1 Introduction
Telefire’s TDM-500i Intelligent Dialer is intended for use in fire-, security- and safety
detection systems to automatically dial and play pre-recorded voice messages on alarm
and trouble events to emergency services and key personnel.
The TDM-500i is available in the following configurations:
•TDM-500i – the standard version that uses 24Vdc input
•TDM-500i/12 – an optional version that uses 12Vdc input
The TDM-500i has the following features:
1. Programming phone numbers and recording messages integral to the dialer, without
additional tools.
2. Programming of separate phone lists and messages for two distinct and separate
events.
3. Programming up to 10 phone numbers for each event (optionally up to 32 numbers)
4. Up to 15-digit phone numbers
5. Digital display of phone numbers and control codes whilst programming and during
normal operations
6. Bypass relay to allow connection to non-dedicated phone line
7. Pulse or tone (DTMF) dialing
8. Phone line monitoring, including reporting to the fire alarm control panel
9. Monitoring of the control panel’s control lines
10. Optional RS-232 interface
11. Password protection for programming and recording
12. Programmable delay for dialing through in-house telephone switchboards
13. Selectable triggering: either change-level or pulse (input pulse latching)
14. Adding, editing, displaying, and deletion of phone numbers
15. Recording and automatic playback of multiple messages:
•Message triggered by event A, consisting of two linked segments, the first
describes the event (segment A, up to 10 seconds), and the second, location
and telephone number (segment C, common to both ,messages, up to 20s)
•Message triggered by event B, consisting of two linked segments, the first
describes the event (segment B, up to 10 seconds), and the second, location
and telephone number (segment C, common to both ,messages, up to 20s)
•Or a common messages for both events (up to 40 seconds) – available from
version 2.01.05
16. Optional printing of the dialing list and dialer configuration (requires tool P/N
GSRS-232)
17. Failure indication and programmable Open Collector (CNT) output
18. Buzzer Silence for telephone line errors – available from version 2.01.05
19. Selection of positive or negative level activation for A or B inputs – available from
version 2.01.05
!
Warning
Connect to the Open Collector only equipment that draws less than
150mA.

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 2 of 10 –
2 Compatibility (all equipment except control panels)
2.1 Control Panels
The TDM-500i is compatible with the following control panels:
•ADR-3000 analog addressable control panel
•All TSA-1000 models
•TSA-1000X
•TSA-200 and TSA-200X
•All GSA-1000 models
•GSA-2B
3 Installation
The TDM-500i dialer can be installed either in close proximity to the control panel or at a
distance, as the control lines are monitored.
The dialer’s enclosure includes wire openings. Do not drill holes in the enclosure.
3.1 Cabling
Connect the telephone company’s (TelCo) line directly to the dialer’s L
INE
connection.
Connect the telephone for regular use to the T
EL
connection.
Connect the dialer to a battery-backed power source from the control panel.
Connect the dialer to the control panel as per the diagrams on page 7 onwards.
!
Warning
Connect the dialer to proper ground – see page 7 onwards.
Improper grounding may cause improper operation of the dialer under
certain conditions.
4 Programming
Programmed data is retained in non-volatile memory even without a power source.
i
Note
Do not disconnect power after programming before exiting programming state
with the Exit key.
When error messages are displayed, press the Prog key for several seconds in order to
enter programming mode.
4.1 Dialer Configuration
Press Prog – the display will show “_.”. Key in the password (default 9241). The
display will change to P. Key in 1and the display will change to d.
Press Display Programming Range Factory
Default
1 _ Dialing method
0 – Pulse
1 – DTMF
0 / 1 1
2 _ Dialing Cycles 1 – 9 4

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 3 of 10 –
Press Display Programming Range Factory
Default
3 _ Delay in Seconds –
delay while dialing through
switchboards
1 – 9 1
4 _ Message Repeats 1 – 9 4
5 _ Event latching
0 – unlatched
1 – latched
0 / 1 0
6
The display will
show the current
programming
and C.
Key in Enter to
confirm and the
display will
change to _
Select level activation
polarity (version 2.05.01 and
above)
00 – A negative; B negative
01 – A negative; B positive
10 – A positive; B negative
11 – A positive; B positive
00 – 11 01
7 _ Outgoing messages
0 – multiple A, B, C
1 – single message
(version 2.05.01 and above)
0 / 1 1
9 _ See output control table
below
* C. Restore to factory default.
Press E
NTER
to confirm.
The dialer will show E10 (no
recorded messages) as
confirmation
i
Note
Configure the dialer (option 6) to 01 when connecting to ADR-3000,
GSA-1000 or GSA-2B
Configure the dialer (option 6) to 11 when connecting to TSA-1000 or
TSA-1000X
Configure the dialer (option 6) to 10 when connecting to TSA-200, or
TSA-200XT or TSA-200X

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 4 of 10 –
Press
Display
Output Programming
Output
Factory
Default
Voltage
between
CNT and
+24V
Voltage
between
CNT and
+12V
9 The display
will show the
current
programming
and C.
Key in Enter
to confirm and
the display will
change to _
00 – output not used
10 – DC present
11 – DC present
20 – TelCo line connected
20 – TelCo line disconnected
21 – TelCo line connected
21 – TelCo line disconnected
80 – No fault present
80 – Any fault present
81 – No fault present
81 – Any fault present
24 V
0 V
24 V
0 V
0 V
24 V
24 V
0 V
0 V
24 V
12 V
0 V
12 V
0 V
0 V
12 V
12 V
0 V
0 V
12 V
00
4.2 Configuring Dialing List
Press Prog – the display will show “_.”. Key in the password (default 9241). The
display will change to P.
Key in 2and the display will change to L.
Key in 1for dialing list A or 2for dialing list B.
Press Display Programming
1
L
Add a phone numbers and press Enter.
2 _ Edit a number (see “Editing Dialing List” below)
0 F Display available space
# Display sequence number in dialing list + programmed
phone number + available space (see “Displaying Dialing
List” below)
* C. Erase dialing list. Press Enter to confirm.
Key in the switchboard’s access number, #, and the phone number to delay dialing
through a switchboard.
4.2.1 Editing Dialing List
Enter the sequence number in the list and the new number.
Let’s assume, for example, that two numbers were programmed. The first is
03 921 1955, and the second 03 921 1111. Replacing the second number
(03 921 1111) with a new number (say, 03 921 1816) will be done thus:
Select dialing list A or B (see “Configuring Dialing List”, above) and enter 2to edit
(display will show _). Key in 02 to select the second number (display will show L). Enter
the new number and press Enter to confirm.
4.2.2 Displaying Dialing List
Display of the phone number’s sequence, the programmed phone number, ending with
available space.
As an example, let’s say that two numbers were programmed into the dialing list. The
first is 03 921 1955, and the second 03 921 1816.

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 5 of 10 –
Displaying the dialing list will cause the following number sequence:
01 039211955 02 039211816 F08
Sequence Phone number Sequence Phone number Available space
4.3 Printing Dialing List and Configuration
Press Prog – the display will show “_.”. Key in the password (default 9241). The
display will change to P.
Key in 2. The display will change to L. Pressing #will print the dialing lists and
configuration on a serial printer connected via an RS-232 adapter (GSRS-232).
4.4 Message Types
4.4.1 Single Message (factory default)
A single 40 second message that is activated by either event A or B
4.4.2 Multiple Messages
See option 7 on page 3.
When configured to multiple messages, the system has three messages as follows:
•Message A – describes the event that triggers by input A
•Message B – describes the event that triggers by input B
•Message C – describes the site’s address + phone number for confirmation.
Event A will cause the playing of message A followed by the playing of message C.
Event B will cause the playing of message B followed by the playing of message C.
It is also possible to record a single 40-second message (see option 7 in the dialer
configuration menu on page 3). This message will be played by either input A or input B.
4.5 Recording, Playing, or Deletion of Messages
Press Prog – the display will show “_.”. Key in the password (default 9241). The
display will change to P. Key in 3and the display will change to
ח
.
A single message is up to 40 seconds. Messages A and B are up to 10 seconds each.
Message C is up to 20 seconds.
To stop recording before the full time press the “Exit / Stop Rec” key.
During recording the lines in the bottom of the 7-segment will flash. During playback the
lines in the top of the 7-segment will flash.

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 6 of 10 –
Press Display Program
1
1
C. Press Enter and record Message A
2
1
C. Press Enter and record Message B
3
1
C. Press Enter and record Message C
4
1
Play back message A.
5
1
Play back message B
6
1
Play back message C
7
1
Play back messages A and C
8
1
Play back messages B and C
9 Play single message
0 C. Press Enter and record single message
* C. Press Enter – display shall show
E
. Press
1
to erase message
A,
2
to erase message B,
3
to erase message C. To erase all
messages or a single message press
#
.
The dialer plays the messages immediately after recording. To listen to the messages
connect a loudspeaker to the SP connector.
4.6 Changing Password
Press Prog – the display will show “_.”. Key in the password (default 9241). The
display will change to P. Key in 4and the display will change to U.
Press Display Program
1 _. Enter new password. Display will change to C. Confirm
by pressing Enter
4.7 Error Messages
Error messages are displayed by flashing the following digits in the display:
Description Resolution
E01 Checksum error Enter programming mode and quit it
by pressing the Exit key
E02 Data mismatch Restore factory default and
reprogram
E03 Empty or damaged dialing list Program at least one number to one
of the dialing lists
E10 •Missing Message
•Three messages are recorded
and dialer configuration was
changed to a single message
or vice versa
Record messages A, B, C, or single
outgoing message according to dialer
configuration
1
This option is valid only if configured to multiple messages.

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 7 of 10 –
Description Resolution
LE Line Error Connect TelCo line or report line
error to your local telephone
company.
4.8 TelCo Line Error – Buzzer Silencing
The telephone line is supervised. When there is no connection the TDM-500i will beep
as an indication that there is a line failure. Press the Exit key for a few seconds to
silence the buzzer.
5 Connection Diagrams
5.1 Connecting a TDM-500i to an ADR-3000

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 8 of 10 –
5.2 Connecting a TDM-500i to a TSA-1000 / TSA-1000X
5.3 Connecting a TDM-500i to a TSA-200 / TSA-200XT / TSA-200X

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 9 of 10 –
5.4 Connecting a TDM-500i to a GSA-1000
5.5 Connecting a TDM-500i to a GSA-2B

TDM-500i
© 2006 –2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 July 2012
– Page 10 of 10 –
5.6 Connecting a TDM-500i or a TDM-500i/12 to a Generic Control
Panel
6 Specification
Dimensions (W / H / D) ................................................. 167 / 125 / 33 mm
Weight .......................................................................... 600 gr.
Operating Temperature Range ..................................... -10°C – +60°C (14°F – 140°F)
Relative Humidity Range .............................................. 10% – 93% non-condensing
Operating Voltage (nominal):
TDM-500i:.............................................................. 24Vdc
TDM-500i/12: ......................................................... 12Vdc
Current Consumption:................................................... 20mA (Standby)
40mA (Dialing)
All values are nominal. Specifications are subject to change without prior notice
7 Certification
Telefire's TDM-500i Conventional Intelligent Dialer has the following approvals:
•Israeli Communication Authority 7-10205-0-100760
•Approved by the Israeli Standards Institute
Table of contents
Popular Control System manuals by other brands

Hans Grohe
Hans Grohe Pontos Base Usage instructions / installation manual

Skov
Skov DOL 34H Technical user guide

Norac
Norac UC4.5 installation manual

FDC
FDC Orion-M Guide

David Clark
David Clark u3800 Installation & operation instructions

Deep Sea Electronics Plc
Deep Sea Electronics Plc 5520 Operator's manual