teca AHP-1200FF User manual

Product Information Packet
Model AHP-1200XMHC
NEMA 4-X, High Shock and Vibration Heat/Cool
Solid State Air Conditioner
with 25C & 10C Temperature Control
0-3030-3-019
Thank you for your purchase. Information has been enclosed regarding the
installation, specifications, and wiring of your solid-state assembly.
Please read and follow all instructions carefully before installation. Only qualified
technicians should install this equipment.
If you have any questions regarding your equipment, please do not hesitate to
call us at 773-342-4900, and we will be happy to assist you. We are open from
8:00 am-4:30 pm Central Time.
Included in this packet you will find:
Installation Notes for Air Conditioners
Product Literature and Specifications
Assembly Drawing # 1200-B-A13
Wiring Drawing # 1200-B-E82
Installation Drawing # 1200-A-F57
Warranty Information

Important Installation Notes for Air
Seal
Ambient
Air
Path
Enclosure
Internal Air
Path
Mounting Styles:
Vertical (Side/Front/Back) Mounting:
Condensate Removal System:
Top Mounting:
Maintenance:
Cautions:
Notes on condensation:
Both ‘thru mount’ and ‘flush mount’ units can be
positioned in any orientation and on any enclosure surface. It is important
to consider interior air flow patterns when determining the mounting
location. Also of importance is an unrestricted flow of ambient air thru
the hot side heat exchanger. Ease of access and inspection must
be considered for those applications in particularly severe
environments which may require occasional maintenance.
Vertical mounting refers to the vertical direction of the cold
side or interior fins and is recommended for applications with
high humidity, poor and incomplete cabinet seals or any
condition which may cause the cold side fins to be maintained
at temperatures below the dew point for long periods of time
allowing for the formation of condensation. The vertical fin
direction provides a drip path whereupon condensation can be
collected via a moisture removal system (standard on FHP-
units) or a drip pan positioned below the cold side fins. Drip pans are
optional for thru mount units.
All FHP-Series and AHP-1400 air conditioners contain a built-in condensate removal system. The condensate kit
consists of a antifungal sponge with a condensate wick. PVC tubing is also provided for drainage. Drip pans are
optional for thru mount units which must be evaluated on an individual basis. Equations defining a relationship between
the cold side fin and enclosure temperatures are provided to assist in the evaluation.
Though often the easiest location to mount it is often the most difficult to protect from condensation in this orientation
due to the fin orientation, gravity and any susceptible components below. If a drip pan is employed by the end user use
caution to place the pan far enough away from the internal fan to minimize the restriction of air flow. The pan should
cover the fin ends as well as the fan area. When there is a choice, the vertical orientation is preferred by most
users.
Since the technology is solid-state, there are no filters, compressors, or fluorocarbons to maintain. The only moving
parts are the fans. It is recommended for harsh or dirty environments that the heat sinks be cleaned from time to
time. This can be accomplished by directing compressed air over the external fins or on NEMA 4 versions by hosing
the unit down. This will increase the overall life and performance of the system.
Take care when mounting not to damage the seal between the hot and cold side sinks. Do not attempt to mount a unit
to a warped surface or try to make the units mounting surface conform to an unflat surface. Do not pinch or damage
any leads when mounting. Do not over tighten any installation screw, use reasonable force. Always mount with any
condensate drain down. Do not compress the cold side between the hot side and any other surface. Do not obstruct
the airflow on either side. When mounting consider the natural air flows of the enclosure. Connect power only after the
installation is complete.
Condensation occurs at the cold side fins when the surface temperature goes below the dew point. To reduce or
remove condensate, consider the following:
• Regulate the Fin Temperature above the Dewpoint.
• Keep Enclosure Closed and Sealed from Outside Humidity.
• Use Desiccant (Moisture absorbing Granules.)
• Employ Condensate Removal System/Drip Pans.
If you have any questions regarding your installation, Please feel free to contact our technical department for assistance
at 773-342-4900.

FEATURES
• Compact, (only 15”L X 7.35”W X 8.17”D)
• Weighs only 21 lbs. (9.5 kg)
• Excels in high ambient temperatures
• Environmentally safe
• Dual voltage versions available
• No compressor, fluorocarbons or filters
• Virtually maintenance-free operation
• Stainless steel exterior housing
• Versions to withstand corrosive environments,
shock and vibration
• Mounts and operates in any orientation
AHP-1200 Air Conditioner
Air Cooled 120 VAC, 240 VAC Input
Thru Mount
NEMA-12, 4,4X
SPECIFICATIONS OPERATING OPERATING
PERFORMANCE VOLTAGE CURRENT WEIGHT TEMP. AMBIENT ENCLOSURE AGENCY
MODEL PART NUMBER RATING VAC AMPS. LBS.(KG) CONTROL TEMPERATURE TEMPERATURE APPROVALS
BTU/HR 50/60HZ AMBIENT °C RANGE °C
AHP-1200FF 0-3090-0-000 500-550 120 4.0 21(9.5) None -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200FF 0-3080-0-000 500-550 120 4.0 21(9.5) TC-6F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200FF 0-30F0-0-000 500-550 120 4.0 21(9.5) 85°F (30°C) -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200FF 0-3050-0-000 500-550 120 4.0 21(9.5) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200FFHC 0-3030-1-000 500-550 120 4.0 21(9.5) TC-3F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200FFHC 0-3050-1-000 500-550 120 4.0 21(9.5) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1201FF 0-3081-0-000 500-550 120/240 4.0/2.2 29(13.2) TC-6F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1201FF 0-3051-0-000 500-550 120/240 4.0/2.2 29(13.2) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1201FF 0-30F1-0-000 500-550 120/240 4.0/2.2 29(13.2) 85°F (30°C) -40/+70 -10/+60 UL1995/CSA22.2
AHP-1201FFHC 0-3031-1-000 500-550 120/240 4.0/2.2 29(13.2) TC-3F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1201FFHC 0-3051-1-000 500-550 120/240 4.0/2.2 29(13.2) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XE 0-3080-4-000 500-550 120 5.0 23(10.4) TC-6F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XE 0-3050-4-000 500-550 120 5.0 23(10.4) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XE 0-30F0-4-000 500-550 120 5.0 23(10.4) 85°F (30°C) -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XEHC 0-3030-5-000 500-550 120 5.0 23(10.4) TC-3F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XEHC 0-3050-5-000 500-550 120 5.0 23(10.4) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1202XE 0-3082-4-000 500-550 240 2.5 30(13.6) TC-6F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1202XE 0-3052-4-000 500-550 240 2.5 30(13.6) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1202XE 0-30F2-4-000 500-550 240 2.5 30(13.6) 85°F (30°C) -40/+70 -10/+60 UL1995/CSA22.2
AHP-1202XEHC 0-3032-5-000 500-550 240 2.5 30(13.6) TC-3F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1202XEHC 0-3052-5-000 500-550 240 2.5 30(13.6) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200X 0-3090-2-000 500-550 120 4.0 23(10.4) None -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200X 0-3080-2-000 500-550 120 4.0 23(10.4) TC-6F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200X 0-3050-2-000 500-550 120 4.0 23(10.4) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200X 0-30F0-2-000 500-550 120 4.0 23(10.4) 85°F (30°C) -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XHC 0-3030-3-000 500-550 120 4.0 23(10.4) TC-3F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XHC 0-3050-3-000 500-550 120 4.0 23(10.4) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XM 0-3080-2-100 500-550 120 4.0 23(10.4) TC-6F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XM 0-3050-2-100 500-550 120 4.0 23(10.4) EXT* -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XMHC 0-3030-3-001 500-550 120 4.0 23(10.4) TC-3F -40/+70 -10/+60 UL1995/CSA22.2
AHP-1200XMHC 0-3050-3-001 500-550 120 4.0 23(10.4) EXT* -40/+70 -10/+60 UL1995/CSA22.2
*Unit is set for 5-32 VDC external signal, relay(s) included
32 TECA 1-888-TECA-USA (832-2872) www.teca-usa.com
INCLUDES
• Adjustable temperature control
• Gasket and mounting hardware
• Power input line cord
N
E
M
A
12
N
E
M
A
4
N
E
M
A
4X
OPTIONS
• Other temperature settings for single set point controls
• Custom finishes
catalog 2011 working on.qxp 8/10/2011 2:27 PM Page 32

DIMENSIONS
33
www.teca-eu.com 1-888-TECA-USA (832-2872) TECA
PERFORMANCE CURVE
Equation of line: y=⌬T(°C) x=Capacity (Watts)
Ambient Temp 20°C 40°C 60°C
Enclosure Air y=.266x-39.5 y=.266x-41.0 y=.266x-42.5
Cold Sink y=.173x-39.5 y=.173x-41.0 y=.173x-42.5
MOUNTING STYLE
Thru Mount
ENVIRONMENTS SERVED
NEMA-12 IP 52
NEMA-4,4X IP 56
RATING (TRADITIONAL)
530 BTU/hr @ 0 °F ⌬T
670 BTU/hr @ +20 °F ⌬T
RATING (DIN 3168)
154 Watts L35 L35
100 Watts L35 L50
See page 10
AHP-1200
Air Conditioner - Air Cooled
*
*
Air Flow Pattern
catalog 2011 working on.qxp 6/28/2011 2:01 PM Page 33


THERMOELECTRIC COOLING AMERICA CORP.
INFORMATION DISCLOSED
HEREIN IS THE
CONFIDENTIAL PROPERTY
OF TECA CORP. RECIPIENT
SHALL NOT USE THE
INFORMATION IN ANY
UNAUTHORIZED MANNER.
DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE SPECIFIED
REV
LEVEL
SHEET
MASTER:
SCALE
DATE:
DRAWN BY:
TOLERANCES ARE:
DECIMALS ANGLE
FRACTION
+/-
+/-
.XX +/-
.XXX+/-
MATERIAL:
FINISH:
APPROVED
Date
DESCRIPTION
REV
DRAWING #

AHP-1200 SERIES
TYPICAL FIELD MOUTING
1200-A-F57
D6033
MASTER
AA
05/21/03 B
6.62 [168.15]
2.88 [73.15]
3.45 [87.68]
TYP.
3.13 [79.38]
12 X Ø0.22 [Ø5.59]
Mounting, Monture, Montage, Montaggio
Exhaust, Echappement, Abluft, Scarico
Enclosure, Armoire, Gehäuse, Armadi
Cord, Cable, Kabel, Cablo
Intake Air, Air d'entrée,
Einlaßluft, Aria di presa
Exhaust, Echappement, Abluft, Scarico
Insulation, Isolation,
Isolierstoff, Isolamento
English, Français, Deutsch, Italiano
Dimensions: Inches [Millimeters]
Gasket, Joint, Dichtung, Guarnizione
Alternate, Alternative, Alternative, Alternativa
Warning - If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
- UL 489 defines branch circuit protection of no more than 4X the rating of the supplemental protector to be used upstream. We suggest a slow reacting, 10-15 Amps circuit breaker.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Avertissement - Si le cordon d'alimentation est endommagé, il doit être remplacé par le fabricant, son agent de service ou de personne de qualification similaire afin d'éviter un danger.
- UL 489 définit la protection du circuit de pas plus de 4X la cote du protecteur supplémentaire pour être utilisé en amont. Nous suggérons une lente réaction, 10-15 disjoncteurs Amps.
- Cet appareil n'est pas destiné à être utilisé par des personnes (enfants compris) dont les capacités physiques, sensorielles ou mentales, ou le manque d'expérience et de
connaissances, à moins qu'ils aient été donnés de surveillance ou d'instructions concernant l'utilisation de l'appareil par une personne responsable de leur sécurité.
Les enfants doivent être surveillés afin de s'assurer qu'ils ne jouent pas avec l'appareil.
Achtung - Wenn das Netzkabel beschädigt ist, muss es durch den Hersteller, seinen Kundendienst oder eine ähnlich qualifizierte Person, um eine Gefahr zu vermeiden ersetzt werden.
- UL 489 definiert den Schutz der Stromzweige nicht mehr als 4X das Rating der Beschützer weiter flussaufwärts genutzt werden. Wir empfehlen eine langsame Reaktion, 10-15
Ampere-Sicherung.
- Dieses Gerät ist nicht für die Verwendung durch Personen (einschließlich Kinder) mit eingeschränkten physischen, sensorischen oder geistigen Fähigkeiten oder Mangel an Erfahrung
und Wissen, bestimmt, sofern sie eine angemessene Aufsicht oder ausführliche Anleitung zur Benutzung des Geräts durch eine verantwortliche Person für ihre Sicherheit.
Kinder sollten beaufsichtigt werden, um sicherzustellen, dass sie nicht mit dem Gerät spielen.
Attenzione - Se il cavo di alimentazione è danneggiato, esso deve essere sostituito dal produttore, dal suo agente di servizio o da un professionistaalfinedievitare rischi.
- UL 489 definisce il circuito di protezione filiale di non più di 4X il rating del protettore supplementare da utilizzare a monte. Vi suggeriamo una lenta reazione, 10-15 interruttore Amp.
- Questo apparecchio non è destinato all'uso da parte di persone (bambini compresi) con ridotte capacità fisiche, sensoriali o mentali, o mancanza di esperienza e conoscenza, a meno
che non siano sorvegliati o istruzioni per l'uso dell'apparecchio da una persona responsabile della loro sicurezza.
I bambini devono essere supervisionati per assicurarsi che non giochino con l'apparecchio.
A Added warning text box. 08/09/2011AA
B Added UL489 branch circuit protection note and added 11/07/2011AA
unqualified operator and supervision note.

Power Temperature Controllers
138 TECA 1-888-TECA-USA (832-2872) www.teca-usa.com
TC-6F SPECIFICATION
MODEL PART NOTES TEMP @ TEMP @ T1-T2 RESET RESET TEMP @ T3 OPERATING SWITCHING SWITCHING
NUMBER NUMBER T1 °C T2 °C (MAX) °C (TYP) °C°C VOLTAGE VOLTAGE CURRENT
TC-6F 6F-00A-00-000 No Relay 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On NA NA NA
TC-6F-AC 6F-03T-00-000 VAC Version 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On 85-250 VAC 24-280 VAC 10
TC-6F-DC 6F-43D-00-000 12/24 VDC 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On 3.5-32 VDC 0-100 VDC .02-20 ADC
TC-6F-DC 6F-33D-00-000 48 VDC 35 +/- 5 25 +/- 5 10 +/- 3 6.5 3 Continuous On 3.5-32 VDC 0-100 VDC .02-20 ADC
TC-3F SPECIFICATION
MODEL PART NOTES COOL HEAT RESET RESET OPERATING SWITCHING SWITCHING
NUMBER NUMBER TEMP. °C TEMP. °C (MAX) °C (TYP) °C VOLTAGE VOLTAGE CURRENT
TC-3F-AC 3F-04R-00-000 VAC Version 35 +/- 5 15 +/- 5 6.5 3 85-250 VAC 24-280 VAC 10 AMPS
TC-3F-DC 3F-44G-00-000 12/24 VDC 35 +/- 5 15 +/- 5 6.5 3 3.5-32 VDC 0-100 VDC .02 - 20 ADC
TC-3F-DC* 3F-44P-00-000 12/24 VDC 35 +/- 5 15 +/- 5 6.5 3 3.5-32 VDC 0-100 VDC .02 - 20 ADC
* H-Bridge relays included
Model TC-6F (Cool Only) thermostat is designed using two temperature power switches in conjunction
with a solid state relay. A three position switch is provided to adjust temperature settings.
Model TC-3F (Heat/Cool) thermostat incorporates the same technology as the TC-6F. It contains a
single setting each for both heating and cooling as referenced below:
TC-1C AND TC-1H POWER TEMPERATURE SWITCHES
Models TC-1C and TC-1H power temperature controllers, with their small tolerance
and reset differential, are the simplest and most cost effective way to control a
cooling or heating device (VAC or VDC) without a need for a relay. For circuits that
have higher current draw simply use them in conjunction with a solid state relay.
TC-6F COOL ONLY
TC-3F HEAT AND COOL
Part Numbers:
Mode Part Number Note
Cool TC-1C-XX switch closes on temperature rise
Heat TC-1H-XX switch closes on temperature drop
XX: Specify temperatures 20 °C, 25 °C, 30 °C, 35 °C for cool mode
and 10°C, 15 °C for heat mode
Example: TC-1C-20 and TC-1H-10
VOLTAGE CURRENT SET POINT TOLERANCE RESET DIFFERENTIAL
amps °C°C
125 VAC 2 +/- 3 3 - 6
250 VAC 1.3 +/- 3 3 - 6
12 VDC 2 +/- 3 3 - 6
24 VDC 1.3 +/- 3 3 - 6
TC-1 SPECIFICATION
Dimensions: Inches [Millimeters]
TC-7F SPECIFICATION
MODEL PART NOTES HX COOL HEAT RESET RESET OPERATING SWITCHING SWITCHING
NUMBER NUMBER TEMP. °C TEMP. °C TEMP. °C (MAX) °C (TYP) °C VOLTAGE VOLTAGE CURRENT
TC-7F-DC 7F-24G-00-000 24 VDC 20 +/- 3 35 +/- 3 10 +/- 3 6.5 3 24 VDC 24 VDC .02 - 20 ADC
* H-Bridge relays included
Model TC-7F (Heat/Cool) thermostat incorporates the same technology as the TC-6F. It contains a
single setting each for both heating and cooling and a heat exchanger mode:
TC-7F HEAT AND COOL
catalog 2011 working on.qxp 7/25/2011 11:07 AM Page 138

LIMITED WARRANTY
In the event a defect in material or workmanship is discovered in any of TECA’s
products within one year after the date they are delivered to Buyer, : (a)
TECA is notified of the defect in writing by certified mail within 14 days of the
date of discovery; (b) TECA may then either, at its sole discretion, inspect the
product at Buyer’s location, or require that the product be made available at
Buyer’s expense at TECA’s premises for TECA’s inspection within 14 days of
the date of notification; and (c ) the products are defective and the defects
result from faulty materials and/or workmanship and not in any way from
accident, misuse, misapplication, mishandling, modification, or alteration by the
Buyer or the shipper, TECA shall, at its sole option, repair or exchange
defective products free of charge to Buyer, or credit to buyer the price of the
defective products. ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, ARE
EXCLUDED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE. IN NO EVENT SHALL TECA BE LIABLE FOR ANY CLAIM BASED
UPON BREACH OF EXPRESS OR IMPLIED WARRANTY OR ANY OTHER
DAMAGES WHETHER SPECIAL, INDIRECT, INCIDENTAL,
CONSEQUENTIAL, LOST PROFITS, BUSINESS INTERRUPTION, OR LOSS
OF BUSINESS OR CUSTOMER RELATIONSHIPS.
In order to return merchandise for any reason ( repair, replacement, or credit) a
return authorization number must be issued by TECA. New merchandise may
not be returned for credit beyond 60 days from shipment. Charges for
incidental or other damages may also be made. All returned goods must be
sent freight prepaid. A restocking charge of 15% will apply. On special
equipment and custom modified equipment orders, additional incremental
cancellation charges may be made.
and if
then
RETURNED GOODS, RESTOCKING CHARGES
This manual suits for next models
42
Table of contents
Other teca Air Conditioner manuals

teca
teca AHP-1501 User manual

teca
teca AHP-270XE User manual

teca
teca AHP-1201FF User manual

teca
teca AHP-1802XPHC-2 User manual

teca
teca AHP-250FF User manual

teca
teca FHP-250 Series User manual

teca
teca IHP-2259XEHC Series User manual

teca
teca AHP-270 User manual

teca
teca AHP-1802XP User manual

teca
teca AHP-270FF User manual

teca
teca FHP-1501 Series User manual

teca
teca 0-018C-4-000 User manual

teca
teca AHP-250FFHC User manual

teca
teca AHP-1800 Series User manual

teca
teca AHP-4200 Series User manual

teca
teca HP-1200FF User manual

teca
teca AHP-1801XM User manual

teca
teca AHP-401 User manual

teca
teca FHP-750XE User manual

teca
teca AHP-1200XP User manual