Tecnocontrol CE100 User manual

EN
IST-1100.CE01.02/B
File: IST-1100 CE01 02-B_CE100-EN.DOC
CENTRAL SYSTEM
CE100
USER INSTRUCTIONS
TECNOCONTROL S.r.l.
Via Miglioli, 47 20090 SEGRATE (MI) - Tel. (+39) 02 26922890 - Fax (+39)02 2133734
http: www.tecnocontrol.it e-mail: [email protected]

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 2/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
IMPORTANT NOTE
The control panel CE100 has three selectable laguages:
Italian, English and French.
If the control panel CE100 is not already set your language, please
see on page 18 “Code Setup (Password)” and on page 20 “Setting
the language”.
Documento / Document name: IST-1100 CE01 02-B_CE100-EN.DOC
Oggetto / Subject : CE100
Rev. Data / Date Da / By Note
1 14/02/2008 UT/BD Revised Text
A 27/07/2009 UT/FG Revised Text and Diagrams
B 28/05/2012 UT/FG Revised Text

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 3/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
CONTENTS
DESCRIPTION............................................................................................................4
CENTRAL SYSTEM MONITORING ...........................................................................5
Alarms Reset.......................................................................................................................................6
Sensor Details Viewing ......................................................................................................................6
Enabling – Disabling Sensors ...........................................................................................................7
CE100 INSTALLATION ..............................................................................................8
ELECTRICAL CONNECTIONS ...........................................................................................................9
CONNECTING THE DETECTORS....................................................................................................10
GAS DETECTORS USE.....................................................................................................................11
COLLEGAMENTO DELLA ELETTROVALVOLA GAS....................................................................12
CENTRAL SYSTEM SETUP.....................................................................................13
Keyboard use and general information’s.......................................................................................13
SENSORS SETUP .............................................................................................................................13
Table 2 - Pre-configured parameters for the Relays.....................................................................15
SENSORS COPY...............................................................................................................................16
SENSORS DELETE...........................................................................................................................16
MODIFYING SENSORS SETUP........................................................................................................16
Sensor modification .........................................................................................................................16
CODE SETUP (PASSWORD)............................................................................................................18
LEVELS OF CODES AND DEFAULT CODES .................................................................................18
CODE EDIT (PASSWORD)................................................................................................................18
Backlight............................................................................................................................................19
ELECTRICAL OPERATIONS “TEST”......................................................................19
Input Test (Detectors).......................................................................................................................19
Output Test (Relays and Led)..........................................................................................................19
SETTING THE LANGUAGE ..............................................................................................................20
APPENDIX................................................................................................................20
LIST OF ANOMALY MESSAGES AND ALARMS............................................................................20
LIST OF ACOUSTIC AND OPTICAL SIGNALS ...............................................................................20
TECHNICAL CHARACTERISTICS...........................................................................21
Technical Characteristics central system Mod. CE100 ................................................................21
Technical Characteristics Expansion CE101 (*).............................................................................21
Technical Characteristics Supply Module AL100..........................................................................21
Technical Characteristics of Lead Battery charger AL101...........................................................21
Technical Characteristics of Lithium Battery charger AL102......................................................21
Technical Characteristics of Lithium Battery BA100....................................................................21
CONFIGURABLE 4÷20 mA DETECTORS TABLES................................................22
Connecting Detectors 4-20mA two-wire products up to December2008....................................22
NOTES:...............................................................................................................................................23

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 4/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
DESCRIPTION
The CE100 gas Central System is realized for DIN rail mounting and it can be connected up to six
4÷20mA remote sensors. It represents a useful instrument for monitoring and controlling areas where
there might be the presence of flammable, toxic gases or oxygen.
CE100 Central Unit: data processing module, with keyboard, backlighted graphic display
122x32 pixel, no.2 4÷20mA sensors inputs and relays outputs.
CE101 Sensors Unit: module with no.2 4÷20mA sensors inputs.(Max n. 2 modules for each
CE100)
AL100 230V/24 Power supply: module (230Vac-50Hz) with 24Vcc/15W output to powered the
CE100 and no.2 CE101.
AL101 Pb Battery Power supply:12Vcc 3Ah or 7Ah Pb Battery power supply module.
AL102 Li-Ion Battery Power supply module to be use with BA100.
BA100 Battery Li-Ion module with lithium battery 10.8Vcc 1,7Ah to maintain the system
powered on in absence of main power supply, to be use with AL102.
1 2 3 4 5 6 7 8 9 10 1112 13
1415 1617 1819 20 21 22 23 24 25
!
Tecnocontro lS rl CE100
ESC
12345678
1011 1213 1415 16 17
9123456
14 15 16 17 18
AL 100
AL101
AL102
BA 100
CE 101
12345678
1011 1213 1415 16 17
9
AL 100
AL101
AL102
BA 100
123456
14 15 16 1718
CE 101
CE100
–
Central
Unit
CE101
n.2Sensors
Imputs
AL100
230V to 24V
Power Supply
AL101
Pb Battery
Power Supply
CE101
n.2 Sensors
Imputs
Possible combinations:
CE100 The Central Unit: can autonomously works if it has an external power supply
12÷24Vdc (at least 15W). It has no.2 4÷20mA sensor inputs (S1-S2) and no.
4 outputs relays, of which no.3 alarm relays (U1-U2-U3) and no.1 Fault relay
(U4).
AL100 + CE100 Central unit powered at 230V: to the central unit add the AL100 power
supply, that connected to the 230Vca, powers the central at 24Vdc.
AL100 + CE100
+ n. 1 CE101 Combination for 4 sensors: to the central unit (that has 2 inputs) add no.1
CE101 module to have other 2 inputs for 4÷20mA sensors (S3 e S4).
AL100 power supply powers both the centrals CE100 and CE101.
AL100 + CE100
+ n. 2 CE101 Combination for 6 sensors: to the central unit (that has 2 inputs) add no.2
CE101 modules to have other 4 inputs for 4-20mA sensors (S3, S4, S5 e S6).
AL100 power supply powers both the centrals CE100 and CE101.
AL100 + CE100 +
one or two CE101
+ AL101
Combination with Lead Battery: to the previous combinations, it is possible
to add the AL101 module to power a lead battery from 12Vdc 3Ah or 7Ah. (Not
included in the supply).
AL100 + CE100 +
one or two CE101
+ AL102 + BA100
Combination with Lithium battery: in alternative to the previous one, it is
possible to use the AL102 power supply and BA100 battery to Lithium-Ion
10.8/1.7Ah (the battery module has to be installed on the left part of the AL102
module).
CE100 central unit can be connected to:
- 4÷20mA transmitters, 3 wires with “Replaceable cartridge sensor”for:
Flammable gases with catalytic sensor: type TS292K (IP65) or TS293K (explosion proof Ex-d) with
range 0÷20%LEL
Flammable gases with Pellistor sensor: type TS292P (IP65) or TS293P (Ex-d) with range
0÷100%LEL.
Toxic gases with electrochemical cell: type TS220E (IP65) or TS293E (Ex-d)
Oxygen with electrochemical cell: type TS220EO and TS293EO (Ex-d) with range 0÷25%O2.

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 5/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
-1-
1: 0000 LEL 4: 0004 ppm
2: 0006 ppm 5: 0001 LEL
3: 0000 LEL 6: - - - - - - - -
- NOTE: Obviously also our previous transmitter’s models made from December 2008 until today
can be connected to this equipment, which are 4÷20mA transmitters, 3 wires for flammable gases
type TS292K (IP65) or TS293K (Ex-d) with range 0÷20%LEL, or type TS293P (Ex-d) with range
0÷100%LEL and 4÷20mA transmitters 2 wires with electrochemical sensor for toxic gases and
Oxygen, type TS220E (IP65).(See note and diagram at Page.22)
- WARNING: inputs can be taken on also with other sensors with range in % LEL or ppm that have
a 4÷20mA signal referred to ground and working technical specifications(Range, minimum
operating voltage, current absorbed, etc….) the same of our products.
We disclaim no liability for malfunctions or failures caused by not compatible products.
The CE100 central unit has 3 Alarm relays:
Each sensor has 3 alarm levels associated to the Alarm Relays (PRE1, PRE2 and ALL). Consider that
the three relays are in common with all sensors, but it can be set different alarm values for each
single sensor.
The CE100 central unit has a Fault relay (FAULT)
- In case of Fault the sensors activate the common Fault Relay. (FAULT).
Every output relay can be configurated as follow:
- Delay ON from 0 to 4 minutes at exceeding of the alarm threshold set.
- Delay OFF from 0 to 30 minutes to the return under the threshold level set.
- Time ON from 0 to 30 minutes, this function only works, if you want to stop the alarm output after
a defined time, even if the sensor remains above the alarm threshold set. (The program does not
allow setting it, if it’s already used the “Delay OFF”). For example it can be used to activate devices
that cannot be powered for a long time or to send an impulse to a telephone dialer or any other
device.
- MEMORY The relay stays in “Alarm” even if the sensor returns under its threshold level. (The
program does not allow to set it, if it’s already used the “Time ON”). Make the RESET to reset it to
the normal conditions.
-LOGIC the relay can be set in POSitive logic with normally closed contact (NC) or in NEGative
logic with normally opened contact (NO).
CE100 central unit has an internal BUZZER:
-It emits a “Beep”, when the keys are pressed, moreover, from the Menu “Divers” (Miscellaneous), it
can be chosen to let it active in case of Alarm (ALL)
CE100 central unit has got a function that allow to disabilities sensors:
-Each sensor can be “disabled“without remove or cancel it from the program.
In this case, the sensor value will be visualized with *symbol before the sensor number, but it
cannot activate any relay. This function is useful in case of Faults, anomalies or maintenance and
sensor calibration.
Ce100 central unit is protected from “PASSWORD”
-The menu access is protected through “Code” (4 numbers Passwords). To enter to this function
it’s necessary to digit the Password.
CENTRAL SYSTEM MONITORING
When switching on the CE100, after the message shown
by side, the display will show a 60 seconds count down.
This is for stabilize the sensors and to avoid false alarms.
Then, the CE100 will show the situation of the connected
detectors. The Display shows all detectors (max 6).
(Detectors not programmed are indicated with a
dashed line). Upper on the right is indicated the
enabled code level. (See at page18 chapter
Password).
For each sensor, the display shows the measured value and also its status: FAULT< (<1mA)
PRE1, PRE2, ALL, FAULT> (over 24 mA). (See explaination in the chapter “Sensor details”).
TECNOCONTROL
CE100 SW Rev x.xx

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 6/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
MENU PRINCIPALE
Service9Menus Protected
8
Configuration6Code
(
Password
)
7
Details
2
Divers (Miscellaneus)5Disablin
g
4Enabling9
Reset1
MAIN MENU
Details2 Enablin
g
3
Reset1
Important Note:all detectors inputs are protected against wire breakings (connection between
detectors and Central System) and against short circuits. If a short circuit occurs, to avoid damages to
the central system or to the sensor, the power supply to that input, is automatically stopped (all others
continue to work properly). Simultaneously the yellow LED “FAULT” lights up and the correspondant
relay is activated (if programmed). Only after having solved the short circuit problem (to test if the
channel is no more in short circuit protection you need to mesure if there is voltage between the
terminals “+” and “-“ with a multimeter) it will be possible to restore normal operational conditions.
Alarms Reset
This procedure should be performed to reset the relay
outputs, programmed latched in normal conditions, only
when the alarm situation is finished.
From the normal screen, press key
ESC
to access to
MAIN MENU.Select “1-Reset” then press to
confirm.
(The menu selected is indicated by an arrow and by the
dark background. Keys are used for navigate
into the menus, those indicated semi-hidden can only be
activated with the code).
After the message RESET DONE, display return to the
MAIN MENU. Press
ESC
to view the normal screen.
Sensor Details Viewing
This function allows you to view all parameters of each
sensor.
From the MAIN MENU press to select 2-Details then
press to confirm. All settings details about Sensor
no. 1 will appear.
Using keys and all Details can be seen:
1st line: type of sensor, 2nd line: the name of sensor, 3rd
line: scale settled, 4th line: the sensor status, 5th line:
input current in mA. Then, you can see the values of the
alarm levels (PRE1, PRE2, ALL).
Pressing key you can see details of the other
sensors. (If a sensor is not used, it will appear a dashed line) Press
ESC
to go back to the
MAIN MENU.
NOTE: In the 4th line, after the value, shows the status of the sensor, with this significance:
FAULT < (<1 mA) ................ Sensor fault, disconnected or not powered
NORmal (up to PRE1) ......... Sensor is in its normal operating conditions.
PRE1, PRE2, ALL ............... the sensor has exceeded the set alarm levels, is always
shown the highest alarm.
FAULT> (above 24 mA)....... The sensor is measuring a gas concentration beyond all limits,
or is broken or disconnected.
Reset
Done
Details
Sensor n° 1
TS292KM
0020 LEL
0000 LEL: Normal
I = 04.0 mA
0010 LEL : PRE 1
0015 LEL : PRE 2
0020 LEL : ALL
Sensor n. 1

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 7/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
MAIN MENU
Disabling4Miscellaneus5
Enablin
g
3
MENU PRINCIPALE
Ena
b
lin
g
3
Disablin
g
4
Details
2
Disabling
Sensor n° 1
TS292KM
Disabling
Sensor n° 1
TS292KM
SENSOR DISABLED
WARNING: From the main menu to access the menu 3-Enable, Disable 4-and 5-
Miscellaneous, you must enter the CODE LEVEL 2 (See chapter "Code" on p. 18).
Enabling – Disabling Sensors
Each single sensor can be "Disabled" and then "Enabled"
without having to delete it from the program. The CE100
will continue to display it, with the symbol next the
sensor number, but it will not activate any alarm. This
function is useful in case of faults, malfunctions or
maintenance and calibration of the sensors.
From the normal screen, press
ESC
to access to MAIN
MENU.After having inserted the code level 2, with
select “3-Enbling” or “4-Disablling” then press to
confirm. Then with the same key select the number of
sensor to be Enabling or Disabling.
Pressing the key the following message will appear
Sensor enabled or Sensor disabled.
Press
ESC
to return to MAIN MENU.
SETTING FUNCTION "MISCELLANEOUS"
This function allows you to set some options.
From the MAIN MENU press select “5-Miscellaneus”
press to confirm and then with o select
the desiderate choice (highlighted line). Press to go
to the next line and in the same way you can set the
required value. Press
ESC
to return to MAIN MENU.
BUZZER:If you select YES means that in case of alarm, as
well as the red Led also the internal buzzer will activated.
If you select NO, the buzzer will never switched on.
BATTERY: Select ABSENT if you have not installed any
supply module for the backup battery.
Select AL101 if the CE100 is installed with the Module
AL101 to charge a lead acid battery (12V 7Ah max).
Select AL102, if is installed the AL102 battery charger
module and BA100 Lithium Battery Module (10.8V 1.7Ah).
NOTE: If in the row BATTERY, it was selected the AL101 or
AL102, the CE100 activates automatically, a test of one
minute every 24 hours. If the battery is low voltage or
exhaust, the yellow LED will flash to indicate the fault.
EV STATUS (electro valve) select YES if you installed a
solenoid Tecnocontrol (models from VR480 to VR400)
with the position sensor connected to the "CONTACT
SOLENOID VALVE".
Press
ESC
to return to MAIN MENU.
In case of alarm the CE100 will check if the valve has effectively closed, otherwise the yellow
LED will light on and the fault relay will activate (FAULT). The display will show the symbol
for the failure to close.
NOTE: This control acts only on the 3th alarm level, and then the valve must be
connected to relay ALL.
Miscellaneous
BUZZER : OFF
BATTERY :ABSENT
EV STATUS :NO
Miscellaneous
BUZZER :OFF
BATTERY :AL101
EV STATUS :NO
Miscellaneous
BUZZER :OFF
BATTERY :AL 102
EV STATUS :NO
Miscellaneous
BUZZER :OFF
BATTERY :AL 101
EV STATUS :YES

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 8/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
IMPORTANT REMARK INSTRUCTIONS INCLUDED INTO THE MANUAL BELOW
INCLUDE INSTALLATION AND SYSTEM SETUP PROCEDURES TO BE EXECUTED
ONLY BY QUALIFIED AND AUTHORIZED PEOPLE.
CE100 INSTALLATION
The control panel should be mounted in a suitable enclosure or cabinet to accommodate
modules on a DIN rail. For your convenience, we recommend to install the modules in the
order shown, with the power supplies on the left of CE100 and the expansions on the right.
The space occupied, depends on the configuration of CE100 (see fig. 1).
The full configuration with lithium-ion battery is 17 modules. For example, can be used an 18
modules enclosure, available from most suppliers of electrical equipment (e.g. in Fig. 2).
12345678910111213
!
Tecnocontrol Srl CE100
ESC
1234567
8910
12345
6789 10
AL100
AL101
AL102
BA100
CE101
1234567
AL100
AL101
AL102
BA100
12345
14 15 16 17 18
CE101
141516171819
20 21 2324 2526 2728
8910 11 18
225 mm
120 mm
Fig. 1
22 23 25 26 27 2820 21
4U
2U
2U
3U
3U
3
1
2
Fig.3 - polarized plug-
in terminals
Fi
g
.2
WARNINGS:
A. Do not install the modules CE100 near heat sources such as contactors, power
supplies or other.
B. Terminals (Fig. 3) are polarized plug-in (1); we recommend using appropriate
cable lugs to the conductors (2) and anchor the cables to the structure to avoid
excessive stress to the circuit and the terminals themselves. Use a screwdriver
(3) with a suitable size.
C. The wiring diagrams on the following pages, for simplicity are always shown
with all the sensors.

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 9/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
ELECTRICAL CONNECTIONS
MODULE AL100 (AC 230Vca/24Vdc-15W)
230Vac Power supply mains must be connected to terminals “L e N”. (See figure 4).
MODULE AL101 (AC 230Vca charger for Lead 12V Battery)
230Vac Power supply mains must be connected to terminals “L e N”. (See figure 4).
Battery can be used a 12V Lead battery with a capacity for the request autonomy and the
connected total load. With one 3Ah, battery life is about 2 hours (with n. 2 Sensors and Gas
Valve 12V-12W max); while with a 7Ah you have more than 3 hours life (with n. 4 or n. 6
Sensors and a Gas Valve 12V-12W max). The battery must be connected to AL101
terminals "B +" (red) and "B-" (Black) (see figure 4).
Example for calculating the hours of autonomy of an installation with 4 sensors (typically
absorb 2W each) and a 12V solenoid valve that absorbs 12W:
hours4
12W2W)x(4 7Ahx12
veelectrovaltheofWno.2Wxdetectorsgasconnectedofno. BatterytheofAhno.x12
Connecting to the CE100 the power supply should be connected to the CE100 with 3-wire
on terminals "INT, + and -" as shown in figure 4.
+ -
A
L100
12/24V
V+
V-
INT
+ - S1
+ - S2
-+ S3
+ -S5
S6
S4
A
L101
AL102 SENSOR
1 SENSOR
2 CE101 n.1
SENSOR 3-4 CE101n.2
SENSOR 5-6
Fig 4– Connection Diagram with Power Supply Module AL101
GND IN
T
GND
CENTRAL UNIT
CE100
C N
A
PRE1 C N
A
PRE2 C N
A
A
LL C N
A
FAULT
RE
L
A
YSOUTPUTS
MODULE
AL101
Pb12VBattery
Charger
L
230V
B+B- INT +
-
+
-
BATT CE100
V
ALV.
N
MODULE
AL100
230VPower
suppy
+ -
CE100
L
230V
N
+ -
CE100
B+
B-
INT
V-
BATT E+
E-
CE100
V+
VALV
24Vdc
12Vdc
If you haveinstalled the
A
L101, connect it to a
Pb
battery
12Vd
c
/
7Ah
max
230Vac
230Vac
CNA
PRE1 C N
A
PRE2 C NA
ALL C N
A
FAULT
REL
A
YSOUTPUTS
Relay PRE1
–
1st
A
larm level
Relay PRE2
–
2nd
A
larm Level
Rela
y
ALL
–
3rd
A
larm Level
Rela
y
FAULT -Fault
CENTRAL UNIT CE100
Inputs: Please see the chapter on the next page “Connecting the detectors“.
Outputs: all 4 relays have only one voltage-free changeover contact. The contact rate
(resistive) is 3A at 250Vac. All output relays contacts are indicated with "C" (common), "NO"
(normally open). This designation refers to the relay in position without power, or programmed
in negative logic. During the programming can be chosen if every single alarm relay must be
in "Negative logic" (the contact will be NO) or "Positive logic" (the contact will be NC). (See
fig. 5, fig. 7 and the NOTE on page 12).

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 10/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
MODULE AL102 (AC 230Vca charger for Li-Ion BA100 Battery)
230Vac Power supply mains must be connected to terminals “L e N”. (See figure 5).
Battery the BA100 module, which contains the lithium battery, has a cable that should be
connected to the corresponding socket.
Connecting to the CE100 the power supply should be connected to the CE100 with 3-wire
on terminals "INT, + and -" as shown in Figure 5.
+ -
A
L100
12/24V
V+
V-
INT
+ - S1
+ - S2
-+S3
+ - S5
S6
S4
A
L101
AL102 SENSOR
1 SENSOR
2 CE101 n.1
SENSOR 3-4 CE101n.2
SENSOR5-6
Fig 5– Connection diagram as in Fig.4, but with Modules AL102 and BA100
GND INT
GND
CENTRAL UNIT
CE100
C N
A
PRE1 C N
A
PRE2 C N
A
A
LL C N
A
FAULT
REL
A
YSOUTPUTS
MODULE
AL100
230Vac Power
Supply
+ -
CE100
L
230V
N
+ -
CE100
24Vdc
12Vdc
MODULE
BA100
LithiumBattery
Connect the polarizedconnector, of the BA100 module,to the
A
L102 socket.
230V
a
c230Vac
C N
A
PRE1 C N
A
PRE2 CNA
A
LL C N
A
FAULT
REL
A
YSOUTPUTS
Rela
y
PRE1
–
1
s
t
A
larm level
Rela
y
PRE2
–
2nd
A
larm level
Relay ALL
–
3rd
A
larm level
RelayFAULT -Fault
MODULE
AL102
BatteryCharger
forBA100
L
230 V
N
INT + - E
+
E-
BATT CE100
V
ALV .
B-
B+
INT V-
BATT E+
E-
CE100
V+
VALV
B-
B+
CONNECTING THE DETECTORS
CENTRAL UNIT CE100 can be connected up two detectors with 4 to 20mA output (S1 and
S2). To have other four (from S3 to S6), you need to install the Expansion Modules CE101.
CE101 MODULE (Expansion of two inputs for detectors 4 to 20mA)
Inputs by installing a CE101 module can be connected two sensors (S3 and S4). Installing
a second CE101 module can be connected other two sensors (S5 and S6).
Connecting with CE100 the first module CE101 should be connected with 4 wires, to
CE100 terminals “+, –, S3 e S4“, as shown in figure 6. If you installed the second module
CE101, is should be connected to the CE100 terminals "+, -, S5 and S6".
Connection with 3-wires 4÷20mA gas detectors
- Detectors for flammable gases with “Replaceable Cartridge Sensor”: with Catalytic sensor:
TS292K (IP65) or TS293K (Explosion-proof Ex-d) series with 0÷20%LEL range and with
Pellistor sensor: TS292P (IP65) or TS293P (Ex-d) series with 0÷100%LEL range.
- Detectors with “Replaceable Cartridge Sensor” using electrochemical cells: for toxic gases
TS220E (IP65) or TS293E (Ex-d) series and for oxygen TS220EO e TS293EO (Ex-d)
series with 0÷25%O2range.

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 11/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
The connection with 4 to 20mA three wires detectors should be performed (fig. 6) between
detector’s terminals "+", "-" and "S" and the corresponding input terminals of the CE100 and
CE101 modules.
The section of the connecting cables
between the panel and the sensors
must be adequate to the distance and
the type of sensor used, as shown in
Table.
We recommend the use of shielded cables, the screen (shield) must be connected only by
the central side and a single point of "GROUND".
+ - S +
SENSOR
A (S5)
-S
SENSOR
B (S6)
S5
+
- S
S6
+
-
S
S3
+
- S
S4
+
- S
+ - S +
SENSOR
A(S3)
- S
SENSOR
B (S4)
+ -
AL100
12/24V V+ V- INT
+ - S1
+- S2
-+ S3
+ - S5
S6
S4
AL101
AL102 SENSOR
1 SENSOR
2 CE101n.1
SENSOR 3-4 CE101 n.2
SENSOR 5-6 CE100 SENSOR
+ - SA
SB
Fig 6 – Connetction diagram with
three wires 4÷20mA detectors
S
3
+ - SA
SB
CE100 SENSOR
+
- S
S1 +
- S
S2
+
GND
S4
S5
+
GND
S6
CE100
CENTRAL UNIT
C NA
PRE1 CNA
PRE2 CNA
A
LL CNA
FAULT
USCITE RELÉ
1st
CE101
INPUTS
DETECTORS
from S3to S4
2nd
CE101
INPUTS
DETECTORS
from S5 to S6
4÷20m
A
INPUTS
+ - S
+
SE N S OR
-S
SENSOR
+ - S
+
SENSOR
-S
SE N SOR
+
-S
A
SB + - S
A
SB
GAS DETECTORS USE
WARNING Always refer to specific instructions attached to them. Please note that all
documentation attached to the products "Central Unit and Gas Detectors" must be
read and kept.
Distance Cable
from 0 up to 300 meters 3x1.5 mm2 shielded
From 300 up to 600 meters 3X2.5 mm2shielded

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 12/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
COLLEGAMENTO DELLA ELETTROVALVOLA GAS
The Manual Resetting NO or NC Solenoid Gas Valve or if required, the Automatic too with
230Vac supply, must be connected as shown in fig.7. If the valve has a 12V coil, please use
the note at the bottom of this page and the figure 8, without consider the “Solenoid Valve with
Position Sensor" not present in the "Normal" Solenoid valve.
Relé PRE2 - 2°Livellod’Allarme
Rela
y
FAULT - Fault
Relay
A
LL
–
3
rd
A
larm Level
MODULE
AL101
Pb Battery
Charger
L
230V
B+
B- INT
V
+
V-E+ E-
BATT CE 100
V
ALV
.
N
MODULE
AL100
230Vca Power
Supply
+ -
CE100
L
230VN
230Vac
CENTRAL UNIT
CE100
C N
A
PRE1 C N
A
PRE2 C N
A
A
LL C N
A
FAULT
RELAYS OUTPUTS
RelayPRE1
–
1st
A
larmLevel
230VcaSiren
(SE301A)
Fig 7– Wiring diagram with gas valve and Siren
NO or NC Manual
Resetting Valve
(
VR600÷VR65
0
)
CONNECTION OF THE SOLENOID GAS VALVE WITH POSITION SENSOR
If you have installed a Tecnocontrol solenoid valve with the position sensor (VR400 to VR480
models) connected to the "VALVE CONTACT", in the menu "MISCELLANEOUS" you must
configure YES the STATE EV (Electro Valve).
WARNING: This control works only on 3rd alarm level, so the valve must be connected to
relay ALL.
If an alarm occurs, the CE100 will check if the valve has been effectively closed, otherwise
the yellow LED will light and the FAULT relays activates. The display will show the symbol
for the failure to close.
Rela
y
FAULT -Fault
RelayPRE1
–
1
s
t
A
larm Level
Relay PRE2
–
2nd
A
larm Level
Fig 8– Wiring diagram with gas valve with position sensor and Siren
CENTRAL UNIT
CE10 0
CNA
PRE1 CNA
PRE2 C N
A
A
LL CNA
FAULT
MODULe
AL101
Pb Battery
Charger
L
230V
B+B- INT V+ V-E+ E-
BA TT CE 100
V
ALV
.
N
MODULE
AL100
230Vac Power
supply
+ -
CE1 0
0
L
230V
N
230Va
c
230Va
c
ManualResettingValve
(VR400÷VR480)
With“POSITION
SENSOR” and with
12Vdccoil.
Rela
y
A
LL
–
3rd
A
larm Level
REL
A
YSOUTPUTS
GND
12Vdc
“
V
ALVE
CONTACT”
Terminals
Terminal “
E
-
“
Te
r
minal“
E
-
“
NOTES: The AL101 and AL102 modules have an auxiliary output “VALVE“ at 12VDC/12W
max (terminals E+ and E-). You can power a gas solenoid valve or other device, operating at
12VDC (10.8÷13.8VDC), whose absorption maximum does not exceed 12W (1A). This
output is protected from "Short Circuit", but should not be connected loads that exceed the
indicated current capacity, or which may generate noise on power supply.

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 13/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
MAIN MANU
Confi
g
uration6
M Exclusio
n
4Miscellaneu
s
5
Sensor choice
Sensor n. 1
Sensor Choice
Sensor n. 1
Model : TS293Px
Sensor Choice
Sensor n. 1
Model : TS293Px
Valve : NO
CONFIRM ? NO
CENTRAL SYSTEM SETUP
Keyboard use and general information’s
The numbers to be changed or entered appear on the display highlighted by the Cursor
(flashing black rectangle). To change or enter a number you can use:
The key to move up or increase a value.
Key to move down or decries a value.
Key to confirm or to enter in the Reset Menu.
Key
ESC
to enter and exit menus.
After having entered the first sensor setup, the software propose this setup as the standard
for all others sensors, in this case, if you are entring more sensors with the same setup, all
operations will be much more easy and quick.
SENSORS SETUP
If any sensors have been already configured, the
following message will be displaied:
IMPORTANT NOTES
A - To set up the Central or make changes later, from the normal screen, press
ESC
to
enter the MAIN MENU. Select 8-Protected Menu and then enter the "Code Level 3".
(Please see on page 18 chapter CODES).
B - At the first set up, the sensor no. 1 must be programmed first. Why choosing the
type of "valve", if installed, is binding, you cannot change this set up in the other
sensors, because the choice only affects the 3rd Alarm Relay "ALL", it follows that
the gas shutoff valve should only be connected to these relays.
Pressing the
ESC
key, you enter in the MAIN MENU.
After entering the code (CODE ACCEPTED), press
ESC
to
return to MAIN MENU, then press key select “Set
up” and press to confirm. Now, press to select
the sensor number to be configured and press to
confirm.
Example:
“1-Sensor Choice”Select “1” press to confirm and
advance to the next line.
“Model”, with key selects the installed gas detector
type (e.g. TS293Px) then press . (See the following
pages to Tables 1 and 2).
"Valve" presses key to select the desired valve type,
if installed. After selecting one of the three options below,
then press to confirm.
NO = Normally Open
NC = Normally Closed
NOT = No Valve installed
"CONFIRM" will be asked to confirm the inserted set up, with the arrow select YES and
then to confirm. If you leave NO the operation will be cancel (please see chapter
"DELETION SENSORS").
1:--------- 4:----------
2:--------- 5:----------
3:--------- 6:----------
-3-

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 14/24
Table 1 - Pre-configured parameters of the detectors (sensors)
To simplify setup, the models indicated in the table are pre-configured with default settings; you can use in common situations. The detectors
into brackets has operational characteristics identical to the first highlighted in bold, the only difference is the type of protection custody. If
necessary you can also configure other detectors, selecting the "Generic" ones. In addition, you can change all parameters of each sensor
according individual requirements.
NOTE - (1): The alarms can be set for the oxygen detectors are: PRE1 and PRE2 to lack, and ALL for excess oxygen. Furthermore, the alarm
threshold PRE2 activates the 1st relay (PRE1), while the threshold PRE1 activates the 2nd relay (PRE2).
NOTE - (2): The twin TS250CB detectors must be programmed on two distinct inputs. The CO as TS220EC and gasoline vapours as TS292Kx.
MODEL GAS RANGE UNITS PRE1 (Level 1) PRE2 ( Level 2) ALL ( Level 3)
TS220EA (TS293EA) NH30-300 ppm 10 20 50
TS220EC (TS293EC) ((2
)
TS250CB) CO 0-300 ppm 50 100 200
TS220EH (TS293EH) H2S 0-100 ppm 10 20 50
TS220EN (TS293EN) NO 0-100 ppm 10 20 50
TS220ES (TS293ES) SO20-20 ppm 10 20 50
TS292KG LPG 0-20 %LEL 10 15 20
TS292KM METHANE 0-20 %LEL 10 15 20
TS292Kx (TS292KB, TS292KI)((2
)
TS250CB)INFLAMMABLE 0-20 %LEL 10 15 20
TS293KG LPG 0-20 %LEL 10 15 20
TS293KM METHANE 0-20 %LEL 10 15 20
TS293Kx (TS293KB, TS293KI) INFLAMMABLE 0-20 %LEL 10 15 20
TS292Px (TS292PM, TS292PG, TS292PI,
TS292PB) INFLAMMABLE 0-100 %LEL 10 15 20
TS293Px (TS293PX-S, TS29PX-H,
TS293PE, TS293PS) INFLAMMABLE 0-100 %LEL 10 15 20
IR101 CO2 0-2.00 % vol. 0.20 0.50 1
IR102 CO20-2.00 % vol. 0.20 0.50 1
Generic
(1
)
TS220EO (TS293EO) Oxygen (O2) 0-25.0 % vol. 18.5 19.5 22.5

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 15/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
Table 2 - Pre-configured parameters for the Relays
MODEL
Relay PRE 1
Delay ON (sec)
Delay OFF (sec)
Positive Logic
MEMORISED
Relay PRE 2
Delay ON (sec)
Delay OFF
Positive Logic
MEMORISED
Relay ALL.
Delay ON (sec)
Delay OFF (sec)
Delay OFF (sec)
Positive Logic
MEMORISED
Relay FAULT
Delay ON (sec)
MEMORISED
TS220EA
K1
1 1 NO NO
K2
1 1 NO NO
K3
30 1 1 SI YES
K4
30 YES
TS220EC 1 1 NO NO 1 1 NO NO 30 1 1 SI YES 30
YES
TS220EH 1 1 NO NO 1 1 NO NO 30 1 1 SI YES 30
YES
TS220EN 1 1 NO NO 1 1 NO NO 30 1 1 SI YES 30
YES
TS220EO 1 1 NO NO 1 1 NO NO 30 1 1 SI YES 30 YES
TS220ES 1 1 NO NO 1 1 NO NO 30 1 1 SI YES 30 YES
TS292KG 1 1 NO NO 1 1 NO
NO 30 1 1 NOTA 1 YES 30 YES
TS292KM 1 1 NO NO 1 1 NO
NO 30 1 1 NOTA 1 YES 30 YES
TS292Kx 1 1 NO NO 1 1 NO
NO 30 1 1 NOTA 1 YES 30 YES
TS293KG 1 1 NO NO 1 1 NO
NO 30 1 1 NOTA 1 YES 30 YES
TS293KM 1 1 NO NO 1 1 NO
NO 30 1 1 NOTA 1 YES 30 YES
TS293Kx 1 1 NO NO 1 1 NO
NO 30 1 1 NOTA 1 YES 30 YES
TS292Px 1 1 NO NO 1 1
NO NO 30 1 1
NOTA 1 YES 30 YES
TS293Px 1 1 NO NO 1 1
NO NO 30 1 1
NOTA 1 YES 30 YES
IR101 1 1 NO NO 1 1
NO NO 30 1 1
NOTA 1 YES 30 YES
IR102 1 1 NO NO 1 1
NO NO 30 1 1
NOTA 1 YES 30 YES
Generic 1 1 NO NO 1 1
NO NO 30 1 1
NOTA 1 YES 30 YES
NOTE 1 “YES” if we choose NC VALVE (normally closed valve) or “NO” for NO Valve (normally open valve)or NOT VALVE.
TIME ON (in seconds) for all relays K1, K2, K3 and K4 is= 0. This parameter should only be used and as indicated in "Change
Sensor" on page 17.

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 16/24
Sensor copy
Sensor n. 1 2
TS292KM
Setup
Senso
r
delete3
S
ensor choice1Sensor Cop
y
2
Sensor copy
Sensor n. 1
TS292KM
Sensor copy
Sensor n. 1 2
TS292KM
CONFIRM ? NO
SENSORS COPY
From the MAIN MENU, with key select the sub-
menu “Setup”. Press , select with “2-Sensor copy”
then press to confirm.
Sensor choice Select with the desired sensor you
wish to copy and then press to confirm.
Sensor copy to an arrow with a number reference on its
right will appear. With insert the desired sensors to
be copy and then press .to confirm.
“CONFIRM”will be asked to confirm the configuration
inserted. With select YES and press .
If you leave NO the operation will be cancel
SENSORS DELETE
From the MAIN MENU, with key select the sub-menu “Setup”. Press , select with
“3-Sensor delete” then press to confirm.
Sensor Selection: with , choose the number of sensor to be deleted, and then press
to confirm.
Confirm: will be asked to confirm the cancellation with , select YES and press to
confirm. If you leave NO, the operation will be cancelled.
NOTE: You cannot delete the sensor No.1.
MODIFYING SENSORS SETUP
It is possible to modify a sensor already configured in two ways:
1 - If you want to change the threshold values or alarm output is sufficient to operate as
described below in section Sensor Setup.
2 - If you need to change sensor model, (except No. 1 which can be reconfigured only) is
recommended before, delete it, then configure it as if new, see the previous paragraph
Sensors delete.
Sensor modification
From the MAIN MENU, with key select the sub-
menu “Setup”. Press , select with “4-Sensor
modification” then press to confirm.
Sensor Selection: with , choose the number of
sensor to be deleted, (The sensors are not configured,
are indicated with a dot line) then press to confirm.
NOTE: If you do not want to continue, press twice
ESC
to
return to the MAIN MENU.
Setup
Sensore delete
3Sensor modification4
Sensor co
py
2
Sensor modification
Sensor n. 3
Model : TS292KM

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 17/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
"PARAMETERS" parameters are proposed in succession,
to move to the next without changing it, simply press
.
“Endo of scale” (Full Scale 9999 max) you can change this
value with the keys then press to confirm.
“Unit” (LEL, %, ppm, °C) to change this value, using the
keys then press to confirm.
“Level PRE1” modify with then press .
“Level PRE2” modify with then press .
“Level ALL” modify with then press .
NOTE: The three thresholds value must have an
increasing progressive value or equal, with the
exception of the Model TS220EO or TS293EO Oxygen
(See NOTE 1 at the bottom of Table 1).
“Output PRE1” first alarm threshold.
“Delay ON”: is the delay of the relay output, in minutes and seconds (max 4’10’’), since the
alarm threshold is exceeded.
“Delay OFF”: is the time, in minutes and seconds (max 30’), during which the output (relay)
remains active, even after the end of the alarm condition.
“Time ON”: is the interval of time, in minutes and seconds (max 30'), during which the output
remains activated, from when it is exceeded the alarm threshold. At the end of this time, the
output (relay) returns to normal operation even if the value and above the alarm threshold
WARNING: "Time ON" can be set, only if the “Delay OFF” is set to "ZERO" and is not
selected "Latched output” YES.
"Positive logic" Indicates if the relay works with Normally
Closed contact (Positive), normally open or normally
(Negative). Modify this with key , to "NO" (Negative) or
"YES" (Positive), then press to confirm.
"Latched output" if you want the output remains activated,
even when the alarm returns under its threshold. Modify
this with key , to "NO" or "YES" and then press
to confirm.
WARNING: "Latched output” YES, can only be set if the Delay OFF and Delay ON time, are
set to "ZERO". Normally the "Latched output” YES" is used on the 3rd alarm
level, to prevent resetting of the solenoid gas valve (either manual or
automatic resetting) without first verifying that the Central Unit is in alarm.
Then, continue as above, also for the other items "Output PRE2" (2nd alarm threshold - Relay
PRE2), "Output ALL" (3rd alarm threshold - Relay ALL) and "Output FAULT" (indicating a failure - FAULT
relay).
CONFIRM: will be asked to confirm the changes inserted
(if you leave NO, the whole operation will be cancelled).
By key selecting YES and then press to
confirm, and then press
ESC
to return to the MAIN
MENU.
Sensor modification
Sensor n° 1
Model : TS292KM
CONFIRM ? NO
Sensore modification
Parameters
End of scale : 0020
Sensore modification
Parameters
Level PRE 1 : 0010
Sensore modification
Output PRE1
Dalay ON : 00’01’’
Sensore modification
Output PRE1
Delay OFF : 00’01’’
Sensor modification
Output PRE1
Positive Logic : NO
Sensor modification
Output PRE1
Latched Output: NO

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 18/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
CODE SETUP (PASSWORD)
The code consists of an access key that, when inserted, is to protect all the system settings
from unauthorized changes. If you want to change the Setup of inputs, outputs and the Code,
you must first enter the correct code.
From the MAIN MENU, with key select the sub-
menu “8-Protected menu”. Press to confirm.
When the message "CODE LEVEL 1" (which in this
version is not active) with the keys you can
move to the "CODE LEVEL 2" or "CODE LEVEL 3", then made
the choice you want, press to confirm.
To select the code, with the keys moves the
cursor to the request number, and with confirms the
choice. After entering the 4 digit, display will show "CODE
ACCEPTED", press
ESC
, to return to the MAIN MENU and
now you can change the settings enabled.
LEVELS OF CODES AND DEFAULT CODES
The CE100 has three levels of code, with different access so as to allow people with different
responsibilities and expertise to operate on the central unit. The three "Code Levels" are
factory preset, it is recommended to change them anyway, and keep them carefully.
Code 1 in this version, has no effect on the menu, under normal use you can go
directly to the menu 1-RESET, 2-DETAILS, 7- CODES, and 8- PROTECTED MENU.
Code 2 2222 for use by the plant manager, also gives access to the menu 3-ENABLE, 4-
DISABLE, and 5-MISCELLANEOUS
Code 3 for maintenance or installation, gives access to all menus.
CODE EDIT (PASSWORD)
From the MAIN MENU, with key select the sub-
menu “7-Code” and press to confirm.
Appear, CODE LEVEL 1 (which in this version is not
active) then the keys you can move to the
"CODE LEVEL 2" or "CODE LEVEL 3".
After you make your selection, press to confirm.
After selecting the code level to edit, enter the 4 digit
original code, with keys scroll numbers and
confirm with . (For each number entered will appear
a star for confirmation).
Then enter the New Code, scroll the numbers with keys
and confirm with .
MAIN MENU
Setu
p
7Protected menu8
Divers (Miscellaneus)6
Protected Menui
CODE LEVEL 2
Protected Menu
INSERTCODE 2
0123456789#$%&-
Code
INSERtCODE2
0123456789#$%&-
MAIN MENU
Code7Protected Menu
8
Setu
p
6
Code
CODE LEVEL 2
Code
NEW CODE 2
0123456789#$%&-

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 19/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
Code
CODE STORED
Code
CONFIRM CODE 2
0123456789#$%&-
Test output
LGreen
MENU PRINCIPALE
Protected Menu8Service9
Code
7
Service
Test Outputs2Test In
p
uts1
Lan
g
ua
g
e
3
Test Inputs
1=04.0mA 2=04.0mA
3=04.0mA 4=04.0mA
5=04.0mA 6=04.0mA
Then to confirm renter the New Code, scroll the
numbers with keys and confirm with .
Now will show STORED CODE, with
ESC
you will return to
the MAIN MENU.
From this moment, the new inserted code becomes
active.
PAY ATTENTION: we suggest writing and keeping the Password in a safety place. In
case you lose the Password get in contact with our technical support.
Backlight
The display backlight will automatically switch off, when not used, after 60 seconds; pressing
any key it light back again.
ELECTRICAL OPERATIONS “TEST”
WARNING: This procedure must be performed with extreme care by trained
and authorized personnel, because both are activated relay outputs that
activate the connected devices, both internal functions the control panel.
The CE100 is equipped with a test program that allows
verifying the electrical operation
From the MAIN MENU, after inserting the Code Level 3,
with select the submenu "9-Service" and then press
to confirm.
Input Test (Detectors)
With key select “1-Test Inputs” and then press .
Now, you will see the sensor’s values, expressed in mA,
even those not configured. Obviously does not consider
the value of those not installed, which can be "0mA" to
"50 mA". At the centre of the display there will be the
symbol of the solenoid valve with Position Sensor.
Output Test (Relays and Led)
Press key
ESC
to go back to menu “Service”, with key
select “2-Test Outputs”, then press to confirm.
From here starts the sequence of tests listed below.
Repeatedly pressing the key activates ON and OFF one after another all Led: LGreen,
LYellow, LRed, the Buzzer and the outputs relay: the PRE1, PRE2, ALL and FAULT.
Finally, will be displayed the Battery voltage, with activation of the internal test "load".
Module AL101 (lead battery) - this value should be about 12VDC
Module AL102 + BA100 (Lithium battery) this value should be about 10.5 Vdc
WARNING: Test Battery, must obviously be only used when the modules are installed
AL101 or AL102. Do not leave this test active for more than a minute. During the test is
activated, the "load" to the internal CE100, consisting of power resistors which
obviously will become hot.

IST-1100.CE01.02/B CE100 “TOWN” / User Instructions PAG. 20/24
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI) - Tel. 02.26 92 28 90 - Fax 02.21 33 734
Language
FRENCH
Language
ENGLISH
Language
ITALIANO
SETTING THE LANGUAGE
With key select "3-Language" and press to
confirm
With keys you can change the language and
pressing confirms the choice.
APPENDIX
LIST OF ANOMALY MESSAGES AND ALARMS
NO SENSORS CONFIGURED The central system is not configured.
FAULT- The input signal is less than 1 mA. The sensor could be
faulty, not connected or not powered.
UNDERFLOW The input signal is between 1 and 3,5mA. The detector could
be out of calibration on the beginning of the scale.
PRE1 The 1st alarm threshold has been exceeded and the related
output relay is active (if configured).
PRE2 The 2nd alarm threshold has been exceeded and the related
output relay is active (if configured).
AL The 3rd alarm threshold has been exceeded and the related
output relay is active (if configured).
OVERFLOW The input signal is between 21 and 24 mA. The sensor is
detecting gas, but the full scale has been exceeded.
FAULT+ The input signal is greater than 24 mA. The sensor could be
faulty, or it’s detecting gas but it has exceeded its full scale.
Mains 230Vac power supply is missing.
Battery empty.
The valve with Position sensor is not close.
Display switched off if the greed Led is ON, the Display could be damaged or the
contrast is too low, tries to regulate it with the trimmer on the
Board: (“Contrast ADJ” bottom right corner) placed in the CE100
housing, on the PCB placed into the front cover.
LIST OF ACOUSTIC AND OPTICAL SIGNALS
Intermittent Buzzer One of the detectors has exceeded the 3rd Alarm Level (ALL)
or the AUX input is active.
Green Led on Mains power supply ON (normally working condition).
Green Led Blinking The CE100 is powered by the Battery; the Mains is OFF.
Red Led on One of the sensors has exceeded the 3rd Alarm level (AL3).
Red Led Blinking One of the Detectors has exceeded the 1st Alarm and/or 2nd
Alarm levels (AL1 and/or AL2) or one of the Latched Output
relay has been activated.
Yellow Led Blinking Battery voltage is less than 10.8Vdc.
Yellow Led on One of the sensors is FAULT+ (>24mA)or FAULT- (0 mA).
Green Led and Display OFF Mains power supply OFF, and battery has powered the
central system till it got down. If the battery voltage gets
down under 10VDC, it is automatically disconnected to avoid
damages.
Table of contents
Other Tecnocontrol Control Panel manuals