D150-04-00 1 I56-596-03R
B110RLP Plug-in Detector Base
For use with the following smoke detectors:
In US : 1151, 2151
In Canada: 1151A, 2151A
In Europe: 1151E, 2151E
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which
provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications. Copies of
this manual are available at no charge from System Sensor.
(For installations in Canada, please refer to CAN4-S524,
Standard for the Installation of Fire Alarm Systems, and
CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
Specifications
Base Diameter: 6.2 inches (157 mm)
Base Height: 0.95 inches (24 mm)
Weight: 0.3 lb. (130 g)
Mounting: 4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2 inch octagon box. Min. Depth–1.5 inches
Operating Temperature Range: 0° to +49°C (32° to 120°F)
Operating Humidity Range: 10% to 93% Relative Humidity
Electrical Ratings — includes base and detector
System Voltage: 24 VDC
Maximum Ripple Voltage: 4 Volts peak to peak
Start-up Capacitance: 0.02 µF Maximum
Standby Ratings: 17 VDC Minimum; 32 VDC Maximum
120 µA Maximum
Alarm Ratings: 10 mA Minimum at 10.5 VDC; 62 mA Maximum at 32 VDC
(If used, the RA400 remote lamp operates within specified detector alarm currents.)
Maximum Alarm Impedance: 1050Ω
Minimum Alarm Impedance: 516Ω
Reset Voltage: 2.50 VDC Minimum
Reset Time: 0.3 Seconds Maximum
Start-up Time: 34.0 Seconds Maximum
General Description
The B110RLP plug-in detector base is used with System
Sensor model 1151 and 1151A ionization detector heads
and model 2151 and 2151A photoelectronic detector heads.
The capability of plugging these detectors into a variety of
special bases makes them more versatile than equivalent
direct-wired models. Refer to the System Sensor catalog for
other available plug-in detector bases.
This base is intended for use in 2-wire systems, with screw
terminals provided for power, ground, and remote annun-
ciator connections. The base also contains a resistor to
provide current limiting in the alarm state.
D150-04-00 4 I56-596-03R
© 2001 System Sensor
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector base to be free from
defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector base. No agent, represen-
tative, dealer, or employee of the Company has the authority to increase
or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or replacement
of any part of the smoke detector base which is found to be defective in
materials or workmanship under normal use and service during the three
year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System
Sensor, Repair Department, RA #__________, 3825 Ohio Avenue, St.
Charles, IL 60174. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to repair
or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date
of manufacture. In no case shall the Company be liable for any conse-
quential or incidental damages for breach of this or any other Warranty,
expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclu-
sion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary from
state to state.
Please refer to insert for the Limitations of Fire Alarm Systems
I56-596-03R
D150-04-00 3 I56-596-03RD150-04-00 2 I56-596-03R
Mounting
This detector base mounts directly to 3-1/2- inch and
4-inch octagon boxes, and 4-inch square boxes (with or
without plaster rings). To mount, remove decorative ring
by turning it in either direction to unhook the snaps, then
separate the ring from the base. Install the base to the box
using the screws supplied with the junction box and the
appropriate mounting slots in the base. Place decorative
ring onto base, then turn in either direction until the ring
snaps in place (see Figure 1).
Installation Guidelines
All wiring must be installed in compliance with the National
Electrical Code and the local codes having jurisdiction.
Proper wire gauges should be used. The conductors used
to connect smoke detectors to control panels and accessory
devices should be color-coded to reduce the likelihood of
wiring errors. Improper connections can prevent a system
from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detec-
tors), it is recommended that the wire be no smaller than
18 gauge (1.0 square mm). Wire sizes up to 12 gauge wire
(2.5 square mm) may be used with the base. For best sys-
tem performance, the power (+) and (–) loop wires should
be twisted pair and installed in separate grounded conduit
to protect the loop from extraneous electrical interference.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loops.
CAUTION
For system supervision — For terminals 2, 3, and 5 do not
use looped wire under terminals. Break wire run to provide
system supervision of connections.
Wire connections are made by simply stripping insulation
from the end of the wire, sliding the bare end of the wire
under the clamping plate, and tightening the clamping
plate screw. Use the strip gauge molded into the base for
ease of wiring to terminals 1 through 5.
System Sensor smoke detectors and mounting bases are
marked with a compatibility identifier located as the last
digit of a five digit code stamped on the back of the prod-
uct. Connect detectors/mounting bases only to compatible
control units as indicated in System Sensor’s compatibility
chart which contains a current list of UL listed control units
and detector head/base combinations. A copy of this list is
available from System Sensor upon request.
Once all the detector bases have been wired and mounted,
and the loop wiring has been checked, the detector heads
may be installed in the bases. The shorting spring in the
base will disengage automatically when the detector head
is removed from the base. DO NOT remove the shorting
spring since it reengages as the detector head is turned into
the base, completing the circuit.
Tamper-resistance Feature
NOTE: Do not use the tamper-resistance feature if the XR2
removal tool is to be used.
The tamper-resistant tab, in the detector mounting bracket,
can make the detector tamper-resistant by making it neces-
sary to use a small screwdriver or similar tool to detach the
detector from the bracket.
SNAP ON
DECORATIVE
RING
SCREWS (NOT
SUPPLIED)
DETECTOR
BASE
BOX (NOT
SUPPLIED)
SHORTING
SPRING
C503-00
2
3
4
1
REMOTE
ANNUNCIATOR
2
3
4
1
REMOTE
ANNUNCIATOR
2-WIRE CONTROL PANEL
E
O
L
CLASS A OPTIONAL WIRING
Figure 2. Typical wiring diagram for 2-wire detector systems:
C0529-00
The zone wiring of the detector base should be checked
before the detector heads are installed in them. To make
this possible, this base contains a special spring-type short-
ing jumper. After a detector base is properly wired and
mounted on an electrical box, make sure that the jumper
spring is in contact with the base of Terminal 3. This tem-
porary connection shorts the negative-in and negative-out
leads and permits the wiring of the loop to be checked for
continuity.
To make the detector tamper-resistant, use needle-nose
pliers to break the smaller tab at the scribed line on the
tamper- resistance tab. Figure 3A shows the location of this
tab on the detector mounting bracket.
To remove a detector from the bracket after it has been
made tamper resistant, use a small screwdriver or other
similar tool, to depress the tamper-resistance tab in the slot
on the mounting bracket, and rotate the detector counter-
clockwise (see Figure 3B).
NOTE: The decorative ring must be removed before the
smoke detector can be detached from the base
after the tamper-resistant capability is enabled.
PLASTIC LEVER
BREAK TAB AT
DOTTED LINE BY
TWISTING TOWARD
CENTER OF BASE.
USE SMALL-BLADED
SCREWDRIVER TO
PUSH PLASTIC LEVER
IN DIRECTION OF
ARROW.
Figure 3A. Activating the tamper-resistance feature: Figure 3B. Removing detector head from base:
C0130-00
Figure 1. Mounting base to box:

Other System Sensor Security Sensor manuals

System Sensor Innovair SSK451 User manual

System Sensor

System Sensor Innovair SSK451 User manual

System Sensor B501AP User manual

System Sensor

System Sensor B501AP User manual

System Sensor OSI-RIE Series User manual

System Sensor

System Sensor OSI-RIE Series User manual

System Sensor B112LP User manual

System Sensor

System Sensor B112LP User manual

System Sensor 2112LP User manual

System Sensor

System Sensor 2112LP User manual

System Sensor 885-WP User manual

System Sensor

System Sensor 885-WP User manual

System Sensor SPECTRAlert H12/24K User manual

System Sensor

System Sensor SPECTRAlert H12/24K User manual

System Sensor B110LPA User manual

System Sensor

System Sensor B110LPA User manual

System Sensor 1112/24D User manual

System Sensor

System Sensor 1112/24D User manual

System Sensor SPECTRAlert CH24 Series User manual

System Sensor

System Sensor SPECTRAlert CH24 Series User manual

System Sensor 5151 User manual

System Sensor

System Sensor 5151 User manual

System Sensor DH400 User manual

System Sensor

System Sensor DH400 User manual

System Sensor WFD20EXP User manual

System Sensor

System Sensor WFD20EXP User manual

System Sensor B112LP User manual

System Sensor

System Sensor B112LP User manual

System Sensor B110RLP User manual

System Sensor

System Sensor B110RLP User manual

System Sensor 22051TLE-RF User manual

System Sensor

System Sensor 22051TLE-RF User manual

System Sensor B114LP User manual

System Sensor

System Sensor B114LP User manual

System Sensor InnovAir DH100ACDCI User manual

System Sensor

System Sensor InnovAir DH100ACDCI User manual

System Sensor SpectrAlert Advance CHSR User manual

System Sensor

System Sensor SpectrAlert Advance CHSR User manual

System Sensor WFD Series User manual

System Sensor

System Sensor WFD Series User manual

System Sensor B224BI-WH User manual

System Sensor

System Sensor B224BI-WH User manual

System Sensor SpectrAlert DS2475WAR User manual

System Sensor

System Sensor SpectrAlert DS2475WAR User manual

System Sensor 5600 Series User manual

System Sensor

System Sensor 5600 Series User manual

System Sensor B300A-6 User manual

System Sensor

System Sensor B300A-6 User manual

Popular Security Sensor manuals by other brands

FIREGUARD GLOBAL FG-BD100 Product introduction

FIREGUARD GLOBAL

FIREGUARD GLOBAL FG-BD100 Product introduction

Polon-Alfa TUN-4046 Installation and maintenance manual

Polon-Alfa

Polon-Alfa TUN-4046 Installation and maintenance manual

König SAS-CA100 manual

König

König SAS-CA100 manual

Ultra-safe UX-96305NQL User instruction manual

Ultra-safe

Ultra-safe UX-96305NQL User instruction manual

IFM PI1689 operating instructions

IFM

IFM PI1689 operating instructions

Newlec EMERGENCY TWINSPOT instructions

Newlec

Newlec EMERGENCY TWINSPOT instructions

STEINEL L20S quick start guide

STEINEL

STEINEL L20S quick start guide

Teledyne UA-6 Installation and operation guide

Teledyne

Teledyne UA-6 Installation and operation guide

AVS Electronics JET DT manual

AVS Electronics

AVS Electronics JET DT manual

Leeo Smart Alert quick start guide

Leeo

Leeo Smart Alert quick start guide

Inficon HLD6000 Original operating instructions

Inficon

Inficon HLD6000 Original operating instructions

schmersal AZ 16-STS30-02 operating instructions

schmersal

schmersal AZ 16-STS30-02 operating instructions

Outdoor Plus TOP-FSPBI-NG OWNER'S OPERATION AND INSTALLATION MANUAL

Outdoor Plus

Outdoor Plus TOP-FSPBI-NG OWNER'S OPERATION AND INSTALLATION MANUAL

Bacharach MGS-150 Installation and operation manual

Bacharach

Bacharach MGS-150 Installation and operation manual

Global Fire Equipment GFE-H Installation

Global Fire Equipment

Global Fire Equipment GFE-H Installation

Astronics Trig-Tek 850A user manual

Astronics

Astronics Trig-Tek 850A user manual

SMC Networks PSE541 instruction manual

SMC Networks

SMC Networks PSE541 instruction manual

Perenio PECMS01 quick start guide

Perenio

Perenio PECMS01 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.