manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Teknim
  6. •
  7. Smoke Alarm
  8. •
  9. Teknim TFD-1251 Instruction Manual

Teknim TFD-1251 Instruction Manual

Release Date: 04/01/2021
Rev:01
TFD-1251
INTELLIGENT ADDRESSABLE OPTICAL SMOKE DETECTOR
WITH BUILT-IN ISOLATOR
Installation & User Manual
Critical Warnings
General
✓Read this manual with care before operating the device and keep it for further reference.
✓Comply with all warnings and measures provided in the manual. Follow all respective operation and usage
instructions.
✓Keep the devices away from water and humidity.
Ortam Şartları
Do not operate the device under extreme temperature conditions that fall outside the following values.
Temperature: Between -10°C and +70°C
Relative Humidity: Max. 95% RH
Service
Do not attempt to repair the device on your own, you may be exposed to electric shock in case you open the
device housing.
Contact your dealer or authorized service in case of a failure. Technical interventions to the device must be
carried out by qualified personel of authorized service.
Failures That Require Service Intervention
Contact your authorized service or dealer in case of a failure or in following cases.
✓If the power line or plug is damaged,
✓If any liquid has leaked or a substance has fallen into the device,
✓If the device is exposed to water or rain,
✓If the device is dropped or the housing is damaged,
✓If there is significant performance change in the device,
✓If the device is not operating normally according to the operating instructions in the user manual
Call the service since erroneous operations may cause further failures.
What You Can Do On Your Own
Do not attempt to repair the device on your own since you may be exposed to electric shock in case you
open the device housing. Contact your dealer or authorized service in case of a failure. Technical
interventions to the device must be carried out by qualified personel of authorized service. The device must
be cleaned with a dry cloth. No chemical must be used for cleaning purposes.
Handling and Transportation
The device must be handled with care in manner that it does not get exposed to impacts and liquid influx.
The damages that may occur during improper handling are out of guarantee.
Human and Environment Health
This device does not contain any chemical or biological substance that may harm human health.
General Features
✓Advanced smoke detection algorithm that minimizes false alarms
✓Denial of temporary signals that may be perceived as alarm
✓Adaptive protection by continuous sampling of the present environment
✓Debris algorithm that perceives inoperability due to dirt accumulation and respective warning
✓Easy to clean smoke chamber
✓External notification light connection means
✓Two LED’s used for state indication purposes
✓15s starting time
✓Three different sensitivity settings that can be selected on the panel
✓Compatible with TFA-0120 Universal Detector Base
Technical Specifications
Power Input
18V(min) –32V(max)
Average (Quiescent) Current Consumption
80uA (@32V)
Maximum Alarm Current
3mA (@32V)
Maximum External Device Current
10mA (@32V) –(2K2 resistance limit)
Alarm Levels (appr.)
H: 0.12, M: 0.15, L: 0.18 dB/m
Operating Temperature Range
-10C ~ 55C (14F ~ 131F)
Humidity
95% RH (max.)
Size (mm)
Ø110, h42
Housing Material
White Color, ABS Plastic
Attached Cable Cross-section
0.4mm ² ~ 1.5mm ²
Weight (wit base / without base)
183 gr / 125 gr
Starting Time
15 sec
Isolator
Average Current Consumption (Normal Op.) @24V
15uA
Vmax.
32V
Vnom.
28V
Vmin.
15V
Vso_max.
18V
Vso_min.
9V
Vsc_max.
5V
Vsc_min.
0,7V
Ic_max.
0,5A
Is_max.
3A
IL_max.
0,026A
Zc_max.
0,026Ω
Warning: Do not attempt to take the card out of its plastic protection. It is sealed solely for your safety.
Users must avoid intervention.
Indicator LEDs
Blue LED
Red LED
Yellow LED
Any error situation
(Pollution etc..)
Blinks with 1 sec. intervals
X
X
The device is in normal
operation mode
(can be turned off.)
Blinks with 20 sec. intervals
X
X
Alarm state
X
Constant
X
Short circuit state
X
X
Constant
Terminals
No. 1
NEG.(-) supply input
No. 2
NEG.(-) supply output, NEG. (-) input of parallel notification light
No. 3
POS. (+) input of parallel notification light
No. 4
POS.(+) supply input, POS.(+) supply output
No. 5
Earth connection
Installation and Connection
1. Turn (1) the detector head counterclockwise to the short line and pull (2) it up to disassemble from the
base.
2. Mount the base part by using the mounting place shown (2).
3. Make the cable connections according to the following diagram. Make the connection by observing that
the polarity of Leg No. 4 is (+) and Leg No. 1 is (–), and then by connecting (-) pole from No 2 and (+)
pole from No. 4 of the current detector to No.1 of the next detector.
4. Use the connections No. 3(+) and 2(-) for the parallel notification light.
5. Install the detector head into its place. Make sure that the line on the head piece is aligned with the long
line on the base.
6. Energize the detector. The LED on the detector will blink blue light once in every 20 seconds in the state
without an alarm in order to indicate that the device is in operation. (This feature may be turned off from
the panel)
7. Make the chasis(earth) connection of the cable continuously over the Leg No. 5 between the loop output
and the last detector.
Test
Observable smoke flow must be provided in order to obtain correct results.
In order to perform a smoke test, ensure that the smoke goes into the smoke detection chamber min. for 1
minute by using a burning material or test spray. The LED lights and indicates the alarm when sufficient
amount of smoke enters into the chamber.
1. Fend of the smoke source when the device goes into the alarm state.
2. Check to see whether the red LED’s light continuously. Reset the detector from the panel.
3. The detector must be sent to the service if it does not produce alarm within 1 minute.
4. The system may be activated after the test is performed.
Warning: The product operates only with Teknim TFP-121x, TFP-122x and TFP-123x Intelligent Addressable
Fire Alarm panels.
A: Head
B: LED’s
C: Base
Loop Connection
Connector
Parallel Notification Light
(TFA-1196)
1922
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul
20
1922-CPR-1461
EN 54-7:2000; EN 54-7:2000/A1:2002; EN 54-7:2000/A2:2006
Point smoke detector (Scattered Light)
EN 54-17:2005
Fire Detection and Fire Alarm Systems –Short Circuit Isolators
TFD-1251
Technical data: See BİLGİ-TEC-170908 kept by the
manufacturer.
Manufacturer Company and Main Service
*In compliance with AEEE regulations. This product is manufactured from recyclable and reusable high
quality parts and materials. Therefore, do not dispose of the product together with domestic or other wastes
at the end of its service lifetime. Take it to a drop-off point for the recycling of electrical and electronic
devices.
*Lifetime of this product specified and announced in the list attached to the After Sales Services Regulations
published in the Official Gazette No 29029 dated 13/6/2014 is 5 years.
*The consumer may apply to the Consumer Arbitration Board or Consumer Court of the place of residance or
of the consumer transactions in case of disputes arising from exercising the rights granted by the guarantee.
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul / Turkey
PHone: +90 216 455 88 46 Facsimile: +90 216 455 99 06
www.bilgielektronik.com.tr
satis@bilgielektronik.com.tr
destek@bilgielektronik.com.tr

Other Teknim Smoke Alarm manuals

Teknim TFD-1250 Instruction Manual

Teknim

Teknim TFD-1250 Instruction Manual

Teknim TSD-5154 User manual

Teknim

Teknim TSD-5154 User manual

Teknim TSD-5124 User manual

Teknim

Teknim TSD-5124 User manual

Teknim TFD-3230 Troubleshooting guide

Teknim

Teknim TFD-3230 Troubleshooting guide

Teknim TFD-1250 Troubleshooting guide

Teknim

Teknim TFD-1250 Troubleshooting guide

Teknim TFD 1430 User manual

Teknim

Teknim TFD 1430 User manual

Teknim TFD-1270 User manual

Teknim

Teknim TFD-1270 User manual

Teknim TSD-5135 Troubleshooting guide

Teknim

Teknim TSD-5135 Troubleshooting guide

Teknim TFD-1250 Instruction Manual

Teknim

Teknim TFD-1250 Instruction Manual

Popular Smoke Alarm manuals by other brands

Cavius 2201-003 quick start guide

Cavius

Cavius 2201-003 quick start guide

Ei Electronics Ei140RC Series instruction manual

Ei Electronics

Ei Electronics Ei140RC Series instruction manual

Argus Security SG100 instruction manual

Argus Security

Argus Security SG100 instruction manual

hager TG 500A installation guide

hager

hager TG 500A installation guide

FireAngel ST-620 Thermoptek user manual

FireAngel

FireAngel ST-620 Thermoptek user manual

Securiton Genius H Mounting instructions

Securiton

Securiton Genius H Mounting instructions

Aico New 160 Series 160 Series Product guide

Aico

Aico New 160 Series 160 Series Product guide

Kidde 1276E Brochure & specs

Kidde

Kidde 1276E Brochure & specs

Mircom MIX-2351RAP Installation and maintenance instructions

Mircom

Mircom MIX-2351RAP Installation and maintenance instructions

Ei Electronics Ei 175 Ionisation product manual

Ei Electronics

Ei Electronics Ei 175 Ionisation product manual

First Alert SA710AB Product specifications

First Alert

First Alert SA710AB Product specifications

LST 7251 Specification sheet

LST

LST 7251 Specification sheet

Heritage HM-560B Installation and service instructions

Heritage

Heritage HM-560B Installation and service instructions

MasterGuard 380 Installation and owner's manual

MasterGuard

MasterGuard 380 Installation and owner's manual

pyrexx RWM MC operating manual

pyrexx

pyrexx RWM MC operating manual

SIGRIST-PHOTOMETER FireGuard 2 instruction manual

SIGRIST-PHOTOMETER

SIGRIST-PHOTOMETER FireGuard 2 instruction manual

Gamewell BD-SS quick guide

Gamewell

Gamewell BD-SS quick guide

no-flame 83198 instruction manual

no-flame

no-flame 83198 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.