P.28 - Selecting mode of steps insertion.
Standard mode - Normal operation with free selection of the steps
Linear mode - the steps are connected in progression from left towards right only following the step number and according to
the LIFO (Last In First Out) logic. The controller will not connect a step when the system steps are of different ratings and by
connecting the next step, the set-point value would be exceeded.
P.29 - Setpoint used when the system is generating active power to the supplier (with negative active power / power factor ).
P.30 - Disconnection sensitivity. Same as the previous parameter but related to disconnection. If set to OFF the disconnection has the
same reaction time of connection set with the previous parameter.
P.31 - If set to ON, when switching from AUT mode to MAN mode, steps are disconnected in sequence.
P.32 –Trip threshold for the capacitors overload protection (alarm A08), that will arise after a integral delay time, inversely proportional
to the value of the overload.
Note: You can use this protection only if the capacitors are not equipped with filtering devices such as inductors or similar.
P.33 - Threshold beyond which the integral delay for tripping of the overload alarm is zeroed, causing the immediate intervention of the
A08
alarm.
P.34 –P.35 –Data of VTs eventually used in the wiring diagrams.
P.36 –Unit of measure for temperature.
P.37 –P.38 - Start and stop temperature for the cooling fan of the panel, expressed in the unit set by P.36. The cooling fan is started
when the temperature is >= to P.37 and it is stopped when it is < than P.38.
P.39 - Threshold for generation of alarm
A08 Panel temperature too high
.
P.40 - Percentage threshold of the residual power of the steps, compared with the original power programmed in general menu. Below
this threshold the alarm
A10 step failure
is generated.
P.41 - Maximum voltage alarm threshold, referred to the rated voltage set with P.07, beyond which the alarm
A06 Voltage too high
is
generated.
P.42 - Undervoltage alarm threshold, referred to the rated voltage set with P.07, below which the alarm
A05 voltage too low
is
generated.
P.43 - Maximum plant voltage THD alarm threshold, beyond which the alarm
A10 THDV too high
is generated.
P.44 –Maximum plant current THD alarm threshold beyond which the alarm
A05 voltage too low
is generated.
P.45 –Maintenace interval in hours. When it is elapsed, the alarm
A12 maintenance interval
will be generated. The hour count
increments as long as the device is powered.
P.46 –Function of the semi-circular bar-graph.
Kvar ins/tot: The bar graph represents the amount of kvar actually inserted, with reference to the total reactive power installed
in the panel.
Curr act/nom: Percentage of actual plant current with reference to the maximum current of the CT.
Delta kvar: bar graph with central zero. It represts the positive/negative delta-kvar needed to reach the setpoint, compared to
the total kvar installed.
P.47 –Default measure shown on the secondary display. Setting the parameter to ROT, the different measures will be shown with a
sequential rotation.
P.48 –If set to ON, the display backlight flashes in presence of one or more active alarms.
P.49 –Serial (node) address of the communication protocol.
P.50 –Communication port transmission speed.
P.51 –Data format. 7 bit settings can only be used for ASCII protocol.
P.52 –Stop bit number.
P.53 –Select communication protocol.