151A ionization detector heads
and model 2151 and 2151A photoelectronic detector heads.
The capability of plugging these detectors into a variety of
special bases makes them more versatile than equivalent
direct-wired models. Refer to the System Sensor catalog for
other available plug-in detector bases.
This base is intended for use in 2-wire systems, with screw
terminals provided for power, ground, and remote annun-
ciator connections. The base also contains a resistor to
provide current limiting in the alarm state.
D150-04-00 4 I56-596-03R
© 2001 System Sensor
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector base to be free from
defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector base. No agent, represen-
tative, dealer, or employee of the Company has the authority to increase
or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or replacement
of any part of the smoke detector base which is found to be defective in
materials or workmanship under normal use and service during the three
year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System
Sensor, Repair Department, RA #__________, 3825 Ohio Avenue, St.
Charles, IL 60174. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to repair
or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date
of manufacture. In no case shall the Company be liable for any conse-
quential or incidental damages for breach of this or any other Warranty,
expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclu-
sion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary from
state to state.
Please refer to insert for the Limitations of Fire Alarm Systems
I56-596-03R
D150-04-00 3 I56-596-03RD150-04-00 2 I56-596-03R
Mounting
This detector base mounts directly to 3-1/2- inch and
4-inch octagon boxes, and 4-inch square boxes (with or
without plaster rings). To mount, remove decorative ring
by turning it in either direction to unhook the snaps, then
separate the ring from the base. Install the base to the box
using the screws supplied with the junction box and the
appropriate mounting slots in the base. Place decorative
ring onto base, then turn in either direction until the ring
snaps in place (see Figure 1).
Installation Guidelines
All wiring must be installed in compliance with the National
Electrical Code and the local codes having jurisdiction.
Proper wire gauges should be used. The conductors used
to connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detec-
tors), it is recommended that the wire be no smaller than
18 gauge (1.0 square mm). Wire sizes up to 12 gauge wire
(2.5 square mm) may be used with the base. For best sys-
tem performance, the power (+) and (–) loop wires should
be twisted pair and installed in separate grounded conduit
to protect the loop from extraneous electrical interference.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loops.
CAUTION
For system supervision — For terminals 2, 3, and 5 do not
use looped wire under terminals. Break wire run to provide
system supervision of connections.
Wire connections are made by simply stripping insulation
from the end of the wire, sliding the bare end of the wire
under the clamping plate, and tightening the clamping
plate screw. Use the strip gauge molded into the base for
ease of wiring to terminals 1 through 5.
System Sensor smoke detectors and mounting bases are
marked with a compatibility identifier located as the last
digit of a five digit code stamped on the back of the prod-
uct. Connect detectors/mounting bases only to compatible
control units as indicated in System Sensor’s compatibility
chart which contains a current list of UL listed control units
and detector head/base combinations. A copy of this list is
available from System Sensor upon request.
Once all the detector bases have been wired and mounted,
and the loop wiring has been checked, the detector heads
may be installed in the bases. The shorting spring in the
base will disengage automatically when the detector head
is removed from the base. DO NOT remove the shorting
spring since it reengages as the detector head is turned into
the base, completing the circuit.
Tamper-resistance Feature
NOTE: Do not use the tamper-resistance feature if the XR2
removal tool is to be used.
The tamper-resistant tab, in the detector mounting bracket,
can make the detector tamper-resistant by making it neces-
sary to use a small screwdriver or similar tool to detach the
detector from the bracket.
SNAP ON
DECORATIVE
RING
SCREWS (NOT
SUPPLIED)
DETECTOR
BASE
BOX (NOT
SUPPLIED)
SHORTING
SPRING
C503-00
2
3
4
1
REMOTE
ANNUNCIATOR
2
3
4
1
REMOTE
ANNUNCIATOR
2-WIRE CONTROL PANEL
E
O
L
CLASS A OPTIONAL WIRING
Figure 2. Typical wiring diagram for 2-wire detector systems:
C0529-00
The zone wiring of the detector base should be checked
before the detector heads are installed in them. To make
this possible, this base contains a special spring-type short-
ing jumper. After a detector base is properly wired and
mounted on an electrical box, make sure that the jumper
spring is in contact with the base of Terminal 3. This tem-
porary connection shorts the negative-in and negative-out
leads and permits the wiring of the loop to be checked for
continuity.
To make the detector tamper-resistant, use needle-nose
pliers to break the smaller tab at the scribed line on the
tamper- resistance tab. Figure 3A shows the location of this
tab on the detector mounting bracket.
To remove a detector from the bracket after it has been
made tamper resistant, use a small screwdriver or other
similar tool, to depress the tamper-resistance tab in the slot
on the mounting bracket, and rotate the detector counter-
clockwise (see Figure 3B).
NOTE: The decorative ring must be removed before the
smoke detector can be detached from the base
after the tamper-resistant capability is enabled.
PLASTIC LEVER
BREAK TAB AT
DOTTED LINE BY
TWISTING TOWARD
CENTER OF BASE.
USE SMALL-BLADED
SCREWDRIVER TO
PUSH PLASTIC LEVER
IN DIRECTION OF
ARROW.
Figure 3A. Activating the tamper-resistance feature: Figure 3B. Removing detector head from base:
C0130-00
Figure 1. Mounting base to box: