5. Hysteresis - applies to both the turn-on threshold value (source) and turn-off threshold value
(receiver). The option is used to delay the controller response to temperature change when the
temperature is fluctuating around the said thresholds.
6. Sensor alarm operation - allows defining if the pump operation should be triggered by an alarm of
any of the sensors.
7. Anti-freezing - the setting allows turning the anti-freezing function on or off. Once the function is
activated the anti-freezing threshold value has to be defined i.e. the temperature below which the
anti-freezing function is to be enabled.
8. Anti-stop - the setting allows turning the anti-stop function on or off. Once the function is activated
the user needs to define the interval (in days) at which the pump will turn on.
Room controller operation
If connected in that mode the pump will operate according to the signal received from the room controller.
When selecting that pump type it needs to be defined when the pump should turn on:
- Pump operating with room controller in open state
- Pump operating with room controller in closed state
PRIORITIES
Option available only for pumps operating in the temperature mode. It is possible to set operation priorities
numbered 1 to 3 (the lower the number the higher the operation priority). It is used only if there are 2 or 3
pumps of the same type in the controller (the priority has no impact on other pumps).
Example: Setting of 1:2:2 denotes that pump1 will have priority over pump2 and pump3 which will operate
simultaneously once the turn-off threshold of pump1 has been reached.
PROGRAMMES
The option allows setting predefined pump operation programmes:
Factory settings –The controller is pre-configured for operation. However, it should be adapted to individual
needs. Factory settings can be restored at any time. Selection of “factory settings” option will result in all
user pump settings being lost and reset to settings saved by the manufacturer. Individual pumps parameters
can be set at that point again.
Central heating + domestic hot water –operation programme for two pumps. They are factory-set as
parallel pumps but it is possible to set any priority for any of the pumps. Additionally, the followings alarms
are factory-set:
- after the temperature on sensor1 has reached 85ºC the central heating pump will operate
- after the temperature on sensor2 has reached 85ºC the domestic hot water pump will be turned off.
Central heating + domestic hot water + circulation–operation programme for three pumps. They are
factory-set as parallel pumps but it is possible to set any priority for any of the pumps. Alarms are identical to
those of programme1.
Central heating + domestic hot water + floor pump –operation programme for three pumps. They are
factory-set as parallel pumps but it is possible to set any priority for any of the pumps. Alarms are identical to
those of programme1.
User’s –once that programme is selected all pumps are shut off –individual settings have to be entered.
Save user’s settings –the option allows to save user’s settings as an own programme.
Note: Loading of any programme will not affect the selected language, sensor types, operating time counters
and saved counter indication until the next activation of the anti-stop function.