ImportantInstallationNotesforAir
MountingStyles:
Vertical(Side/Front/Back)Mounting:
Compressedairsupply:
CondensateRemovalSystem:
Theonlyrecommendedmoutingorientation
forthisproductisverticalmountingwiththecompressedair
inputfittinglookingdownwardasshowninthesketch.Itis
importanttoconsiderinteriorairflowpatternswhendetermining
themountinglocation.Alsoofimportanceisanunrestrictedflow
ofambientairthruthehotsideheatexchanger.Easeofaccess
andinspectionmustbeconsideredforthoseapplicationsin
particularlysevereenvironmentswhichmayrequireoccasional
maintenance.
Verticalmountingreferstotheverticaldirectionofthecoldside
orinteriorfinsandisrecommendedforapplicationswithhigh
humidity,poorandincompletecabinetsealsoranycondition
whichmaycausethecoldsidefinstobemaintainedat
temperaturesbelowthedewpointforlongperiodsoftime
allowingfortheformationofcondensation.Theverticalfin
directionprovidesadrippathwhereuponcondensationcanbe
collectedviaamoistureremovalsystem(standardonFHP-
units)oradrippanpositionedbelowthecoldsidefins.Drip
pansareoptionalforthrumountunits.
Inorderforthisproducttofunction,sufficientamountofcompressedairmustbesuppliedthroughthe3/8NPTfitting
toVortexAirAmplifier.ToobtainmaximumperformancefromtheVortexAirAmplifier,accuratemeasurementsofair
pressure(psi)andairvolume(cfm)mustbeobtained.Linepressureof70-90psicanbepresentwithoutsufficient
volume(scfm)ofair.ToensurethatbothpressureandvolumearepresenttoefficientlyoperatetheVortexAirAmplifier,
alinesizeof1/4”pipeor1/2”hoseshouldbeusedforapplicationsupto10feetfromthemainheader.Use3/8”pipeor
3/4”hoseupto20feet.and3/4”pipeor1”hoseupto50feet.Donotusecoiledhoseastheverysmallinsidediameter
ofthehoselimitsairflow.
Airsuppliesareplaguedwithcondensedwatervaporintheairlines.Thiscondensationleadstorustanddirtinthe
airlines.Alsosomecompressorswillallowoiloroilvaportoenterthelines.SmallorificesintheVortexAirAmplifier
maybecomecloggedwiththerustdirt,andwaterdroplets.A5-micronfilterwillseparate99%oftheforeignmaterial
fromtheairsupplyallowingvirtuallymaintenancefreeoperation.Theuseofanoilfilterwillremovetheoildropletswith
aneffectivefiltrationof0.01ppmforanevencleanerairsupply.
AllFHP-SeriesandAHP-1400airconditionerscontainabuilt-incondensateremovalsystem.Thecondensatekit
consistsofaantifungalspongewithacondensatewick.PVCtubingisalsoprovidedfordrainage.Drippansare
optionalforthrumountunitswhichmustbeevaluatedonanindividualbasis.Equationsdefiningarelationshipbetween
thecoldsidefinandenclosuretemperaturesareprovidedtoassistintheevaluation.
A)
B)