Teknim TFD-1270 User manual

TFD-1270
Analogue Addressable Optical Smoke + Heat
Detector (Multisensor) Installation & Operation
Manual
Yayın Tarihi: 11/09/2017
Rev:00
Issue Date: 07/12/2017
Rev:02
Important Warnings
General
✓Before using the device read this manual carefully. Keep it just in case of necessity.
✓Abide all the rules and precautions stated in the manual. Follow all the instructions one by one.
✓Keep the devices away from water and moisture
Conditions
Do not energize the device above or below the given limits of extreme hot or cold conditions,
Temperature: Between -10°C and +70°C
Relative Humidity: %95 RH max
Service
Do not try to fix the device on your own. Removal of cover may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical
interventions have to be done by technicians of company.
Malfunctions that require technical service
In case of any malfunction or below conditions contact with your authorized service,
✓When Mains cable or the plug is harmed,
✓Contact of device with a fluid,
✓Exposure of rain and water,
✓Fell down of device or harmed outer cover,
✓Serious performance fall on the device,
✓Depending on the instructions stated in manual, if your device not working properly
Contact with your authorized service in such terms.
Maintenance on your own
Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are
allowed for cleaning
Transportation
Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions
that caused by improper transportation is not under warranty.
Human and Environmental Health
This device contains no chemical or biological elements that could harm human condition.
General Features
✓Advanced smoke detection algorithm that minimizes false alarms
✓The detector is in the A2S class and alarms at 55 ° C in this conditions
✓Rejection of transient signals that can be detected as alarms
✓Adaptive intelligent protection by constantly sampling the environment
✓Dust algorithm and warning to understand that it is getting polluted and unable to detect
✓Easy to clean smoke chamber
✓Ability to connect an remote indicator
✓Two leds used for status indicators
✓15s start time
✓Three sensitivity settings via panel
✓The logic of working on the panel and / or
✓Can only work as heat and smoke detectors only through the panel
✓Compatible with TFA-0120 Universal Detector Base
Technical Features
Power Input
18V(min) –32V(max)
Average Current Consumption
80uA (@32V)
Maximum Alarm Current
3mA (@32V)
Maximum External Device Current
10mA (@32V) –(2K2 resistance limited)
Alarm Threshold (approximate)
H: 0.12, M: 0.15, L: 0.18 dB/m
Operating Temperature Range
-10C ~ +70C (14F ~ 158F)
Humidity
95% RH (max)
Dimensions (mm)
Ø110, h42
Housing Material
White Color, ABS Plastic
Used Cable Cut
0.4mm ² ~ 1.5mm ²
Weight (incl. Base / excluding base)
183 gr / 125 gr
Start Time
15 sn
Indicator Leds
Blue Led
Red Led
Any error condition
(dust or power failure)
Blinks for 1s period
X
In normal operating condition
Blinks for 20s period
X
In alarm condition
X
It is constantly lit
Terminals
Number 1
Negative (-) supply input, Negative (-) supply output
Number 2
Negatif(-) input of the remote indicator
Number 3
Positive (+) input of remote indicator
Number 4
Positive (+) supply input, Positive (+) supply output
Number 5
Earth connection
Warning: The product only works with TFP-121x, TFP-122x and TFP-123x Analogue Addressable
Fire Alarm panels.
Warning: Do not attempt to remove the electronic board from its plastic case. The electronic board is
closed for your safety. Users should avoid from interference.
Mounting and Connection
1. Remove the head of the detector by pulling it upwards (2) by turning it (1) up to the short line in the
direction of the counterclockwise direction as seen from the base.
2. Mount the base using the 2 mounting locations shown.
3. Make the cable connection according to the following diagram. Make the connection so that the 4th leg +
the 1st leg is the pole - take the next detector from number 1 - the pole from pole 4 + pole.
4. Use the 3 (+) and 2 (-) connections for the remote indicator.
5. Replace the detector head. Make sure the line on the head matches the long line on the base
6. Give the detector energy. In the absence of an alarm, the LED on the detector indicates that it is
operating with a blue color for approximately 20 seconds. (This feature can be switched off via the panel)
7. Continuously route the earth connection of the cable from the cycle output to the last detector through
the No. 5 leg.
Test
Smoke Test:
For the smoke test, allow the smoke to enter the smoke detection chamber for at least 1 minute with a
flammable material or a test aerosol. When enough amount of smoke enters the chamber, the LED
illuminates and reports the alarm.
1. Remove the smoke source when the alarm condition is reached.
2. Check that the red LEDs are lit continuously. Reset the detector on the panel.
3. If the detector does not give an alarm within 1 minute, the detector should go to service.
4. The system can be activated after the test has been performed.
Heat Test:
For the detector test it is sufficient to provide air flow at a temperature of about 70 ° C.
1. Open the hot air flow and check the temperature.
2. Hold the hot air into the detector. The detector should give an alarm within 30 seconds.
3. Check that the red LEDs are lit continuously. Reset the detector on the panel.
4. System can be activated after test
1922
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul
17
1922-CPD-0938
EN 54-7:2000; EN 54-7:2000/A1:2002; EN 54-7:2000/A2:2006
Point type smoke detector (Ionization)
EN 54-5:2000; EN 54-5:2000/A1:2002
Point type heat detector
Class A2S
TFD-1270
Technical data: see BİLGİ-TEC-171128-1 held by the manufacturer.
Manufacture
* 2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper recycling, return this product to your local supplier upon
the purchase of equivalent new equipment, or dispose of it at designated collection points. For more
information see: www.recyclethis.info.
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul / Türkiye
Telephone: +90 216 455 88 46 Fax: +90 216 455 99 06
Sales: sa[email protected]
Technical Support: [email protected]

Other Teknim Smoke Alarm manuals

Teknim TSD-5135 Troubleshooting guide

Teknim

Teknim TSD-5135 Troubleshooting guide

Teknim TSD-5154 User manual

Teknim

Teknim TSD-5154 User manual

Teknim TSD-5124 User manual

Teknim

Teknim TSD-5124 User manual

Teknim TFD 1430 User manual

Teknim

Teknim TFD 1430 User manual

Teknim TFD-1250 Instruction Manual

Teknim

Teknim TFD-1250 Instruction Manual

Teknim TFD-1250 Instruction Manual

Teknim

Teknim TFD-1250 Instruction Manual

Teknim TFD-1250 Troubleshooting guide

Teknim

Teknim TFD-1250 Troubleshooting guide

Teknim TFD-1251 Instruction Manual

Teknim

Teknim TFD-1251 Instruction Manual

Teknim TFD-3230 Troubleshooting guide

Teknim

Teknim TFD-3230 Troubleshooting guide

Popular Smoke Alarm manuals by other brands

Matelec FSA-30000 user manual

Matelec

Matelec FSA-30000 user manual

AJAX FireProtect quick start guide

AJAX

AJAX FireProtect quick start guide

nest S2001BW user guide

nest

nest S2001BW user guide

Chuango SMK-500 user manual

Chuango

Chuango SMK-500 user manual

Securiton ASD 535 Application guidelines

Securiton

Securiton ASD 535 Application guidelines

Det-Tronics X9800 instructions

Det-Tronics

Det-Tronics X9800 instructions

Gira 0869 00/04 Instructions for installation

Gira

Gira 0869 00/04 Instructions for installation

First Alert SA3210 user manual

First Alert

First Alert SA3210 user manual

INIM Electronics V200 quick start guide

INIM Electronics

INIM Electronics V200 quick start guide

Honeywell compact asd installation instructions

Honeywell

Honeywell compact asd installation instructions

Mircom FX-3500 Installation and operation manual

Mircom

Mircom FX-3500 Installation and operation manual

Clymac zm2 Operating and maintenance instructions

Clymac

Clymac zm2 Operating and maintenance instructions

ELRO FC400211 instruction manual

ELRO

ELRO FC400211 instruction manual

First Alert SC7010B user manual

First Alert

First Alert SC7010B user manual

WOOX R7049 quick start guide

WOOX

WOOX R7049 quick start guide

Ei Electronics Easichange Series user manual

Ei Electronics

Ei Electronics Easichange Series user manual

AROHA SM11R4 manual

AROHA

AROHA SM11R4 manual

System Sensor B224BI Installation and maintenance instructions

System Sensor

System Sensor B224BI Installation and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.