TCi HGP HarmonicGuard Series User manual

HarmonicGuard®Series
Drive Applied Harmonic Filter Kit
Installation, Operation, and Maintenance Manual
TCI, LLC
W132 N10611 Grant Drive
Germantown, Wisconsin 53022
Phone: 414-357-4480
Fax: 414-357-4484
Helpline: 800-TCI-8282
Web Site: http://www.transcoil.com
© 2019 TCI, LLC All rights reserved
Product No: 29289
Effective: 01/06/2020 Version: N

No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any
form or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the
prior written permission of TCI, LLC. The information in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. TCI, LLC assumes no
responsibility for errors or omissions. Neither is any liability assumed for damages resulting from
the use of the information contained in this publication.

No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by
any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission
of TCI, LLC. The information in this manual is subject to change without notice. Every precaution has been
Revision Description Date
A
Release
B
Added 600 V Option
10/22/14
C
Updated Kit Numbering system
02/03/15
D
Updated Kit Usages Instructions
09/13/16
E
Updated 480 V 60 Hz HGP Fuse Tables
06/26/17
F
Updated 480 V 60 Hz HGP Fuse Tables
10/19/17
G
Updated Fuse Requirements Table
12/01/17
H
Updated Filter Schematics
04/23/18
J
Update to include compliance
11/15/18
K
Update to include PQconnect
08/22/19
L
Update to include Bluetooth capability with PQconnect
09/25/19
M
Fixes to PQconnect section
11/11/19
N
Updates to PQconnect section
01/06/20

taken in the preparation of this manual. TCI, LLC assumes no responsibility for errors or omissions. Neither is
any liability assumed for damages resulting from the use of the information contained in this publication.
Performance Guarantee
Select and install the appropriate HarmonicGuard®Passive Harmonic Filter Kit
in a variable torque, variable frequency AC drive application, within our
published technical specifications and we guarantee that the input current
distortion will be less than or equal to 5% THID for standard HGP Series filters
at full load, and less than 8% at 30% load. If a properly sized and installed filter
fails to meet its specified THID level, TCI will provide material for necessary
modifications or replacement filter at no charge.
HG filters can also provide similar performance in other drive applications such
as constant torque, DC drives and other phase controlled rectifiers, but actual
THID levels can vary by load and/or speed and therefore cannot be guaranteed.
Consult factory for assistance when applying HGP filters on these types of
equipment.
MINIMUM SYSTEM REQUIREMENTS:
The guaranteed performance levels of this filter will be achieved when
the following system conditions are met:
Frequency: 60Hz ± 0.75Hz
System Voltage: Nominal System Voltage (line to line) ±10%
Balanced Line Voltage: Within 0.5%
Background Voltage Distortion: < 0.5% THVD
The input VFD current waveform shall be consistent with that of a VFD
with 3% AC line reactance at full load.
NOTE: The presence of background voltage distortion will cause motors and
other linear loads to draw harmonic currents.
Additional harmonic currents may flow into the HGP filter if there is harmonic
voltage distortion already on the system.
If higher levels of harmonic voltage distortion (2%-5%) are present, please use
the high voltage distortion wiring of the HGP filter kit.
*For PQconnect: To run PQvision software, minimum system requirements
are Windows 7 and 1280 x 720 resolution.

1
Table of Contents
1.0 Safety .......................................................................................................................................................2
Safety Instructions Overview ....................................................................................................................2
Warnings and Cautions ............................................................................................................................2
General Safety Instructions ......................................................................................................................3
2.0 General Information................................................................................................................................4
Intended Audience....................................................................................................................................4
Receiving Inspection.................................................................................................................................4
Storage Instructions..................................................................................................................................4
TCI Limited Warranty Policy .....................................................................................................................4
3.0 Pre-Installation Planning........................................................................................................................6
Verify the Application ................................................................................................................................6
Recommendations Kit Usage ...................................................................................................................6
HGP Kit Part Numbering System .............................................................................................................6
Technical Specifications ...........................................................................................................................7
Select a Suitable Location ........................................................................................................................8
4.0 Installation ...............................................................................................................................................7
Installation Guidelines...............................................................................................................................7
Mounting the Filter Kit...............................................................................................................................8
Power Wiring ............................................................................................................................................8
SCCR Ratings ..........................................................................................................................................9
Filter Wire Sizing.................................................................................................................................... 11
KDR Line Reactor Installation Instructions ............................................................................................ 14
Tuning Reactor ...................................................................................................................................... 17
Tuned Circuit Capacitors ....................................................................................................................... 17
Capacitor Brackets ................................................................................................................................ 19
Contactor (Optional Customer Supplied)............................................................................................... 19
5.0 PQconnect .............................................................................................................................................20
Product Description ............................................................................................................................... 20
Installation.............................................................................................................................................. 21
Mounting ................................................................................................................................................ 21
Wiring..................................................................................................................................................... 23
PQconnect PCB Calibration .................................................................................................................. 26
PQvision Software ................................................................................................................................. 30
Modbus RTU.......................................................................................................................................... 38
RS485 to USB Serial Converter ............................................................................................................ 51
6.0 Troubleshooting ...................................................................................................................................54

HGP Kit Manual 1.0 Safety
2
1.0 Safety
The information presented in this manual covers the HGP filter kits only. For the
full HGP manual please visit:
https://transcoil.com/Products/HGP-Passive-Harmonic-Filter.htm
Safety Instructions Overview
This section provides the safety instructions which must be followed when installing, operating, and
servicing the HGP Filter kit. If neglected, physical injury or death may follow, or damage may occur
to the filter or equipment connected to the filter. The material in this chapter must be read and
understood before attempting any work on or with the product.
The HGP filter is intended to be connected to the input terminals of one or more VFDs. Three-
phase power is connected to the input terminals of the filter and power is supplied to the VFD or
VFDs through the filter. The instructions, and particularly the safety instructions, for the VFDs,
motors, and any other related equipment must be read, understood, and followed when working on
any of the equipment.
Warnings and Cautions
This manual provides two types of safety instructions. Warnings are used to call attention to
instructions that describe steps that must be taken to avoid conditions that can lead to a serious
fault condition, physical injury, or death.
Cautions are used to call attention to instructions that describe steps that must be taken to avoid
conditions that can lead to a malfunction and possible equipment damage.
Warnings
Readers are informed of situations that can result in serious physical injury and/or serious damage
to equipment with warning statements highlighted by the following symbols:
Warning
Dangerous Voltage Warning: warns of situations where
high voltage can cause physical injury and/or damage
equipment. The text next to this symbol describes ways
to avoid the danger.
Warning
General Warning: warns of situations that can cause
physical injury and/or damage equipment by means other
than electrical. The text next to this symbol describes
ways to avoid the danger.
Warning
Electrostatic Discharge Warning: warns of situations in
which an electrostatic discharge can damage equipment.
The text next to this symbol describes ways to avoid the
danger.
Cautions
Readers are informed of situations that can lead to a malfunction and possible equipment damage
with caution statements:
Caution General Caution: identifies situations that can lead to a
malfunction and possible equipment damage. The text
describes ways to avoid the situation.
!
!

HGP Kit Manual 1.0 Safety
3
General Safety Instructions
These safety instructions are intended for all work on the HGP filter. Additional safety instructions
are provided at appropriate points on other sections of this manual.
Warning
Be sure to read, understand, and follow all safety
instructions.
Warning Only qualified electricians should carry out all electrical
installation and maintenance work on the HGP filter.
Warning All wiring must be in accordance with the National
Electrical Code (NEC) and/or any other codes that apply
to the installation site.
Warning Disconnect all power before working on the equipment.
Do not attempt any work on a powered HGP filter.
Warning The HGP filter, drive, motor, and other connected
equipment must be properly grounded.
Warning
After switching off the power, always allow 5 minutes for
the capacitors in the HGP filter and in the drive to
discharge before working on the HGP, the drive, the
motor, or the connecting wiring. It is a good idea to check
with a voltmeter to make sure that all sources of power
have been disconnected and that all capacitors have
discharged before beginning work.
!
!
!

HGP Kit Manual 2.0 General Information
4
2.0 General Information
Thank you for selecting the HGP filter kit. TCI has produced this filter for use in many variable
frequency drive (VFD) applications that require input power line harmonic current reduction. This
manual gives an overview of how to install, operate and maintain the HGP PQconnect Filter kit.
Please contact TCI Technical Support or visit transcoil.com/Support.htm for additional information.
Intended Audience
This manual is intended for use by all personnel responsible for the assembly, wiring installation,
operation and maintenance of the HGP filters and kits. Such personnel are expected to have knowledge
of electrical wiring practices, electronic components and electrical schematic symbols. Panel design
using a TCI HGP Filter Kit should be performed with appropriate engineering supervision so the design
meets the requirements based on materials utilized in the construction of the panel, wiring practices
followed by your shop, and the actual ambient conditions of the components for each application.
Receiving Inspection
The HGP filter kit has been thoroughly inspected at the factory and carefully packaged for shipment.
When you receive the unit, you should immediately inspect the shipping container and report any
damage to the carrier that delivered the unit. Verify that the part number of the components you
received is the same as the part numbers listed on the engineering drawings for the kit.
Storage Instructions
If the HGP Kit filter is to be stored before use, be sure that it is stored in a location that
conforms to published storage humidity and temperature specifications on the applicable
technical drawings available at: https://transcoil.com/products/kits-page/hgp-kits/. Store
the unit in its original packaging.
TCI Limited Warranty Policy
TCI, LLC (“TCI”) warrants to the original purchaser only that its products will be free from defects
in materials and workmanship under normal use and service for a period originating on the date of
shipment from TCI and expiring at the end of the period described below:
Product Family
Warranty Period
KLR, KDR
For the life of the drive with which they are installed.
HGA, KLC, KLCUL, KMG,
MSD, V1k
One (1) year of useful service,
not to exceed 18 months from the date of shipment.
PF Guard, HGP, HGL, HG7,
HSD, KRF
Three (3) years from the date of shipment.
KCAP, KTR,
Five (5) years from the date of shipment.
All Other Products
One (1) year of useful service,
not to exceed 18 months from the date of shipment.
The foregoing limited warranty is TCI’s sole warranty with respect to its products and TCI makes
no other warranty, representation, or promise as to the quality or performance of TCI’s products.
THIS EXPRESS LIMITED WARRANTY IS GIVEN IN LIEU OF AND EXCLUDES ANY AND ALL
EXPRESS OR IMPLIED WARRANTIES INCLUDING, WITHOUT LIMITATION, ANY IMPLIED
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
This warranty shall not apply if the product was:
a) Altered or repaired by anyone other than TCI;
b) Applied or used for situations other than those originally specified; or
c) Subjected to negligence, accident, or damage by circumstances beyond TCI’s control,
including but not limited to, improper storage, installation, operation, or maintenance.

HGP Kit Manual 2.0 General Information
5
If, within the warranty period, any product shall be found in TCI’s reasonable judgment to be
defective, TCI’s liability and the Buyer’s exclusive remedy under this warranty is expressly limited,
at TCI’s option, to (i) repair or replacement of that product, or (ii) return of the product and refund
of the purchase price. Such remedy shall be Buyer’s sole and exclusive remedy. TCI SHALL NOT,
IN ANY EVENT, BE LIABLE FOR INCIDENTAL DAMAGES OR FOR CONSEQUENTIAL
DAMAGES INCLUDING, BUT NOT LIMITED TO, LOSS OF INCOME, LOSS OF TIME, LOST
SALES, INJURY TO PERSONAL PROPERTY, LIABILITY BUYER INCURS WITH RESPECT TO
ANY OTHER PERSON, LOSS OF USE OF THE PRODUCT OR FOR ANY OTHER TYPE OR
FORM OF CONSEQUENTIAL DAMAGE OR ECONOMIC LOSS.
The foregoing warranties do not cover reimbursement for removal, transportation, reinstallation, or
any other expenses that may be incurred in connection with the repair or replacement of the TCI
product.
The employees and sales agents of TCI are not authorized to make additional warranties about
TCI’s products. TCI’s employees and sales agent’s oral statements do not constitute warranties;
these shall not be relied upon by the Buyer, and are not part of any contract for sale. All warranties
of TCI embodied in this writing and no other warranties are given beyond those set forth herein.
TCI will not accept the return of any product without its prior written approval. Please consult TCI
Customer Service for instructions on the Return Authorization Procedure.

HGP Kit Manual 3.0 Pre-Installation Planning
6
3.0 Pre-Installation Planning
Verify the Application
The HGP is a drive-applied harmonic filter designed and developed by TCI to reduce the harmonic
currents drawn from the power source by VFDs. The published HGP voltage, Power (HP or kW)
and current ratings apply to matching power (HP or kW) rated standard VFDs with six-pulse diode
bridge rectifiers. The HGP may also be sized to filter other loads such as SCR six-step drives,
SCR Direct Current (DC) motor drives, thyristor furnaces, battery chargers, electroplating supplies
or other types of nonlinear loads. In many cases, the filter power rating (HP or kW) will differ from
load power rating (HP or kW). Please contact TCI Technical Support for additional information
and support on sizing HGP harmonic filters for your non six-pulse diode front end VFD
applications.
The HGP is a passive filter connected in series with the input terminals of a VFD or several VFDs
that operate as a group. It is designed to provide a low impedance path for the major harmonic
currents demanded by the drive.
Recommendations Kit Usage
Panel design using a TCI HGP Filter Kit should be performed with appropriate engineering
supervision so the design meets the requirements based on materials utilized in the construction of
the panel, wiring practices followed by your shop, and the actual ambient conditions of the
components for each application.
HGP Kit Part Numbering System
Figure 1: HGP Kit Part Numbering System

HGP Kit Manual 4.0 Installation
7
Make sure that the HGP kit is correct for the application. The voltage ratings of the filter kit must
match the input voltage rating of the connected drive. The horsepower and current ratings of the
filter kit must be appropriate for the connected load.
Technical Specifications
Table 1 - HarmonicGuard®Passive Filter Technical Specifications
Electrical Characteristics
Voltage Rating
208, 240, 380-415, 440, 480 or 600 VAC
Phase
3
Compliance
IEEE-519 2014
Operating Frequency
50 or 60 Hz
Motor drive input power rating range
1.5 – 1250 HP for 480V units. Power range varies
depending on system voltage.
Immunity from Voltage Distortion
Less than 5% THID at full load with THVD as high as
5%*
Overload Capability
200% of current rating for 3 minutes
Environmental Conditions
Operating Temperature
Kit component ambient: 50°C (122°F)
Storage Temperature
60°C (140°F)
Elevation
Up to 2,000 m without derating
Humidity
95% non-condensing
Agency approvals or certifications
Capacitor Assemblies
UL and cUL Listed
Capacitors UR and cUR Recognized
Reactors UR and cUR Recognized
Reactors UL and cUL Listed
Performance Guarantee
To meet the requirements for the Performance Guarantee the minimum system conditions must
conform to the following:
•No more than 1.5% Source inductance
•The input VFD current waveform shall be consistent with that of a VFD with 3% AC line
reactance at full load
Please consult TCI regarding optimum filter performance when applied to DC drives.
4.0 Installation
Installation Guidelines
Installation Checklist
The following are the key points to be followed for a successful installation.
Make sure that the installation location will not be exposed to direct sunlight, corrosive
or combustible airborne contaminants, excessive dirt or liquids.
Select a mounting area that will allow adequate cooling air and maintenance access.

HGP Kit Manual 4.0 Installation
8
Make sure that all wiring conforms to the requirements of the National Electrical Code
(NEC) and/or other applicable electrical codes.
Ground the filter components using properly sized grounding conductor.
Connect three-phase power to the input terminals of the HGP, L1, L2, and L3.
Connect the output power terminals of the HGP line reactor, T1, T2, and T3, to the
input power terminals of the VFD.
Select a Suitable Location
Environment
Locating the HGP filter kit in a suitable environment will help ensure proper performance and a
normal operating life. Refer to the environmental specifications listed on Table 1 -
HarmonicGuard® Passive Filter Technical Specifications.
Warning
Unless specifically labeled as approved for such use, this equipment is
not suitable for use in an explosive atmosphere or in a "Hazardous
(Classified) Location" as defined in article 500 of the National Electrical
Code (NEC).
The unit must be installed in an area where it will not be exposed to:
•Direct sunlight
•Rain or dripping liquids (unless the filter kit is installed in a Type 3R enclosure)
•Corrosive liquids or gasses
•Explosive or combustible gases or dust
•Excessive airborne dirt and dust
•Excessive vibration
Working Space
Provide sufficient access and working space around the unit to permit ready and safe installation,
operation and maintenance. Make sure that the installation conforms to all working space and
clearance requirements of the National Electrical Code (NEC) and/or any other applicable codes.
Provide sufficient unobstructed space to allow cooling air to flow through the unit.
Mounting the Filter Kit
When mounting the filter kit in your own enclosure, you must provide an enclosure that is
adequately sized and ventilated sufficiently to prevent overheating. Refer to the applicable kit
drawings for rating and dimensions. The maximum temperature of the air around the HGP filter
capacitors, line reactor, tuning reactor, and optional PQconnect PCB should not exceed 50°C
(122°F). Consult the table of filter power dissipation below when planning enclosure ventilation.
Power Wiring
When selecting a mounting location for the HGP filter kit, plan for the routing of the power wiring.
Make sure all wiring conforms to the requirements of the NEC electrical codes and can handle the
max current required according to your filter in Table 3 – 208 V, 60Hz, HGP through Table 7 – 600
V, 60Hz, HGP.
NOTE: If your filter kit includes the PQconnect PCB please also read Section 5.0 for proper
mounting and wiring installation.
!

HGP Kit Manual 4.0 Installation
9
Filter Schematic
The schematics shown below are illustrations of typical HGP filter wiring.
Figure 1 : Typical HGP Filter Wiring for up to 480 V/800 HP
Figure 2 : HGP Filter Wiring for 480 V/900 HP and Larger Rating
SCCR Ratings
If you need an SCCR greater than the default values of components, for example, 10 kA for terminal
blocks or 5 kA for contactors, pay attention to component selection and circuit fusing. Contactors
need to be protected by line or branch tuned circuit fusing based on their published SCCR.
TCI HGP Kit include reactors that are not required to have a short circuit current rating per UL 508A
SB4.2.1 Exception 1.
See Table 2 for line fuse requirements to complete 100 kA SCCR. Larger kits include dry-type
capacitors that are not required to have a short circuit current rating per UL 508A SB4.2.1 Exception 1.
Small horsepower HGP kits (see Table 2) have a line fuse requirement in order to reduce incoming 100
kA short circuit current to 10 kA on the panel suitable for the oil filled capacitors used on these small
horsepower ratings.
*Indicates optional customer supplied material, not included in kit.

HGP Kit Manual 4.0 Installation
10
Table 2 – Customer Installed Line Fuse Requirements to Comply with 100kA SCCR
Voltage/
Frequency
Size
(HP)
Customer installed line fuse requirement for
100kA SCCR
600/60 < 25 Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
600/60 > 25 No requirement for SCCR
480/60 < 25 Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
480/60 > 25 No requirement for SCCR
440/60 < 20 Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
440/60
> 20
No requirement for SCCR
440/50 < 15
kW
Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
440/50
> 15
kW
No requirement for SCCR
415/60 < 20 Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
415/60 > 20 No requirement for SCCR
415/50 < 15
kW
Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
415/50
> 15
No requirement for SCCR
240/60 <7.5
Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
240/60
> 7.5
No requirement for SCCR
208/60 <7.5
Use appropriately rated Class J, T, or L fuse less
than or equal to 60 A
208/60
> 7.5
No requirement for SCCR
*Please review UL 508A SB4.1 in context of the final filter design (any deviation from the TCI HGP filter
of similar rating) and Table 2 – Customer Installed Line Fuse Requirements to Comply with 100kA
SCCR to confirm applicable SCCR.
KP capacitor kit KPCUL assemblies are listed UL 508 assemblies, and therefore do not carry an SCCR.
Customer or installer shall provide UL required overcurrent protection upstream of filter.

HGP Kit Manual 4.0 Installation
11
Filter Wire Sizing
Wire Sizing
Wires need to be sized based on current to be carried, wire insulation temperature rating, panel
temperature rating, bundling of wires, and appropriate codes and standards. Wire size between the
power source and the filter line reactor, as well as the line reactor and the drive input, are based
rated filter line current. Wire size in the branch circuit is based on rated tuned circuit current. If the
capacitor wiring is split into separate capacitor branches, the current each branch carries is
proportional to the value of capacitance in each branch.
Table 3 – 208 V, 60Hz, HGP
HGP Rating (HP)
Tuned Circuit Current (A)
Line Current (A)
5
10.3
16.7
7.5
17.1
24.2
10
25.7
30.8
15
34.4
46.2
20
42.9
59.4
25
51.5
74.8
30
68.6
88
40
103
114
60
129
169
75
154
211
100
205
273
150
310
396
200
412
528
250
515
660
300
641
792
Table 4 – 240 V, 60Hz, HGP
HGP Rating (HP)
Tuned Circuit Current (A)
Line Current (A)
5
10.3
15.2
7.5
13.7
22
10
17.1
28
15
25.7
42
20
34.4
54
25
42.9
68
30
51.5
80
40
68.6
104
50
77.0
130
60
103
154
75
129
192
100
154
248
125
205
318
150
257
360
200
308
480
250
410
604
300
513
722
400
641
954

HGP Kit Manual 4.0 Installation
12
Table 5 – 480 V, 60Hz, HGP
HGP Rating (HP)
Watts Loss
Tuned Circuit Current (A)
Line Current (A)
1.5
80
0.9
3
3
85
1.5
4.8
5
85
2.2
7.6
7.5
115
5.1
11
10
135
5.1
14
15
190
8.6
21
20
230
10.3
27
25
285
13.7
34
30
240
17.1
40
40
435
25.7
52
50
455
25.7
65
60
600
34.2
77
75
750
42.8
96
100
700
51.3
124
125
815
68.4
156
150
1075
77.0
180
200
1325
103
240
250
1475
128
302
300
1875
154
361
350
1725
180
414
400
1775
205
477
450
2000
231
515
500
2300
257
590
600
1975
308
720
700
1975
359
840
800
2025
410
960
900
2250
230/230 (Parallel Branches)
1080
1000
2500
257/257 (Parallel Branches)
1200
Note: Addition of PQconnect option increases Watts Loss by 10.

HGP Kit Manual 4.0 Installation
13
Table 6 – 380-415 V, 50Hz, HGP
HGP Rating (HP)
Tuned Circuit Current (A)
Line Current (A)
2
1.5
4.3
3
2.2
6.1
7.5
5.1
14
10
8.6
18
15
10.3
27
20
13.7
34
25
25.7
43
30
25.7
51
40
25.7
66
50
42.8
83
60
51.3
103
75
68.4
128
100
77.0
165
125
103
208
150
103
240
175
128
275
200
154
320
250
180
403
300
257
482
350
257
560
400
308
636
450
308
711
500
359
786
600
410
960
700
513
1120
750
513
1200
800
650
1280
900
650
1440
950
650
1520

HGP Kit Manual 4.0 Installation
14
Table 7 – 600 V, 60Hz, HGP
HGP Rating (HP)
Tuned Circuit Current (A)
Line Current (A)
5
1.8
6.1
7.5
4.1
9
10
4.1
11
15
6.8
17
20
8.2
22
25
10.9
27
30
13.7
32
40
20.5
41
50
20.5
52
60
27.4
62
75
34.2
77
100
41.0
99
125
54.7
125
150
61.6
144
200
82.1
192
250
103
242
300
123
289
350
144
336
400
164
382
450
185
412
500
205
472
600
246
576
700
287
672
800
328
780
900
369
864
1000
410
960
KDR Line Reactor Installation Instructions
Recommendations and Considerations
When installing the KDR Line Reactors on the INPUT side of the VFD, please use the following
guidelines when wiring the unit:
The KDR Line Reactor is a 3-phase device and should be wired in series and positioned on the input
side of the VFD.
All Terminal Block connectors will be marked. A1, B1, and C1 are the input terminals where the 3
phases of incoming power are to be wired. The tap for the filter connection will be marked AT, BT,
and CT. Output terminals will be marked A2, B2, and C2. Do not swap input and output terminals.
Units with copper bus or ring lug terminals are not marked. Wiring from the output terminals should
connect to the input of the VFD.
Refer to NEC (National Electrical Code) wiring practices for appropriate wire sizes for your application.
TCI recommends that these reactors be wired and located as close to the front end of the VFD as
possible to have the greatest success in both protecting the VFD as well as mitigating line harmonics.
We recommend this be 10 feet of cable or less.
Reactors generate a lot of heat in normal operations and their surfaces get very hot. In standard 40°C
ambient or less installations, a clearance of 3 inches on all sides of the reactors and its enclosure is
recommended for assisting in heat dissipation. This is a general guideline for typical applications. If
the reactor is being installed next to a heat sensitive instrument or control device, we recommend

HGP Kit Manual 4.0 Installation
15
reviewing specific requirements on heat limitations. Line reactor heat loss information is available on
the web at https://transcoil.com/products/kits-page/hgp-kits.
These reactors are designed to be floor-mounted or wall-mounted. Large open-style devices should
be panel mounted by incorporating a bracket that would act as a shelf to support the reactor and/or
enclosure. When installing an open style device in an existing control cabinet, drive cabinet, motor
control center, or other large enclosure, the reactor should be mounted in the lower half of the cabinet
to prevent hot spots or pockets of heat. Locating the reactor in the lower half of the cabinet typically
allows better thermal dissipation and heat convection. Reactors with ducts should be mounted
vertically for proper cooling.
NOTE: If the PQconnect PCB board is included in your kit please read through mounting and wiring
practices found in section 5.0.
Line Reactor Wiring
In the higher performance HGP design, tapped line reactor wiring is more critical than standard line
reactor designs. Before tapped line reactors, it did not matter if you connected the A1, B1, C1 to the
line side or the drive side, however, on the HGP, the terminals cannot be swapped. Incorrect wiring of
the line reactor will result in poor harmonic mitigation and could damage the reactor. Consult the
reactor drawing for your line reactor to verify proper filter wiring. All line reactor drawings are available
on the parts web page:
https://transcoil.com/products/kits-page/hgp-kits
The incoming line must be wired to the winding start noted as A1, B1, and C1 in the reactor
drawing. The tuned circuit is typically connected to the winding tap noted as AT, BT, and CT in
the reactor drawing, or it may be connected to the winding end noted as A2, B2, and C2 in the
reactor drawing.
•In small line reactors with nine position terminal blocks, the terminal block is wired A1, AT,
A2, B1, BT, B2, C1, CT, and C2 from left to right.
Figure 3 – Nine Position Terminal Block

HGP Kit Manual 4.0 Installation
16
•In small line reactors with six position terminal blocks, the terminal block is wired A1, A2,
B1, B2, C1, and C2 from left to right. The tap lugs AT, BT, and CT extend out from the front
face of the coil.
Figure 4 – Six Position Terminal Block
•In line reactors where current exceeds terminal block capability, ring lugs are used for all
three terminations. Note from the drawing below, the tap connection is at the lower right
side of the coil.
Figure 5 – Ring Lug Terminations
•In larger line reactors, all three terminals extend from the front of the reactor, and are
constructed from copper bus bar terminals. Unless you are an expert on start and finish
windings, consult the reactor drawing to be sure which terminal is which. In the example
below, the tap winding is on the bottom of the coil.
Table of contents
Other TCi Water Filtration System manuals
Popular Water Filtration System manuals by other brands

Schwamborn
Schwamborn STA 550 User and Maintenance Book

Beko
Beko DRYPOINT M PLUS Instructions for installation and operation

Beko
Beko CLEARPOINT L100 Instructions for installation and operation

Trox Technik
Trox Technik PFG-E Series Installation and maintenance manual

Oase
Oase Filtral UVC 1500 Commissioning

Culligan
Culligan WH-HD200-C Installation and operating instructions