manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. TE Connectivity
  6. •
  7. Measuring Instrument
  8. •
  9. TE Connectivity Integra Ri3 User manual

TE Connectivity Integra Ri3 User manual

Installation and
Operating Instructions
Integra Ri3
DIN-rail digital meter for single
and three-phase electrical systems
Caution: consult instructions before installation or use
Introduction
This unit measures and displays the characteristics of single-phase
two-wire, three-phase three-wire and three-phase four-wire
supplies, including voltage, frequency, current, power and real and
reactive energy, imported and exported.
For more in-depth operating instructions, please refer to the full
manual that is available on the Crompton Instruments website, at
www.crompton-instruments.com.
Measurement
In measurement mode, the buttons control the displayed
measurement as follows:
Selects the Voltage and Frequency display screens.
Successive operations of the button select voltage,
frequency and %THD (Total Harmonic Distortion).
In Set-up mode, this is the ‘Back’ button.
Selects the Current display screens. Successive
operations select phase and neutral (3ph4w) currents,
max. demanded currents and current %THD.
In Set-up mode, this is the ‘Up’ button.
Selects the Instantaneous Power screens. Successive
operations select power (W, VAr & VA), max.
demanded power and power factor.
In Set-up mode, this is the ‘Down’ button.
Selects the Energy display screens. Successive
operations select imported/exported Wh and Varh.
Display can indicate up to 9999999·9.
Running man symbol flashes as data accumulates.
1% symbol shows that power values of <1% of range
maximum will be included in energy readings.
In Set-up mode, this is the ‘Enter’ button.
Display shows the units of measurements in use for each range.
Energy units can be set via set-up screens; other units are set
automatically.
A Demand Reset resets maximum demand readings to zero.
Setting up
To enter set-up mode, firmly press the and buttons
simultaneously and hold for 5 seconds, until the password screen
appears. Setting up is password-protected so you must enter the
correct password (default ‘0000’) before proceeding. If an incorrect
password is entered, the display reverts to measurement mode.
To exit setting-up mode, press repeatedly until the
measurement screen is restored or hold and buttons
simultaneously for 5 seconds.
Setup Menu Structure
Change password
nnnn –4-digit number, default ‘0000’.
Supply system
3-phase 3-wire or 4-wire or single phase.
CT Set the value of the CT primary in use
nnnn –4-digit number, 0001 to 9999.
dIT - Demand Integration Time
This is the period in minutes over which the current and power
readings are integrated for maximum demand measurement.
Options are: Off, 5, 8, 10, 15, 20, 30 and 60 minutes.
RSET Resets cumulative Energy and/or Demand
measurements to zero.
COMS Communication parameters for RS485 interface:
FMT –Format:
Modb Modbus protocol,
Baud rate 2400/4800/9600/19200/38400
Parity none/odd/even
Stop bits 1 (1 or 2 if parity is None)
Network address nnn –3-digit number, 1 to 247
Order: Norm/Rev –Indicates Modbus word order.
N2 Johnson Controls (JC) N2 protocol,
Network address nnn –3-digit number, 1 to 255.
Rly - Relay pulse output
kWh/kVArh (Active/reactive) Import or Export
Rate 0.001/0.01/0.1/1/10/100/1k/10k kWh or kVArh per pulse
Pulse width 200/100/60 ms.
NRGy - Energy
Unit/kilo/Mega units selection
1% limit on/off. If on, power values <1% of range max. will not
be included in energy measurements (prevents ‘creep’).
Test
Display on –all elements on to check display
dISTG –Display toggle. Each element is turned on and off
Phase sequence (V123 I123).
SOFT
Displays firmware version and build numbers.
Menu Option Selection
1.
Use the (up) and (down) keys to select the required
item from the menu. Selection does not roll over between
bottom and top of list.
2.
Press to confirm the selection.
3.
If an item flashes, then it can be adjusted by the (up) and
(down) keys. If not, there may be a further layer, e.g.
Comms - Baud rate, before adjustment is possible. Press
to select the lower layer.
4.
Having selected an option from the current menu layer, press
to confirm your selection. The SET indicator will appear.
5.
Having completed a parameter setting, press to return to
a higher menu level. The SET indicator will be removed and
you will be able to use the and keys for further
menu selection.
6.
On completion of all setting-up, press repeatedly until the
measurement screen is restored.
Number Entry Procedure
When setting up the unit, some screens require the entering of a
number. In particular, on entry to the setting up section, a
password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1.
The current digit to be set flashes and is set using the
(up) and (down) keys.
2.
Press to confirm each digit setting. The SET indicator
appears after the last digit has been set.
3.
After setting the last digit, press to exit the number
setting routine. The SET indicator will be removed.
Installation
Case Dimensions:
Width 71·3 mm, Depth 57·5 mm, Length 90·5 mm
Length including fixing tag 93·5 mm.
The unit is intended for mounting on a standard DIN rail within a
suitable metallic or flame proof enclosure (IP2X minimum) such that
only the front face (display) can be accessible in normal use. Avoid
mounting the unit where there is excessive vibration; in excessive
direct sunlight; or outside a reasonably stable ambient temperature
of -10 to +55°C
Safety
The unit is designed in accordance with BS EN 61010-1:2001
(IEC 61010-1:2001) –Permanently connected use, Normal
condition. Installation category III, pollution degree 2, basic
insulation for rated voltage. Measurement Category III.
EMC Installation Requirements
Whilst this unit complies with all relevant EU EMC (electro-magnetic
compatibility) regulations, any additional precautions necessary to
provide proper operation of this and adjacent equipment will be
installation dependent and so the following can only be general
guidance:
Avoid routing wiring to this unit alongside cables and
products that are, or could be, a source of interference.
The auxiliary supply to the unit should not be subject to
excessive interference. In some cases, a supply line filter
may be required.
To protect the product against incorrect operation or
permanent damage, surge transients must be controlled.
It is good EMC practice to suppress transients and surges
at the source. The unit has been designed to
automatically recover from typical transients; however in
extreme circumstances it may be necessary to temporarily
disconnect the auxiliary supply for a period of greater than
5 seconds to restore correct operation.
Screened communication leads are required. These and
other connecting leads may require the fitting of RF
suppression components, such as ferrite absorbers, line
filters etc., if RF fields cause problems.
It is necessary to wind the three current inputs through
separate ferrite rings an example part number Wurth 742
701 110, a minimum of 6 times.
It is good practice to install sensitive electronic instruments
that are performing critical functions in EMC enclosures
that protect against electrical interference causing a
disturbance in function.
Wiring
Input connections are made to screw clamp terminals. Choice of
cable should meet local regulations for the operating voltage and
current. Terminals are suitable for Copper wire only, 0.05-2.5mm²
(30-12AWG). Recommended tightening torque 0.5/0.6Nn (4.4/5.3
Lbf in) For UL approved installations wiring should conform to
National Electrical Code (NEC) Class 1, rated 600V / 60°C
minimum.
The current inputs of these products are designed for
connection into systems via current transformers only,
conforming to IEC 60044-1 or ANSI / IEEE C57.13
All negative current inputs are commoned inside the unit and
grounding should be at one point only. To minimise measurement
errors, the CTs should be grounded as shown in the wiring
diagram.
CT secondaries must be grounded in accordance with local
regulations. It is desirable to make provision for shorting links to be
made across CTs to permit easy replacement of a unit should this
ever be necessary.
Additional considerations for three wire systems
The neutral terminal (terminal N) is indirectly connected to the
voltage input terminals (terminals L1, L2, L3). When connected to
a three wire system the neutral terminal will adopt a potential
somewhere between the remaining lines.
If external wiring is connected to the neutral terminal it must be
connected to either the neutral line or earth (ground) to avoid the
possibility of electric shock from the neutral terminal.
Danger: Risk of Elecric Shock
During normal operation, voltages hazardous to life may
be present at some of the terminals of this unit.
Installation and servicing should be performed only by
qualified, properly trained personnel abiding by local
regulations. Ensure all supplies are de-energised before
attempting connection or other procedures.
Terminals should not be user accessible after installation
and external installation provisions must be sufficient to
prevent hazards under fault conditions.
This unit is not intended to function as part of a system
providing the sole means of fault protection - good
engineering practice dictates that any critical function be
protected by at least two independent and diverse
means.
The unit does not have internal fuses therefore external
fuses must be used for protection and safety under fault
conditions.
Never open-circuit the secondary winding of an
energised current transformer.
This product should only be operated with the CT
secondary connections earthed.
If this equipment is used in a manner not specified by the
manufacturer, protection provided by the equipment may
be impaired.
Auxiliary circuits (communication & relay outputs) are
separated from metering inputs and 110-400V supply
circuits by at least basic insulation. Any equipment
connected to these auxiliary circuits that may be
accessible in normal use, should provide supplementary
insulation rated 400Vrms minimum between auxiliary
circuits and any accessible parts, such that at least basic
insulation is maintained under fault conditions. The
connection at the remote end of such auxiliary circuits
should not be accessible in normal use. Depending on
application, equipment connected to auxiliary circuits
may vary widely. The choice of connected equipment or
combination of equipment should not diminish the level
of user protection specified in the end use application.
Fusing
This unit must be fitted with external fuses in voltage and auxiliary
supply lines. Voltage input lines must be fused with a quick blow
fuse 1A maximum. Auxiliary supply lines must be fused with a slow
blow fuse rated 1A maximum. Choose fuses of a type and with a
breaking capacity appropriate to the supply and in accordance with
local regulations. For UL approved installation, use UL listed branch
circuit fuses. A suitable switch or circuit breaker should be included
in the installation. It should be positioned so as to be easy to
operate, in close proximity to the equipment, and clearly identified
as the disconnecting device.
Earth/Ground Connections
For safety reasons, current transformer secondary connections
should be grounded in accordance with local regulations. Under no
circumstances should this product be operated without this earth
connection.
Maintenance
In normal use, little maintenance is needed. As appropriate for
service conditions, isolate from electrical power, inspect the unit
and remove any dust or other foreign material present. Periodically
check all connections for freedom from corrosion and screw
tightness, particularly if vibration is present.
The front of the case should be wiped with a dry cloth only. Use
minimal pressure, especially over the viewing window area. If
necessary wipe the rear case with a dry cloth. If a cleaning agent is
necessary, isopropyl alcohol is the only recommended agent and
should be used sparingly. Water should not be used. If the rear
case exterior or terminals should be contaminated accidentally with
water, the unit must be thoroughly dried before further service.
Should it be suspected that water might have entered the unit,
factory inspection and refurbishment is recommended.
In the unlikely event of a repair being necessary, it is recommended
that the unit be returned to the factory or nearest Crompton
Instruments/Tyco Electronics service centre.
Specification
Measured Parameters
The unit can monitor and display the following parameters of a
single phase, 3-phase 3-wire or 3-phase 4-wire supply:
Voltage and Frequency
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w)
Voltages between phases 173 to 500V a.c. (3p only)
Frequency in Hz
Percentage total voltage harmonic distortion (THD%) for
each phase to N (not for 3p3w supplies)
Percentage voltage THD% between phases (3p only)
Current
Current on each phase –1 to 9999A range, set by external
Current transformer(s) (CTs)
Neutral current (calculated) (3p4w supplies only)
Maximum demand currents on each phase, since the last demand
reset
Maximum neutral demand current, since the last demand
Reset (3p4w supplies only)
Current THD% for each phase
Power and Power Factor
Instantaneous power:
Power 0 to 3600 MW
Reactive Power 0 to 3600 MVAr
Volt-amps 0 to 3600 MVA
Maximum demanded power since last Demand reset
Power factor
Energy Measurements
Imported energy 0 to 9999999·9 Wh, kWh or MWh
Exported energy 0 to 9999999·9 Wh, kWh or MWh
Imported reactive energy 0 to 9999999·9 VArh, kVArh or MVArh
Exported reactive energy 0 to 9999999·9 VAhr, kVArh or MVArh
Measured Inputs
Voltage inputs through 4-way fixed connector with 2·5mm²
(12AWG) stranded wire capacity. 3-Phase 3- & 4-wire, and Single-
phase 2-wire. Line frequency measured from L1 voltage or L3
voltage.
Three current inputs (six physical terminals) with 2·5mm² (12AWG)
stranded wire capacity for connection of external CTs. Nominal
rated input current 5A a.c. rms.
Range of Use
Voltage
5 to 120% of Range Maximum
(below 5% of range maximum voltage, current
indication may only be approximate)
Current
1 to 120% of nominal
Power factor
1 to 0, leading or lagging
Active power
1 to 144% of nominal, 3600 MW maximum
Apparent power
1 to 144% of nominal, 3600 MVA maximum
Power is only registered when voltage and current are within their
respective range of use.
Power factor is only indicated when the measured VA is over 3% of
range maximum.
Accuracy
Voltage
0·5% of range maximum
Current
0·5% of nominal
Neutral current
4% of nominal (calculated)
Frequency
0·2% of mid-frequency
Power factor
1% of unity (0.01)
Active power (W)
±1% of range maximum
Reactive power (VAr)
±1% of range maximum
Apparent power (VA)
±1% of range maximum
Active energy (Wh)
Class 1 IEC 62053-21 section 4.6
Reactive energy (VARh)
±1% of range maximum
Total harmonic distortion
1% up to 31st harmonic (above
30% THD the error in this reading
may increase to 1·5% for the
higher harmonics)
Temperature co-efficient, typ.
Voltage and current = 0·013%/°C
Active energy = 0·018%/°C
Response time to step input
1s, typical, to >99% of final
reading, at 50 Hz.
Error change due to variation
of an influence quantity in the
manner described in Section
6 of IEC 688:1992
2 error allowed for the reference
condition applied in the test.
Error due to temperature variation
as above.
Error in measurement when a
measurand is within its
measuring range, but outside
its reference range
2 error allowed at the end of the
reference range adjacent to the
section of the measuring range,
where the measurand is currently
operating / being tested.
Tyco Electronics (UK) Ltd
Freebournes Road,
Witham
Essex CM8 3AH
England
Tel: +44 (0) 1376 509509
Fax: +44 (0) 1376 509511
www.crompton-instruments.com
www.energy.te.com
CI-3K46701 Project 2191 rev 07 21/01/21
Registered office:
Faraday Road, Dorcan
Swindon, SN3 5HH
Reg. no. 550 926
While TE Connectivity (TE) has made every reasonable effort to ensure the accuracy of the information in this catalog, TE does not guarantee
that it is error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current.
TE reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied
warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a
particular purpose. The dimensions in this catalog are for reference purposes only and are subject to change without notice. Specifications are
subject to change without notice. Consult TE for the latest dimensions and design specifications. TE connectivity (logo) and TE Connectivity are
trademarks of the TE Connectivity Ltd. family of companies. Other logos, product and company names mentioned herein may be trademarks of
their respective owners. Crompton is a trademark of Crompton Parkinson and is used by TE Connectivity under a licence.
Auxiliary Supply
Two-way fixed connector with 2·5mm2 (12AWG) stranded wire
capacity. 110 to 400V a.c. 50/60Hz ±10% or 120V to 350V d.c.
±20%. Consumption < 10W.
Pulse Relay Output
The pulse relay output can be set to generate pulses to represent
imported kWh, exported kWh, imported kVArh or exported kVArh.
Rate can be set to generate 1 pulse per:
0·001 = 1 Wh/VArh
0·01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1k = 1 MWh/MVArh
10k = 10 MWh/MVArh
The rate cannot be set to a value that could result in more
than 2 pulses per second.
Pulse width 200/100/60 ms.
Relay Rating 240V ac 50mA
RS485 Output for Modbus or JC N2 Protocol
For Modbus protocol, the following RS485 communication
parameters can be configured from the Set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400
Parity none/odd/even
Stop bits 1 or 2
RS485 network address nnn –3-digit number, 1 to 247
Modbus Word order Shows the word order (Hi/Lo) of the 8-bit
bytes in the Modbus message format. This setting can only be
changed from the Modbus port.
Note that with odd or even parity, Stop Bits are forced to one.
For JC N2 protocol, only the RS485 network address can be
configured. The range of addresses is 1 to 255.
For technical assistance please contact your nearest Crompton
service centre, or:
Tyco Electronics (Crompton Instruments) Ltd
Freebournes Road
Witham
CM8 3AH
United Kingdom
Tel: +44 (0) 1376 509509
Fax: +44 (0) 1376 509511
Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to
a minor degree. Accuracy is verified under nominal value (within
the specified tolerance) of these conditions.
Ambient temperature
23°C ±1°C
Input waveform
50 or 60Hz ±2%
Input waveform
Sinusoidal (distortion factor <0·005)
Auxiliary supply voltage
Nominal ±1%
Auxiliary supply frequency
Nominal ±1%
Auxiliary supply waveform
(if AC)
Sinusoidal (distortion factor <0·05)
Magnetic field of external
origin
Terrestrial flux
Environment
Operating temperature
-10°C to +55°C*
Storage temperature
-20°C to +70°C*
Relative humidity
0 to 90%, non-condensing
Altitude
Up to 2000m
Warm up time
1 minute
Vibration
10Hz to 50Hz, IEC 60068-2-6, 2g
Shock
30g in 3 planes
*Maximum operating and storage temperatures are in the context of
typical daily and seasonal variation.
Mechanics
DIN rail dimensions
72 x 90 mm (WxH) per DIN 43880
Mounting
DIN rail (DIN 43880)
Sealing*
IP20 (minimum)
Material
Self-extinguishing UL 94 V-0
*Not evaluated by UL
Approval, Certification, and Standards Compliance
RoHS compliant. (Although this class of product is presently
excluded from the RoHS regulations, the unit has been designed
and manufactured in compliance with the RoHS regulations.)
EMC Emissions BS EN 61326, Class A (Industrial)
EMC Immunity BS EN 61326, Class A (Industrial)
Safety BS EN 61010-1
UL61010-1

Other TE Connectivity Measuring Instrument manuals

TE Connectivity M242-05 Series User manual

TE Connectivity

TE Connectivity M242-05 Series User manual

TE Connectivity Challenger 361 Series User manual

TE Connectivity

TE Connectivity Challenger 361 Series User manual

TE Connectivity Integra INT-2270 User manual

TE Connectivity

TE Connectivity Integra INT-2270 User manual

TE Connectivity 805M1 User manual

TE Connectivity

TE Connectivity 805M1 User manual

TE Connectivity Integra INT-2270 Owner's manual

TE Connectivity

TE Connectivity Integra INT-2270 Owner's manual

TE Connectivity 832 User manual

TE Connectivity

TE Connectivity 832 User manual

TE Connectivity DRS-100-3P User manual

TE Connectivity

TE Connectivity DRS-100-3P User manual

TE Connectivity 549 AC User manual

TE Connectivity

TE Connectivity 549 AC User manual

TE Connectivity 549 User manual

TE Connectivity

TE Connectivity 549 User manual

TE Connectivity DRS-CT-3P-MOD-2T User manual

TE Connectivity

TE Connectivity DRS-CT-3P-MOD-2T User manual

Popular Measuring Instrument manuals by other brands

TESTO 557 quick start guide

TESTO

TESTO 557 quick start guide

LIBRA S22 Operation manual

LIBRA

LIBRA S22 Operation manual

Masimo O3 Regional Oximeter Operator's manual

Masimo

Masimo O3 Regional Oximeter Operator's manual

Leuze AMS 301i Original operating instructions

Leuze

Leuze AMS 301i Original operating instructions

PSI LaiPen LP 110 Instruction guide

PSI

PSI LaiPen LP 110 Instruction guide

Vimar 02963 quick start guide

Vimar

Vimar 02963 quick start guide

Keysight Streamline Series Configuration guide

Keysight

Keysight Streamline Series Configuration guide

CORNET ED-85EXPlus5 user manual

CORNET

CORNET ED-85EXPlus5 user manual

PEWA Amprobe ACF3000 AK operating instructions

PEWA

PEWA Amprobe ACF3000 AK operating instructions

Huvitz HLM-7000P Service manual

Huvitz

Huvitz HLM-7000P Service manual

Badger Meter ModMAG M Series installation manual

Badger Meter

Badger Meter ModMAG M Series installation manual

Ecom EN2 operating instructions

Ecom

Ecom EN2 operating instructions

Compact Instruments Advent A2101 operating instructions

Compact Instruments

Compact Instruments Advent A2101 operating instructions

Keithley 617 instruction manual

Keithley

Keithley 617 instruction manual

Edwards AIM-S-NW25 instruction manual

Edwards

Edwards AIM-S-NW25 instruction manual

MICRODOS MP2-HT PULSE Programming instructions

MICRODOS

MICRODOS MP2-HT PULSE Programming instructions

Wurth Master WDM 201 operating instructions

Wurth Master

Wurth Master WDM 201 operating instructions

Grove Slide Potentiometer manual

Grove

Grove Slide Potentiometer manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.