manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. TE Connectivity
  6. •
  7. Measuring Instrument
  8. •
  9. TE Connectivity M242-05 Series User manual

TE Connectivity M242-05 Series User manual

CI-3K472001 Project 2215 Rev.0 04/03/13
Installation Instructions
M series Analogue DIN Panel Meters
M242-05*, M242-15*, M244-13*, M242-41*
M243-05*, M243-15*, M244-21*, M243-41*
M244-05*, M244-15*, M244-31*, M244-41*
Introduction
This product range includes a wide range of functions,
including AC Ammeters and maximum demand meters; AC
Voltmeters; DC Ammeters and milliammeters; DC
Voltmeters and millivoltmeters; Elapsed time meters;
Frequency meters; AC wattmeters and var meters and
Power factor meters.
Marking and ratings
Body side labels show function, electrical rating, and
connection diagram, where there are more than two
terminals on the unit. For two terminal units, the terminals
are connected directly across the input to be measured.
Terminal numbers are moulded into the base adjacent to
each terminal stud and corresponding numbers appear on
the connection diagram. Note that the electrical rating may
differ from the dial scale marking, and the unit side label is
definitive.
These meters are intended for a rated temperature range, is
-20/+60 deg C and up to 80% relative humidity, and only for
indoor use at an altitude of less than 2000m. Shock
maximum level is 30g.
Installation
The meter should be installed in line with the requirements
of the local electrical code. It should be installed in a dry
position, not in direct sunlight and where the ambient
temperature is reasonably stable and within ratings above.
These units are only for built in use and with terminals
inaccessible to users after installation and should be
mounted to a DIN panel cut-out up to a maximum thickness
of 5 mm. Mounting is by 2 opposed corner clamps. It may
be convenient to use a 7mm screwdriver style nut driver to
engage the barrel nuts on those models with plastic nuts,
particularly when starting the thread, but great care must be
taken not to over tighten. It is very easy to cause damage
with excessive torque when using a nut driver, so final
tightening should be performed with finger pressure only.
Fusing and connections
External voltage transformers and current transformers may
be used where appropriate to extend the range, provided
that the ratings marked on the side label are not exceeded
at point of connection to meter. These products are
designed for permanently connected use, normal condition
measurement category III, pollution degree 2 (e.g. non
ventilated panels or ventilated panels with filters, without
condensation occurring), basic insulation, for rated voltage.
Connection diagrams shown on the unit side label should
be carefully followed to ensure correct polarity and phase
rotation where applicable. Terminals are intended for use
with insulated ring lugs. Ensure a minimum spacing of
5.5mm (0.21”) between uninsulated parts of adjacent ring
lugs. Tighten terminal screws to 2Nm (1.5 ft/Lb) only.
These products do not have internal fuses therefore
external fuses must be used for safety protection under
fault conditions. Voltage input lines where required must be
fused with a quick blow fuse 1A maximum. Auxiliary supply
lines, where required must be fused with a slow blow fuse
rated 1A maximum. Current metering circuits directly
connected in line with the load must be fused at the rated
current for the meter. Where fitted, current transformer (CT)
secondaries must be connected to protective earth in
accordance with local regulations. Do not fuse CT circuits.
The equipment into which this meter is installed must have
a clearly marked adjacent means of isolating the supply
voltage to permit safe access for subsequent maintenance.
Ensure supply circuits are rated for meter VA: >4.5VA
Choice of associated components
Choose fuses of a voltage rating equal to or exceeding the
rated voltage of the circuit into which the meter is connected
and of a type and with a breaking capacity appropriate to
the supply to which the fuse is connected. Connection
wires and ring lugs should be rated for at least 1A for
voltage and auxiliary lines and to at least the rated current
for current measuring circuits. Additionally, wires for DC
current meters rated over 50mA must be rated at 75 deg C
or greater. Ensure cables and ring lugs have a voltage
insulation rating equal to or greater than the rated voltage of
the circuit to which they are connected.
CT cable impedance should ensure that CT VA rating is not
exceeded and it’s accuracy impaired.
Cleaning and maintenance
As required, wipe the front face with a damp cloth, ensuring
that no moisture enters the unit or penetrates behind the
mounting panel. No maintenance is required beyond
periodically checking the mechanical zero of the meter as
described overleaf in “commissioning”, if necessary
removing any accumulations of dust or other foreign matter
from the terminal area and ensuring that connections
remain tight.
Warnings
During normal operation, voltages hazardous to life may be
present at some of the terminals of this unit.
These instructions contain important safety information: Read
before starting installation or servicing of the equipment
Installation and maintenance should be performed only by
qualified, properly trained personnel' abiding by local
regulations.
Ensure all supplies are de-energised before attempting
connection or other procedures.
Never open circuit the secondary winding of an energised
current transformer.
If this equipment is used in a manner not specified by the
manufacturer, protection provided by the equipment may be
impaired.
Measurement categories 600V CAT III.
Caution: Risk of
Electric Shock
CI-3K472001 Project 2215 Rev.0 04/03/13
Electromagnetic Compatibility
This unit has been designed to provide protection against
EM (electro-magnetic) interference in line with requirements
of CE and other regulations. Precautions necessary to
provide proper operation of this and adjacent equipment will
be installation dependent and so the following can only be
general guidance:-
• Avoid routing wiring to these products alongside cables
and products that are, or could be, a source of
interference.
• Where required, the auxiliary supply to the unit should
not be subject to excessive interference. In some
cases, a supply line filter may be required.
• To protect the product against incorrect operation or
permanent damage, surges and transients must be
controlled. It is good EMC practice to suppress
transients and surges at the source.
• Connecting leads may require the fitting of RF
suppression components, such as ferrite absorbers or
line filters
•It is good practice to install sensitive electronic
instruments that are performing critical functions in
EMC enclosures that protect against electrical
interference causing a disturbance in function.
Commissioning
The units are calibrated at the factory for full accuracy. No
further adjustments are required except to check the zero
position.
With the meter in the intended attitude, adjust the centre
slotted adjuster for scale zero without electrical input signal.
It is
recommended that after installation, test signals are applied
to confirm correct indication and that, where applicable, CT
phasing is correct and voltage and current connections
match. Bezel
Panel cut-out
For assistance on protection requirements please contact
your local sales office.
(M242) (M243) (M244)
Bezel 48x48mm 72x72mm 96x96mm
Panel
Cut out 45x45mm 68x68mm 92x92mm
Terminal Covers
Terminal covers are supplied as standard. All types have a
push fit cover and this cover is fitted after the meter has
been installed in the panel and all wire connections made.
Tyco Electronics (UK) Ltd
a TE Connectivity Ltd. company
Freebournes Road,
Witham
Essex CM8 3AH
England
Tel: +44 (0) 1376 509509
Fax: +44 (0) 1376 509511
www.crompton-instruments.com
www.energy.te.com
Registered office:
Faraday Road, Dorcan
Swindon, SN3 5HH
Reg. no. 550 926
While TE Connectivity (TE) has made every reasonable effort to ensure the accuracy of the information in this catalog, TE does not guarantee
that it is error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current.
TE reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied
warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a
particular purpose. The dimensions in this catalog are for reference purposes only and are subject to change without notice. Specifications are
subject to change without notice. Consult TE for the latest dimensions and design specifications. TE connectivity (logo) and TE Connectivity are
trademarks of the TE Connectivity Ltd. family of companies. Crompton is a trademark of Crompton Parkinson and is used by TE Connectivity
under a licence. Other logos, product and company names mentioned herein may be trademarks of their respective owners.

This manual suits for next models

11

Other TE Connectivity Measuring Instrument manuals

TE Connectivity Integra Ri3 User manual

TE Connectivity

TE Connectivity Integra Ri3 User manual

TE Connectivity 549 User manual

TE Connectivity

TE Connectivity 549 User manual

TE Connectivity DRS-CT-3P-MOD-2T User manual

TE Connectivity

TE Connectivity DRS-CT-3P-MOD-2T User manual

TE Connectivity 549 AC User manual

TE Connectivity

TE Connectivity 549 AC User manual

TE Connectivity Integra INT-2270 Owner's manual

TE Connectivity

TE Connectivity Integra INT-2270 Owner's manual

TE Connectivity Challenger 361 Series User manual

TE Connectivity

TE Connectivity Challenger 361 Series User manual

TE Connectivity Integra INT-2270 User manual

TE Connectivity

TE Connectivity Integra INT-2270 User manual

TE Connectivity DRS-100-3P User manual

TE Connectivity

TE Connectivity DRS-100-3P User manual

TE Connectivity 805M1 User manual

TE Connectivity

TE Connectivity 805M1 User manual

TE Connectivity 832 User manual

TE Connectivity

TE Connectivity 832 User manual

Popular Measuring Instrument manuals by other brands

AGFA DX-G user manual

AGFA

AGFA DX-G user manual

KBR F96 TFT- -5 Series user manual

KBR

KBR F96 TFT- -5 Series user manual

4iiii PM100 quick start guide

4iiii

4iiii PM100 quick start guide

Ecolab Nalco Water STORM Settling Rate Monitor Installation, operation & maintenance manual

Ecolab

Ecolab Nalco Water STORM Settling Rate Monitor Installation, operation & maintenance manual

techem ultra S3 operating instructions

techem

techem ultra S3 operating instructions

Reer Micron Series INSTALLATION, TECHNICAL FEATURES, CONFIGURATION SOFTWARE

Reer

Reer Micron Series INSTALLATION, TECHNICAL FEATURES, CONFIGURATION SOFTWARE

A.R.C. Laser C-Pro user manual

A.R.C. Laser

A.R.C. Laser C-Pro user manual

Endress+Hauser Proline Prowirl D 200 Brief operating instructions

Endress+Hauser

Endress+Hauser Proline Prowirl D 200 Brief operating instructions

Mediana i20 user manual

Mediana

Mediana i20 user manual

Ametek WDG-V user manual

Ametek

Ametek WDG-V user manual

Clas Ohlson UT203 manual

Clas Ohlson

Clas Ohlson UT203 manual

PP Systems CIRAS-3 operating manual

PP Systems

PP Systems CIRAS-3 operating manual

Nic RA-7000A+SANPRA 5 quick start guide

Nic

Nic RA-7000A+SANPRA 5 quick start guide

Huvitz HLM-7000P Service manual

Huvitz

Huvitz HLM-7000P Service manual

wtw Cond 1970i operating manual

wtw

wtw Cond 1970i operating manual

Dillenger KT-LCD3 user manual

Dillenger

Dillenger KT-LCD3 user manual

KATA DGM-1500 Turva manual

KATA

KATA DGM-1500 Turva manual

KROHNE SD 200 W quick start

KROHNE

KROHNE SD 200 W quick start

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.