teca AHP-1801X User manual

ProductInformationPacket
ModelAHP-1801X
SolidState,NEMA4X,AirConditioner
withTC-1FTemperatureControl
Part#0-01F1-2-000
Thankyouforyourpurchase.Informationhasbeenenclosedregardingthe
installation,specifications,andwiringofyoursolid-stateassembly.
Pleasereadandfollowallinstructionscarefullybeforeinstallation.Onlyqualified
techniciansshouldinstallthisequipment.
Ifyouhaveanyquestionsregardingyourequipment,pleasedonothesitateto
callusat773-342-4900,andwewillbehappytoassistyou.Weareopenfrom
8:00am-4:30pmCentralTime.
Includedinthispacketyouwillfind:
InstallationNotesforAirConditioners
ProductLiteratureandSpecifications
AssemblyDrawing#1800-B-A18
WiringDrawing#SK180612
InstallationDrawing#1800-A-F49
TemperatureControlInformation
WarrantyInformation

ImportantInstallationNotesforAirConditioners
Seal
Ambient
Air
Path
Enclosure
InternalAir
Path
MountingStyles:
Vertical(Side/Front/Back)Mounting:
CondensateRemovalSystem:
TopMounting:
Maintenance:
Cautions:
Notesoncondensation:
Both‘thrumount’and‘flushmount’unitscanbepositionedin
anyorientationandonanyenclosuresurface.Itisimportanttoconsiderinterior
airflowpatternswhendeterminingthemountinglocation.Alsoofimportance
isanunrestrictedflowofambientairthruthehotsideheatexchanger.Ease
ofaccessandinspectionmustbeconsideredforthoseapplicationsin
particularlysevereenvironmentswhichmayrequireoccasional
maintenance.
Verticalmountingreferstotheverticaldirectionofthecoldside
orinteriorfinsandisrecommendedforapplicationswithhigh
humidity,poorandincompletecabinetsealsoranyconditionwhich
maycausethecoldsidefinstobemaintainedattemperatures
belowthedewpointforlongperiodsoftimeallowingforthe
formationofcondensation.Theverticalfindirectionprovidesadrip
pathwhereuponcondensationcanbecollectedviaamoisture
removalsystem(standardonFHP-units)oradrippanpositioned
belowthecoldsidefins.Drippansareoptionalforthrumountunits.
AllFHP-SeriesandAHP-1400airconditionerscontainabuilt-incondensateremovalsystem.Thecondensatekitconsistsofa
antifungalspongewithacondensatewick.PVCtubingisalsoprovidedfordrainage.Drippansareoptionalforthrumountunits
whichmustbeevaluatedonanindividualbasis.Equationsdefiningarelationshipbetweenthecoldsidefinandenclosure
temperaturesareprovidedtoassistintheevaluation.
Thoughoftentheeasiestlocationtomountitisoftenthemostdifficulttoprotectfromcondensationinthisorientationduetothe
finorientation,gravityandanysusceptiblecomponentsbelow.Ifadrippanisemployedbytheenduserusecautionto place
thepanfarenoughawayfromtheinternalfantominimizetherestrictionofairflow.Thepanshouldcoverthefinendsaswellas
thefanarea.Whenthereisachoice,theverticalorientationispreferredbymostusers.
Sincethetechnologyissolid-state,therearenofilters,compressors,orfluorocarbonstomaintain.Theonlymovingpartsare
thefans.Itisrecommendedforharshordirtyenvironmentsthattheheatsinksbecleanedfromtimetotime.Thiscanbe
accomplishedbydirectingcompressedairovertheexternalfinsoronNEMA4versionsbyhosingtheunitdown.Thiswill
increasetheoveralllifeandperformanceofthesystem.
Takecarewhenmountingnottodamagethesealbetweenthehotandcoldsidesinks.Donotattempttomountaunittoa
warpedsurfaceortrytomaketheunitsmountingsurfaceconformtoanunflatsurface.Donotpinchordamageanyleadswhen
mounting.Donotovertightenanyinstallationscrew,usereasonableforce.Alwaysmountwithanycondensatedraindown.
Donotcompressthecoldsidebetweenthehotsideandanyothersurface.Donotobstructtheairflowoneitherside.When
mountingconsiderthenaturalairflowsoftheenclosure.Connectpoweronlyaftertheinstallationiscomplete.
Condensationoccursat thecoldsidefinswhenthesurfacetemperaturegoesbelowthedewpoint.Toreduceorremove
condensate,considerthefollowing:
•RegulatetheFinTemperatureabovetheDewpoint.
•KeepEnclosureClosedandSealedfromOutsideHumidity.
•UseDesiccant(MoistureabsorbingGranules.)
•EmployCondensateRemovalSystem/DripPans.
Ifyouhaveanyquestionsregardingyourinstallation,Pleasefeelfreetocontactourtechnicaldepartmentforassistanceat773-
342-4900.

AHP-1800 Air Conditioner
Air Cooled 120 VAC, 240 VAC Input
Through Mounted 1100 BTU/HR
NEMA-12, 4, 4X
FEATURES
• Compact, (18” L X 12.35” W X 9.69”D)
• Excels in high ambient temperatures
• Environmentally Safe
• Dual voltage versions available, consult factory.
• No compressor, fluorocarbons or filters
• Virtually maintenance-free operation
• Stainless steel exterior housing
• Versions to withstand corrosive environments,
shock and vibration
• Mounts and operates in any orientation
• Easy to use Pivot Clean feature
• Agency approvals: UL 1995, CSA 22.2, CE
INCLUDES
• Temperature control
• Mounting gasket and hardware
• Power input line cord
SPECIFICATIONS OPERATING OPERATING
VOLTAGE CURRENT WEIGHT TEMP. AMBIENT ENCLOSURE
MODEL PART NUMBER VAC AMPS. LBS.(KG) CONTROL TEMPERATURE TEMPERATURE ENVIRONMENT
50/60 HZ RANGE °C RANGE °C
AHP-1800 0-0180-0-000 120 8.0 46(21) TC-6F -40/+70 -10/+60 NEMA-12
AHP-1800 0-0150-0-000 120 8.0 46(21) EXT* -40/+70 -10/+60 NEMA-12
AHP-1800 0-01F0-0-000 120 8.0 46(21) TC-1F -40/+70 -10/+60 NEMA-12
AHP-1800HC 0-0130-1-000 120 8.0 46(21) TC-3F -40/+70 -10/+60 NEMA-12
AHP-1800HC 0-0150-1-000 120 8.0 46(21) EXT* -40/+70 -10/+60 NEMA-12
AHP-1802 0-0182-0-000 240 5.0 46(21) TC-6F -40/+70 -10/+60 NEMA-12
AHP-1802 0-0152-0-000 240 5.0 46(21) EXT* -40/+70 -10/+60 NEMA-12
AHP-1802 0-01F2-0-000 240 5.0 46(21) TC-1F -40/+70 -10/+60 NEMA-12
AHP-1802HC 0-0132-1-000 240 5.0 46(21) TC-3F -40/+70 -10/+60 NEMA-12
AHP-1802HC 0-0152-1-000 240 5.0 46(21) EXT* -40/+70 -10/+60 NEMA-12
AHP-1801 0-0181-0-000 120/240 8.0/5.0 46(21) TC-6F -40/+70 -10/+60 NEMA-12
AHP-1801 0-01F1-0-000 120/240 8.0/5.0 46(21) TC-1F -40/+70 -10/+60 NEMA-12
AHP-1801HC 0-0131-1-000 120/240 8.0/5.0 46(21) TC-3F -40/+70 -10/+60 NEMA-12
AHP-1800XE 0-0180-4-000 120 8.0 47(21.4) TC-6F -40/+70 -10/+60 NEMA-4
AHP-1800XE 0-0150-4-000 120 8.0 47(21.4) EXT* -40/+70 -10/+60 NEMA-4
AHP-1800XE 0-01F0-4-000 120 8.0 47(21.4) TC-1F -40/+70 -10/+60 NEMA-4
AHP-1800XEHC 0-0130-5-000 120 8.0 47(21.4) TC-3F -40/+70 -10/+60 NEMA-4
AHP-1800XEHC 0-0150-5-000 120 8.0 47(21.4) EXT* -40/+70 -10/+60 NEMA-4
AHP-1802XE 0-0182-4-000 240 5.0 52(23.6) TC-6F -40/+70 -10/+60 NEMA-4
AHP-1802XE 0-0152-4-000 240 5.0 52(23.6) EXT* -40/+70 -10/+60 NEMA-4
AHP-1802XE 0-01F2-4-000 240 5.0 52(23.6) TC-1F -40/+70 -10/+60 NEMA-4
AHP-1802XEHC 0-0132-5-000 240 5.0 52(23.6) TC-3F -40/+70 -10/+60 NEMA-4
AHP-1802XEHC 0-0152-5-000 240 5.0 52(23.6) EXT* -40/+70 -10/+60 NEMA-4
AHP-1800X 0-0180-2-000 120 8.0 47(21.4) TC-6F -40/+70 -10/+60 NEMA-4X
AHP-1800X 0-0150-2-000 120 8.0 47(21.4) EXT* -40/+70 -10/+60 NEMA-4X
AHP-1800X 0-01F0-2-000 120 8.0 47(21.4) TC-1F -40/+70 -10/+60 NEMA-4X
AHP-1800XHC 0-0130-3-000 120 8.0 47(21.4) TC-3F -40/+70 -10/+60 NEMA-4X
AHP-1800XHC 0-0150-3-000 120 8.0 47(21.4) EXT* -40/+70 -10/+60 NEMA-4X
AHP-1801X 0-0181-2-0000 120/240 8.0/6.0 47(21.4) TC-6F -40/+70 -10/+60 NEMA-4X
AHP-1801X 0-01F1-2-000 120/240 8.0/6.0 47(21.4) TC-1F -40/+70 -10/+60 NEMA-4X
AHP-1801XHC 0-0131-3-000 120/240 8.0/6.0 47(21.4) TC-3F -40/+70 -10/+60 NEMA-4X
AHP-1859XEHC†0-01LB-5-000 100-240 5.0/2.0 47(21.4) TC-5300D -40/+70 -10/+60 NEMA-4
AHP-1859HC†0-01LB-1-000 100-240 5.0/2.0 47(21.4) TC-5300D -40/+70 -10/+60 NEMA-12
† Precise temperature control model * Unit is set for 5-32 VDC external signal, relay(s) included Consult factory for shock and vibration models
TECA 1-888-TECA-USA (832-2872) www.thermoelectric.com
OPTIONS
• Other temperature settings for single set point controls
• Custom finishes

Equation of line: y=⌬⌬⌻⌻(°C) x=Capacity (Watts)
Ambient Temp 20°C 40°C 60°C
Enclosure Air y=.122x-37.0 y=.122x-39.7 y=.122x-42.3
Cold Sink y=.09x-37.0 y=.09x-39.7 y=.09x-42.3
MOUNTING STYLE
Through Mounted
ENVIRONMENTS SERVED
NEMA-12 IP 52
NEMA-4,4X IP 56
RATING (TRADITIONAL)
1100 BTU/hr @ 0 °F ⌬T
1420 BTU/hr @ +20 °F ⌬T
RATING (DIN 3168)
322 Watts L35 L35
210 Watts L35 L50
AHP-1800
DIMENSIONS
Air Conditioner - Air Cooled
www.thermoelectric.com 1-888-TECA-USA (832-2872) TECA
PERFORMANCE CURVE
PERFORMANCE CURVE
Air Flow Pattern




Power Temperature Controllers
TECA 1-888-TECA-USA (832-2872) www.thermoelectric.com
MODEL PART NOTES TEMP @ TEMP @ T1-T2 RESET RESET TEMP @ T3 OPERATING SWITCHING SWITCHING
NUMBER NUMBER T1 °C T2 °C (MAX) °C (TYP) °C°C VOLTAGE VOLTAGE CURRENT MAX.
TC-6F 6F-00A-00-000 No Relay 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On NA NA NA
TC-6F-AC 6F-03T-00-000 VAC Version 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On 85-250 VAC 24-280 VAC 10
TC-6F-DC 6F-43D-00-000 12/24 VDC 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On 12/24 VDC 0-100 VDC 20 ADC
TC-6F-DC 6F-33D-00-000 48 VDC 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On 48 VDC 0-100 VDC 20 ADC
MODEL PART NOTES COOL HEAT RESET RESET OPERATING SWITCHING SWITCHING H-BRIDGE
NUMBER NUMBER TEMP. °C TEMP. °C (MAX) °C (TYP) °C VOLTAGE VOLTAGE CURRENT MAX. RELAYS
TC-3F-AC 3F-04R-00-000 VAC Version 35 +/- 5 15 +/- 5 6.5 3 85-280 VAC 24-280 VAC 10 AMPS N/A
TC-3F-DC 3F-44G-00-000 12/24 VDC 35 +/- 5 15 +/- 5 6.5 3 3.5-32 VDC 0-100 VDC 20 ADC N/A
TC-3F-DC 3F-44P-00-000 12/24 VDC 35 +/- 5 15 +/- 5 6.5 3 3.5-32 VDC 0-100 VDC 20 ADC Solid State
Model TC-6F (Cool Only) thermostat is designed using two temperature power switches in conjunction with a solid state relay. A three position
switch is provided to adjust temperature settings.
Model TC-3F (Heat/Cool) thermostat incorporates the same technology as the TC-6F. It contains a single setting each for both heating and
cooling as referenced below:
TC-1F POWER TEMPERATURE SWITCHES
Models TC-1F power temperature controller, with small tolerance and reset differential, are
the simplest and most cost effective way to control a cooling or heating device (VAC or VDC)
without a need for a relay. For circuits that have higher current draw simply use them in
conjunction with a solid state relay.
TC-6F COOL ONLY
TC-3F HEAT AND COOL
Part Numbers:
Mode Part Number Note
Cool TC-1C-XX switch closes on temperature rise
Heat TC-1H-XX switch closes on temperature drop
XX: Specify temperatures 20 °C, 25 °C, 30 °C, 35 °C for cool mode
and 10°C, 15 °C for heat mode
Example: TC-1C-20 and TC-1H-10
VOLTAGE CURRENT SET POINT T RESET
AMPS OLERANCE °CDIFFERENTIAL °C
125 VAC 2 +/- 3 3 - 6
250 VAC 1.3 +/- 3 3 - 6
12 VDC 2 +/- 3 3 - 6
24 VDC 1.3 +/- 3 3 - 6 Dimensions: Inches [Millimeters]
MODEL PART NOTES COOL HX HEAT RESET RESET OPERATING SWITCHING SWITCHING H-BRIDGE
NUMBER NUMBER TEMP. °C TEMP. °C TEMP. °C (MAX) °C (TYP) °C VOLTAGE VOLTAGE CURRENT MAX. RELAYS
TC-7F-DC 7F-24G-00-000 24 VDC 35 +/- 3 25 +/- 3 10 +/- 3 6.5 3 24 VDC 24 VDC 20 ADC N/A
TC-7F-DC 7F-24O-00-001 24 VDC 35 +/-3 25 +/-3 10 +/-3 6.5 3 24 VDC 24 VDC 12 ADC Solid State
TC-7F-DC 7F-24S-00-000 12 VDC 35 +/-3 25 +/-3 10 +/-3 6.5 3 12 VDC 12 VDC 20 ADC Solid State/Mechanical
TC-7F-DC 7F-24T-00-000 24 VDC 35 +/-3 25 +/-3 10 +/-3 6.5 3 24 VDC 24 VDC 20 ADC Solid State/Mechanical
TC-7F-DC 7F-24U-00-000 48 VDC 35 +/-3 25 +/-3 10 +/-3 6.5 3 48 VDC 48 VDC 20 ADC Solid State/Mechanical
Model TC-7F (Heat/Cool) thermostat incorporates the same technology as the TC-3F. It contains a single setting each for both heating and
cooling and a heat exchanger mode (ECO-Mode).
TC-7F HEAT/COOL WITH ECO-MODE
TC-4F COOL ONLY WITH ECO-MODE
Model TC-4F is simillar to TC-1F plus it has a 2nd power switch for heat exchanger mode (ECO-Mode). The active cool set point for TC-4F is 35 °C
and for heat exchanger mode (ECO-Mode) is 25 °C.
MODEL PART NOTES HX COOL RESET RESET OPERATING SWITCHING ACTIVE MODE ECO-MODE
NUMBER NUMBER TEMP. °C TEMP. °C (MAX) °C (TYP) °C VOLTAGE VOLTAGE SWITCHING SWITCHING
CURRENT MAX. CURRENT
TC-4F-DC 4F-24C-00-000 12/24/48 VDC 25 +/- 3 35 +/- 3 6.5 3 12/24/24 VDC 0-100 VDC 12 ADC 1.3 ADC
TC-4F-DC 4F-24D-00-000 12/24/48 VDC 25 +/- 3 35 +/- 3 6.5 3 12/24/48 VDC 0-100 VDC 20 ADC 1.3 ADC
TC-4F-DC 4F-24E-00-000 12/24/48 VDC 25 +/- 3 35 +/- 3 6.5 3 12/24/48 VDC 0-100 VDC 40 ADC 1.3 ADC
For custom variations of any of the controls, contact TECA.

LIMITEDWARRANTY
Intheeventadefectinmaterialorworkmanshipisdiscoveredinanyof
TECA’sproductswithinoneyearafterthedatetheyaredeliveredtoBuyer,
:(a)TECAisnotifiedofthedefectinwritingbycertifiedmailwithin14
daysofthedateofdiscovery;(b)TECAmaytheneither,atitssolediscretion,
inspecttheproductatBuyer’slocation,orrequirethattheproductbemade
availableatBuyer’sexpenseatTECA’spremisesforTECA’sinspectionwithin
14daysofthedateofnotification;and(c)theproductsaredefectiveandthe
defectsresultfromfaultymaterialsand/orworkmanshipandnotinanyway
fromaccident,misuse,misapplication,mishandling,modification,oralteration
bytheBuyerortheshipper,TECAshall,atitssoleoption,repairor
exchangedefectiveproductsfreeofchargetoBuyer,orcredittobuyerthe
priceofthedefectiveproducts.ALLOTHERWARRANTIES,EXPRESSOR
IMPLIED,AREEXCLUDED,INCLUDINGBUTNOTLIMITEDTOTHE
IMPLIEDWARRANTIESOFMERCHANTABILITYANDFITNESSFORA
PARTICULARPURPOSE.INNOEVENTSHALLTECABELIABLEFOR
ANYCLAIMBASEDUPONBREACHOFEXPRESSORIMPLIED
WARRANTYORANYOTHERDAMAGESWHETHERSPECIAL,INDIRECT,
INCIDENTAL,CONSEQUENTIAL,LOSTPROFITS,BUSINESS
INTERRUPTION,ORLOSSOFBUSINESSORCUSTOMER
RELATIONSHIPS.
Inordertoreturnmerchandiseforanyreason(repair,replacement,orcredit)
areturnauthorizationnumbermustbeissuedbyTECA.Newmerchandise
maynotbereturnedforcreditbeyond60daysfromshipment.Chargesfor
incidentalorotherdamagesmayalsobemade.Allreturnedgoodsmustbe
sentfreightprepaid.Arestockingchargeof15%willapply.Onspecial
equipmentandcustommodifiedequipmentorders,additionalincremental
cancellationchargesmaybemade.
andif
then
RETURNEDGOODS,RESTOCKINGCHARGES
This manual suits for next models
49
Table of contents
Other teca Air Conditioner manuals

teca
teca AHP-401 User manual

teca
teca AHP-270 User manual

teca
teca AHP-270XE User manual

teca
teca AHP-1200FF User manual

teca
teca AHP-1200XP User manual

teca
teca 0-018C-4-000 User manual

teca
teca AHP-250XEHC User manual

teca
teca AHP-270FF User manual

teca
teca AHP-1800 Series User manual

teca
teca HP-1200FF User manual

teca
teca IHP-2259XEHC Series User manual

teca
teca AHP-1200XP-1 User manual

teca
teca FHP-250 Series User manual

teca
teca AHP-250FF User manual

teca
teca FHP-750XE User manual

teca
teca AHP-1201FF User manual

teca
teca AHP-1802XP User manual

teca
teca FHP-1501 Series User manual

teca
teca AHP-1802XPHC-2 User manual

teca
teca AHP-1801XM User manual