Thomas&Betts TR User manual

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 1
FOR YOUR SAFETY
The use and storage of gasoline or other
flammable vapors and liquids in open
containersinthevicinityofthisapplianceis
hazardous.
WARNING: Gas-fired appliances are not
designedforuseinhazardousatmospherescontaining
flammable vapors or combustible dust, in
atmospheres containing chlorinated or halogenated
hydrocarbons, or in applications with airborne
silicone substances. See Hazard Levels, Page 2.
GENERAL
Installation should be done by a qualified agency in accordance with the in-
structionsinthismanualandincompliancewithallcodesandrequirementsof
authorities having jurisdiction. The instructions in this manual apply to the
heater models shown below.
Model Characteristics
TR Indoor, Gas-Fired,
Low-Intensity
Infrared Tubular
System, 0-2000 ft
(0-610M) elevation
TR-H Indoor, Gas-Fired,
Low-Intensity Infrared
Tubular System,
for 2001-8000 ft
(611-2438M) elevation
Table of Contents
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don't touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
APPLIESTO: INFRA-REZ®Heater ModelsTR/TR-H
Gas-FiredTubular,
Radiant, Low-Intensity
Infrared Heater
INSTALLATIONFORMRZ-NA-I-TR
Obsoletes Form 456 (Version B)
WARNING: Improper installation, adjust-
ment,alteration,service, ormaintenancecan
cause property damage, injury or death.
Read the installation, operation, and
maintenanceinstructionsthoroughlybefore
installingorservicingthisequipment.
Paragraph No. Page Paragraph No. Page
GENERAL................................................................................................. 1
HEATER INSTALLATION............................................................... 1-21
1A. Installation Codes............................................................................... 2
1B. Warranty .............................................................................................. 2
2. Description/General .............................................................................. 2
3. Specifications ........................................................................................ 3
4. Clearances to Combustibles ................................................................. 3
5. Location and Mounting Height .......................................................3-4
6. Uncrating/Packaging ............................................................................ 4
7. High Altitude Operation ....................................................................... 5
8. Suspension Dimensions and Preparation ........................................... 5
9. Prepare and Install Burner/Control Box and
Combustion Chamber Tube .........................................................6-8
10. Install the Heat Exchanger Tube(s), Tail Pipe
Tube, and Turbulator Strip ....................................................... 8-11
11. Install Reflectors (including Standard Reflectors, Optional
Side Shield, and Optional Reflector Gap and End Covers) ..... 12
12. Venting ........................................................................................ 13-17
13. Combustion Air ................................................................................ 17
14. Gas Piping and Pressures .......................................................... 17-19
15. Electrical Supply and Connections.......................................... 19-20
16. Check Installation and Start-Up ..................................................... 21
OPTIONAL EQUIPMENT - Field Installed ................................ 22-23
17. Optional Heat Exchanger Tubes ("U", "L", 5-ft) ......................... 22
18. Hanger Kit, Option CK11............................................................... 22
19. Turnbuckle Kit, Options CK12-18................................................ 22
20. Combustion Air Inlet Kit, Option DE2 ......................................... 23
21. Dual Vent Kit, Option CC5 ............................................................. 23
22. Optional Side Shield, Options CD13-20....................................... 23
23. Optional Reflector Gap and End and Gap Covers ...................... 23
24. Multiple Heater Control, Options CL31 and 32 .......................... 23
25. Optional Unit-Mounted Thermostat Bracket Kit,
Option CM3 ................................................................................... 23
Index......................................................................................................... 24
REFERENCES: Operation/Maintenance/Service Manual, Form RZ-NA-O-TR
Suspension Dimensions and Configuration Drawings Booklet, Form RZ-NA 607
Replacement Parts Manual, Form RZ-NAP-VR/TRP/TR
®

Form RZ-NA-I-TR, Page 2
HAZARDINTENSITYLEVELS
1. DANGER: Failure to comply will result in severe personal injury or death and/or property damage.
2. WARNING: Failure to comply could result in severe personal injury or death and/or property dam-
age.
3. CAUTION: Failure to comply could result in minor personal injury and/or property damage.
1A. Installation Codes
These units must be installed in accordance with local building codes.
In the absence of local codes, in the United States, the unit must be
installedinaccordance with the NationalFuelGasCodeANSIZ223.1a
(latest edition).ACanadian installation must be in accordance with the
CAN/CGA B149.1 and B149.2 Installation Code for Gas Burning
Appliances and Equipment. These codes are available from CSA In-
formation Services, 1-800-463-6727. Local authorities having juris-
diction should be consulted before installation is made to verify local
codes and installation procedure requirements.
All electrical wiring must be in accordance with the National Electric
CodeANSI/NFPA NO. 70 (latest edition) or, in Canada, the Canadian
Electrical Code, part I-C.S.A. Standard C22.1.
The installing contractor must be familiar with all of the various re-
quirements and is responsible for installing this heater in compliance
with the applicable codes.
Special Installations --
AircraftHangars: In the United States, the heaters must be installed
in accordance withANSI NFPA 409 (latest edition), Chapter 5. NFPA
Publications are available from the National Fire ProtectionAssocia-
tion, Batterymarch Park, Quincy, MA 02269. In Canada, installation
in an aircraft hangar must comply with CAN/CGA-B149.2, Section
4.21. BothANSI NFPA 409 and the CAN/CGA-B149.2 specify that
the heater shall not be located in an area of an aircraft hangar where it
may be subjected to physical damage by aircraft, cranes, moveable
scaffolding, or other objects.
NFPA 409 specifies a clearance of 10 feet to the bottom of the heater
from the highest surface of the wings or engine enclosures of the
highestaircraftwhichmay be housed inthehangar.CAN/CGAB149.2
specifiesthataninfrared heater installed in anaircrafthangarbe at least
10 ft (3m) above either the highest fuel storage compartment or the
highest engine enclosure of the highest aircraft which may occupy the
hangar. NFPA 409 and CAN/CGA B149.2 specify a minimum clear-
ance of eight feet from the floor to the heater in other sections, such as
offices, or shops, that communicate with the aircraft hangar.
Public Garages: In the United States, heaters installed in public ga-
ragesmustbeinaccordance with National Fire ProtectionAssociation
(NFPA) 88B (latest edition), Section 3-2.3. Overhead heaters must be
located not less than eight feet above the floor and installed in accor-
dance with the conditions of their approval. NFPA 88B requires the
following warning:
WARNING:Minimumclearancemarkedonthe
heatermustbemaintainedfromvehiclesparked
under the heater.
In Canada, in a garage, the minimum clearance from the bottom of an
infraredheaterto the upper surface ofthehighestvehiclewhich may be
housed therein shall be 50 percent greater than the certified clearance,
and in no case less than eight feet (2.4m).
WARNING:These tubularradiant heaters DO
NOTqualifyfor explosion-proofinstallations.
WARNING: The installing contractor must be
certain that the area where the heater is being
installeddoesnotcontaincorrosiveortoxicfumes
orthatelementsin the atmosphere donotproduce
corrosiveortoxicfumes in the presenceofanopen
flame.
The chlorine atmosphere in enclosed swimming
poolareasmaycauseburner and tube corrosion if
the area is not ventilated.ASHRAE design guides
suggest a minimum of 5-6 air changes per hour.
The manufacturer recommends outside
combustionair.Toprovide outsidecombustion air,
Option DE2, Combustion Air Inlet Kit, must be
used.
1B.Warranty
Refertolimited warranty informationonthewarranty sheet in the"Owner's
Envelope".
2. Description/General
These radiant tubular heaters are low-intensity infrared heaters using a
power burner that fires into a 4" diameter steel tube, either 20, 30, 40, 50,
60, or 70 feet in length. The power burner is equipped with a blower for
supplyingcombustionairandaspark-to-pilot-to-mainburnerignitionsys-
tem. The highly emissive tubes are in 10-foot sections, and each section
has a polished reflector. The tube section attached to the burner is the
combustion chamber and all other sections are heat exchanger tubes with
the exhaust end heat exchanger tube being identified as the tail pipe. Op-
tional "L"-shaped, "U"-shaped, and 5-foot heat exchanger tubes are avail-
able to change the heater configuration to adapt to various applications.
Standardmodelheatersare designed to operate at fullinputratesof50,000,
75,000, 100,000, 125,000, 150,000, 175,000, or 200,000 BTUH at alti-
tudesfrom0to2000ftelevation.Highaltitudemodelheatersaredesigned
tooperateatfullinputratesof50,000,75,000,100,000,125,000,150,000,
175,000,or200,000BTUHat altitudes from 2001 to 6000 ft elevation and
from 6001 to 8000 ft at full input rates from 50,000 to 175,000 BTUH.
Venting may be either vertical or horizontal. A vent cap must be used.
Install a vent cap supplied as Option CC1 or a fully-comparable, field-
suppliedventterminalcap such as aType L BreidertAir-x-hauster®. (Type
L Air-x-hauster®is a trademark of The G. C. Breidert Company.) Dual
venting of two units is permissible when using an Optional Dual Vent Kit
(Option CC5). These heaters are also approved for operation without
outdoor venting.
Combustion air can either come from the heated space or be piped from
outside. Outside combustion air should be supplied (1) if the building
atmospherehasnegativepressure;(2)ifthe building atmosphere is dirty or
dusty; (3) if the building atmosphere contains substances that will cause
toxicgaswhencombinedwithflameorflue products; or (4) if the heater is
being installed in a tightly closed room that does not provide required air
for combustion. Installation of an Optional Combustion Air Inlet Kit is
required to provide outside combustion air.
3. Specifications

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 3
BTUH/Length/Configurations
Depending on the length and size of the heater, the heat exchanger
sections may be installed in various configurations. Optional "L"-
4. Clearances to Combustibles
Required clearances depend on the size of the heater (BTUH input), the position of the reflector, and the addition of an optional side shield on the rear
side of the heater. Refer to illustrations in Figure 1 to define clearances.
BTUHInput MinimumLength MaximumLength
50,000 20 feet 30 feet
75,000 20 feet 40 feet
100,000 30 feet 50 feet
125,000 40 feet 50 feet
150,000 50 feet 60 feet
175,000 50 feet 70 feet
200,000 50 feet 70 feet
BTUH Gas SupplyPressure
Input Type Minimum Maximum
50,000 - 150,000 Natural 4.5" w.c. 14" w.c.
175,000 - 200,000 Natural 6" w.c. 14" w.c.
50,000 - 150,000 Propane 11" w.c. 14" w.c.
Voltage/Phase Standard 115/1; Optional
208/1, 230/1, 460/1
Frequency 60 Hertz
Maximum Amps 3.0
Flame Safety Electronic
Pilot Burner Ignition Spark
Main Burner Ignition Pilot
shaped, 5-foot, and "U"-shaped heat exchanger tubes are available
to adapt the heaters to these configurations (Option UC2 for "L";
Option UB3 for "U"; Option UA1 for 5-foot heat exchanger tube).
Refer to the Suspension Dimensions and Configuration Drawings
Booklet (in the Owner's Envelope) to determine the permissible
configurations for each size and length of heater and guidelines for
using the 5-ft heat exchanger tube.
GasType and Supply Gas Pressure
Sizes 50-150 heaters are available for use with either natural or
Clearancetocombustiblesisdefinedastheminimum distance from
the heater to a surface or object that is necessary to ensure that a
surface temperature of 90°F above the surrounding ambient tem-
perature is not exceeded.
The clearances listed in the tables are installation requirements. In
addition,ANSI Z-223-1, Section 6.18, requires that signs be posted
specifyingthemaximum permissible stacking heights to assure that
the required clearances from the heater to combustibles are main-
tained in areas where items are stored under the heater.
Refer to Paragraph 1, Special Installations, for specific clearance
requirements for heaters installed in aircraft hangars and public ga-
rages.
5. Location and Mounting Height
When selecting the installation location, major factors to consider are (1)
Personal and Property Safety, (2) Personal Comfort, and (3) Heating Effi-
ciency
(1) Safety
The location must meet the Installation Codes listed in Paragraph 1 and any
local codes. These heaters are approved for indoor commercial/industrial
installations only. Do not install these tubular radiant heaters in areas that
containcorrosive or toxic fumes or where elements in the atmosphere could
produce corrosive or toxic fumes in the presence of an open flame. These
heaters do not qualify for explosion-proof installations.
propane gas. Sizes 175-200 are available for use with natural gas only.The
supply pressure listed is the gas pressure required at the gas valve inlet.
Measure gas pressure with a manometer.
Electrical Characteristics
Top of Reflector
Front
of
Reflector
Below the Reflector
or Below the Tube Optional
Side
Shield
Rear
of
Reflector
Front
of
Reflector
Top of Reflector
Rear
of
Reflector
Below the Tube
HORIZONTAL REFLECTOR REFLECTOR AN LED (1° TO 45°)
Burner
End
Heat
Exchanger
Bend
Exhaust End
HORIZONTAL CLEARANCES
Figure 1 - Clearance Orientation
Clearances to Combustibles
Horizontal Clearances
Below
Top*
Burner
End
Heat
Exchanger
Bend (U or L)
Exhaust
End
Vent
inches 66 12 24 36 24 6
mm 1676 305 610 914 610 152
inches 78 12 30 48 24 6
mm 1981 305 762 1219 610 152
inches 84 12 30 48 24 6
mm 2134 305 762 1219 610 152
With Reflector Positioned
BTUH
Input 0-30o31-45o0-30owith
Side Shield
**
(000)
Front
Rear
Front Rear Front
Rear
inches 30 30 48 18 36 12
mm 762 762 1219 457 914 305
inches 42 42 66 32 42 12
mm 1067 1067 1676 813 1067 305
inches 54 54 78 36 54 12
mm 1372 1372 1981 914 1372 305
** Refer to Paragraph 10 for side shield installation.
125/
150
175/
200
BTUH
Input
(000)
* If the heater is not vented to the outside of the building, the
top clearance to combustibles is 18" (457mm).
50/75/
100
125/
150
175/
200
50/75/
100

Form RZ-NA-I-TR, Page 4
Tube Cartons - Tubes are also packaged so that a minimum number of
cartons will cover all lengths of heater systems. This package identifica-
tion system applies to all heaters, whether shipped from distributor stock
or shipped to order from the factory. Before beginning installation,verify
thatthe packages at the job site match the length ofheater being installed.
Packaging Scheme for Tubes
Pkg P/N Contents
120294 Combustion ChamberTube; Tail Pipe with Turbulator
120295 Combustion ChamberTube; Heat Exchanger Tube;
Tail Pipe with Turbulator
120296 Heat Exchanger Tube; Heat ExchangerTube with
Turbulator
Tube Packages (left) Required by Length of System
Length Qty Pkg Qty Pkg
20 ft system requires 1 P/N 120294
30 ft system requires 1 P/N 120295
40 ft system requires 1 P/N 120294 1P/N 120296
50 ft system requires 1 P/N 120295 1P/N 120296
60 ft system requires 1 P/N 120294 2P/N 120296
70 ft system requires 1 P/N 120295 2P/N 120296
Reflectors, reflector brackets, and hardware packages are included in
heatingapplications. Referto therecommendedminimummountingheights
below. Use the mounting height, the size ofthe heater, the heater configu-
ration,andtheapplicationconditionstodeterminethemostefficientloca-
tion of the heater.
6. Uncrating/Packaging
Check for shipping damage. If any damage is found,document the dam-
age with the shipping agency and immediately contact your Reznor
Dsitributor.
Because of their modular design, these heaters are packaged in sections
and require field assembly. The burner/control box is in one carton, and
the tubes are packaged in one, two or three cartons depending on the
length of the system.
Burner/ControlBox Carton - For the convenience of both the stocking
and the non-stocking distributor, the burner/control boxes have two dif-
ferent packaging methods. Readcarefullytodeterminewhetherornot
the burner/control box requires field conversion before being in-
stalled.
(1) Burner/Control Box Packages
Package Contents
TR50 Factory-assembled Size 50,000 BTUH heater
TR75/100 Factory-assembled Size 75,000 BTUH heater
Conversion kit to change to a Size 100,000 BTUH heater
TR125/150 Factory-assembled Size 125,000 BTUH heater
Conversion kit to change to a Size 150,000 BTUH heater
TR175/200 Factory-assembled Size 175,000 BTUH heater
Conversion kit to change to a Size 200,000 BTUH heater
(2)Burner/ControlBoxFactoryBuiltto a Specific Size - If the burner/
controlboxcartondoesnot have a label about field conversion, the carton
contains a burner/control box factory-built to a specific size. Check the
rating plate to verify size and type of gas.
5. Location and Mounting
Height (cont'd)
Clearancetocombustiblesmustbeobserved(SeeParagraph 4), includ-
ing clearances to stock that might be periodically stacked underneath
theheater.
The supporting structure must have a load-carrying capacity of at least
200 lbs.
Do not locate the heater above or too close to electric lines, gas pipes,
emergency sprinkler systems, or any such structures that could be
adversely affected by radiant or convection heat.
Donotlocatethe heater where it could be damaged byhighlifts,cranes,
or any other such equipment.
Since chain suspension is required to allow for expansion and contrac-
tionof the tubes, proper positioning near large door openings is impor-
tant.Iftheheater is being installed near alargedoor(ex:garage, loading
dock,aircrafthangar,etc.),position the heater so that it willnot"swing"
inthe wind. Lateral movement of the tubular system should be limited.
(2) Comfort
Because of the unique heat transfer features of an infrared heater, the
comfort quality of the heat is greatly affected by the location of the
heater. Rays of heat are emitted from the surface of the tubes and
directedbythereflectors.Whenradiantheatraysreachasurface,those
rays are absorbed, raising the temperature of that "object". Since infra-
red heat does not heat the air, a comfort advantage is that stratification
does not occur. When the rays are not obstructed from reaching the
floor, the floor and lower level areas maintain a more comfortable
temperature than with convection (warm air) heating equipment.
For optimum comfort when infrared heaters are being used to "heat"
personnel (spot heating), it is recommended that (1) the rays of heat be
directed toward the person(s) from an angle rather than from directly
overhead, and (2) the heater(s) be arranged so that rays are directed
against at least two sides (or front and back) of the person(s). If the
heater must be hung directly overhead, a higher mounting height will
increasethecomfortlevelbecause the greater distance will decrease the
intensity level of the rays. Another significant factor when locating
the heater in relation to people is that the heat emitted from the
burner/combustionchamber end of the tubularinfrared heater is
moreintense than the heat emitted from the exhaustend. For this
reason, a U-tube configuration is often best suited for overhead
spot heat applications.
Tubular radiant heaters are engineered to provide comfort-level per-
sonal spot and space heating, but each application should be designed
individuallyto determine the best, quality-comfort locations.
(3)Efficiency
Because of the unique features of radiant heat transfer, selecting the
most efficient location for infrared equipment depends on the "floor"
coverage of the emitted heat rays. Floor coverage distance can be fig-
uredasapproximatelytwotimes the mounting height of the unit. How-
ever,comfort levelheating depends on the infrared intensity, and inten-
sity levels decrease with higher mounting heights and greater floor
coverage. For more accurate measurement, consult the manufacturer's
flux density tables.
Forspaceheatinginfrared applications, the location of theunitsmustbe
evaluatedaspartoftheheatersizeselection.DeterminethetotalBTU's
required, the floor coverage required, and the mounting height. From
thisinformation design a heater size and location plan that will provide
the most complete floor coverage without excessive overlapping. In
mostcases,perimeterheatersshouldbe located parallel to the wall. The
distance from the wall is determined by whether the reflectors will be
angled or horizontal.
For spot heating applications, the tubular system should be located to
direct the rays toward the area requiring heat. Depending on the instal-
lation,thiscan be done from directly overhead or reflector angled from
the side. U-tube configurations are often best suited to overhead spot
RecommendedMinimum Mounting Height
Reflector Size (000BTUH Input)
Position 50 75 100 125 150 175 200
feet 11 12 13 15 16 17 18
M3.4 3.7 4.0 4.6 4.9 5.2 5.5
feet 9 101113141516
M2.7 3.0 3.4 4.0 4.3 4.6 4.9
feet 8 9 10 11 13 14 15
M2.4 2.7 3.0 3.4 4.0 4.3 4.6
Horizontal
30° Angle
45° Angle

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 5
each carton. (NOTE: Chain for hanging is not included. Use either an Optional Hanger Kit and/or Turnbuckle Kit or field-supplied hardware. See
suspension requirements in Paragraph 7.)
Accessory Cartons --All field-installed options are shipped in separate cartons.
7. High Altitude Operation
All factory-built Model TR-H units are designed to operate at full input rates at elevations from 2001 to 6000 ft (611-1830M). In addition, Model TR-
H in Sizes 50 to 175 will operate at full rate at elevations from 2001 to 8000 ft (611-2440M).
High altitude kits are available to convert Size 50, 75, 100, 175, and 200 sea level burner/control boxes for use at high altitudes. Kits are available for
all sizes to convert from one high altitude level to another.
If the heater being installed requires high altitude conversion, contact your distributor to obtain the appropriate kit and complete the conversion as part
of the burner/control box preparation in Paragraph 9.
8. Suspension Dimensions and Preparation
Refer to the Suspension Point Dimensions and Installation Con-
figuration Drawings Booklet. This booklet provides suspension
point dimensions, illustrations of permissible configurations for
eachsizeand length of heater,andrequirementsthatmust be met to
include an optional 5-ft heat exchanger tube in the system.
Fromthedimensionsontheselectedconfiguration drawing, deter-
mine the building suspension points.
WARNING: Install heaters only in the
configurations illustrated or noted in the
configuration booklet (Form RZ 607 in the
Owner's Envelope). Don't install a heater in
aconfigurationthatisnotpermissibleforthat
BTUH input capacity or length. See
Paragraph 3 and Hazard Levels on page 2.
Suspension Point Requirements:
1) Supporting structure must have a minimum load-carrying ca-
pacity of 200 lbs. (Do not suspend the heater from gas piping
orelectricalconduit.)
2) Clearances to combustibles must be observed. See Paragraph
4.
3) Heatermustbesuspended by hanging chains.Chain,"S"hooks,
and/or turnbuckle length at each suspension point must be a
minimum of 12 inches. All chains suspending tubes must be
plumb. See Figure 2 for dimensions for burner/control box
suspension points.
4) Refer to Paragraph 5 for recommended minimum mounting
heights.Theinstalleris responsible for properly andadequately
fastening the chains to the building and supporting the weight of
the heater. Depending on the type of building construction at the
installationsite,eitherattach the chain support directlytothebuild-
ing or attach and extend a support to the location needed.
SUPERSTRUT®brackets or a comparable metal strut material is
well suited as a support structure that requires numerous suspen-
sion points.
Chainmustaccepta1/4""S"hookandhaveaminimumof200
lbs working load rating. Use either optional hanging chain kit
(Option CK11) or field-supplied chain.
Since the heater must be level, turnbuckles are recommended at the "S"
hook connections on the heater. Turnbuckles must be of steel or malleable
iron. Use either optional turnbuckle kits (Options CK12-20) or field-sup-
pliedequivalent.
Aminimumlengthof12"ofchain,"S"hooksand/orturnbuckleisrequired
at each suspension point.
Chains suspending tubes must be plumb when the heater is installed.
Suspension points required for the burner/control box are illustrated in
Figure 2.
Thistubular radiant heater
must be suspended with
chainbecausethetubes will
expand when heated. The
overall length of a straight
system will expand ap-
proximately as shown in
thetable.
Straight System Expansion Length
70 ft 2-3/4" (70mm)
60 ft 2-3/8" (60mm)
50 ft 2-1/8" (54mm)
40 ft 1-7/8" (48mm)
30 ft 1-1/2" (38mm)
20 ft 1-1/8" (29mm)
High Altitude Conversion Kits (full rate operation)
Gas feet meters 50 75 100 125* 150* 175 200
2001-4000 610-1219 U.S. or Canada** 126440 120880 120882 132664 132667 132670 132673
4001-6000 1220-1828 U.S. Only 126442 120884 120886 132682 132685 132688 132691
6001-8000 1829-2438 U.S. Only 126444 120888 120890 132700 132703 132706 N/A
2001-4000 610-1219 U.S. or Canada** 126441 120881 120883 132676 132679 N/A N/A
4001-6000 1220-1828 U.S. Only 126443 120885 120887 132694 132697 N/A N/A
6001-8000 1829-2438 U.S. Only 126445 120889 120891 132712 132715 N/A N/A
**Canadian high altitude installations must choose kits designed for 2001-4000 ft (610-1219M) elevation.
TR/TR-H
*Kits for Sizes 125 and 150 may only be used to change a Model TR-H from one high altitude elevation to another.
DO NOT attempt to field convert asea level ModelTR125 or TR150 to high altitude.
Natural
Gas
Only
Propane
Gas
Only
TR/TR-H TR-H only
Structural support added by the
installer or part of the building structure
A + A/4
A
At least 12
(305mm) of
chain MUST
BE used for
proper expansion
movement.
Optional turnbuckle
Use for convenience
if space permits.
Figure2-Suspension
DimensionsandHanging
Arrangementof the
Burner/Control Box

Form RZ-NA-I-TR, Page 6
9. Prepare and Install Burner/Control Box and Combustion Chamber
Tube Figure3A - CombustionAirInletSideof
Burner/Control Box
Figure 3B - Remove factory-installed air restrictor plate
and replace with the restrictor plate in the parts bag
Figure 4 - Burner/Control Box Showing Location of
theBurnerOrifice
BurnerOrifice
--Remove with
9/16" open end
wrench
Model Size is stamped
in the upper left hand corner
Combustion Air
Restrictor Plate
10-32 Nuts
Rubber tubing (attaches to
combustion airflow sensor)
Combustion Airflow Sensor
There are very important steps that must be followed to prepare, sus-
pend, and assemble these tubular radiant heaters. Preparing the heater,
suspension, and field assembly are the responsibility of the installer.
Follow all instructions carefully.
STEP 1) Prepare Burner/Control Box
All burner/control boxes require some field preparation. The type of
preparation depends on how the unit was ordered and where it will be
installed.Determine which of these six situations matches your applica-
tion and follow the appropriate instructions. The first three are for units
ordered by specific size; the last three are for burner/control box pack-
ages that cover two sizes. (Refer to Paragraph 6 for further explanation
on packaging.)
•Theunitwasorderedas a specific size to be installed at a specific
elevation (sea level or high altitude) and is being installed at
thatelevation. Proceed to STEP 2 of these Preparation instructions.
•Theunit was ordered asa specific size tobe installed atsea level
to 2000 ft and is being installed above 2000 ft (NOTE: Does not
apply to Sizes 125 and 150). Install the high altitude kit selected in
Paragraph7. Follow the instructions provided with the kit. When the
kit is installed, proceed to STEP 2 of these Preparation Instructions.
•The unit was ordered as a specific size to be installed at an
elevationabove2000ftand is being installed at a different eleva-
tionabove2000 ft. Install the high altitude kit selected in Paragraph
7. Follow the instructions provided with the kit. When the kit is
installed, proceed to STEP 2 of these Preparation Instructions.
•The burner/control box was ordered as a TR75/100, TR125/
150, or TR175/200 and will be installed at sea level to 2000 ft as
a Size 75, 125, or 175. Proceed to STEP 2 of these Preparation
instructions. (The Size Conversion Kit shipped with the burner/con-
trol box will not be used.)
•The burner/control box was ordered as a TR75/100 or TR175/
200andwillbeinstalled above 2000 ft elevation asaSize75,100,
175, or 200. Install the high altitude kit selected in Paragraph 7.
Follow the instructions provided with the kit. When the kit is in-
stalled, proceed to STEP 2 of these Preparation Instructions. (The
Size Conversion Kit shipped with the burner/control box will not be
used.)
•The burner/control box was ordered as a TR75/100, TR125/
150, or TR 175/200 and will be installed at sea level to 2000 ft
elevation as a Size 100, 150, or 200. Follow the instructions below
toinstall the size conversion kit shipped with the burner/control box.
Instructions to Change the Combustion Air Restrictor Plate and
Burner Orifice to Field Convert a Burner/Control Box from Size
75,000 to 100,000; or from Size 125,000 to 150,000; or from Size
175,000 to 200,000.
PartsRequired: Conversion package in the burner/control box includ-
ing a burner orifice, a combustion air restrictor plate, and conversion
labels.
1. Conversion Size Labels (one on the restrictor plate, one or two
loose) -- Fill-in all labels stating that the burner/control box has been
converted to either a Size 100,000, 150,000 or 200,000.
2. ChangeAir Restrictor Plate -- Refer to Figure 3A and identify the
combustion air inlet on the side of the burner box. Locate the paper
warninglabelonthefactory-installedcombustion air restrictor plate.
Attached to the restrictor plate is a combustion air sensor tube and
bracket. See Figure 3B.
Remove the hardware (screws and/or nuts) holding the combustion
air sensor bracket and the restrictor plate. Remove and discard the
factory-installedcombustionairrestrictor plate. Using the same hard-
ware, attach the combustion air restrictor plate shipped in the parts
bag. Re-attach the combustion air flow sensor bracket.
3. Change Burner Orifice - Open the hinged access panel on the
bottom of the burner/control box. Locate the burner orifice. See Fig-
ure 4. Using a 9/16" open-end wrench, remove and discard the fac-
tory-installed burner orifice. Install the burner orifice shipped in the
parts bag. Close the bottom panel.
Combustion Air Restrictor Plate
Warning label which
must be removed
Static Pressure Port
Combustion Airflow Sensor
Tubing to Pressure Switch
IMPORTANT

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 7
Instructions:
1. Refer to Figure 6 and identify the combustion air inlet side of the
burner box. If paper warning label is attached, remove.
2. Position the combustion air inlet cover over the air inlet opening.
Usingthe four screws in the parts bag, attach the coverto the burner/
control box. See Figure 7.
Figure7-AttachCombustionAirInlet Cover(Field-
attachment of the combustion air inlet cover is
required with either an indoor or outdoor combustion
airsupply.)
Figure 6 - CombustionAir Inlet Side of the Burner/
Control Box
Figure 5 - CombustionAir Inlet Cover
4. Adhere label(s) to the burner/control box directly below the rating
plate.
Field size conversion is complete. Continue to STEP 2) Install Com-
bustion Air Inlet Cover.
STEP2--InstallCombustionAir Inlet Cover-- Applies to allburner/
control boxes.
Fromthehardwarebagintheburner/controlbox,removetheinstruction
sheet and the parts listed in Figure 5.
STEP 3 -- Assemble and Suspend the Burner/Control Box and
Combustion Chamber Tube
Use these parts (from the hardware bag) to assemble the box and tube.
Qty Description P/N
4 Lockwashers 1333
4 Nuts 1035
1 Gasket 116029
Instructions:
1. Identify the Combustion Chamber Tube -- The tube with the
square flange welded to one end.
2. Attach Combustion Chamber Tube to Burner/Control Box --
Slidethegasketovertheboltsontheburnerendoftheburner/control
box(SeeFigure8B).Positionthe tube so that the hangers (on the end
of the tube) are toward the top and bottom. See Figure 8A.
Slide the flange over the bolts. See Figure 8B.
Use the washers and nuts to attach the combustion chamber flange
securely to the burner/control box. (The bolts are pre-welded to the
inside of the box.)
3. Suspend the Combustion Chamber Tube/Burner Box Assem-
bly
Parts needed from the hardware bag: 3 "S" Hooks
Attachthetwo"S"hookstothehangerbrackets on the burner/control
box. Attach the third to the top hanger bracket on the end of the
combustionchambertube. Suspend theassemblyfromthe three hang-
ing chains. Refer to Figure 9.
The illustration in Figure 9 includes turnbuckles. Turnbuckles are
Figure 8A - End
ofCombustion
ChamberTube
Showing
Position of
Hanger
Brackets
Position hanger
bracketsat the top
andbottom
Burner/Control Box
Fiberglass
Gasket
Combustion
Chamber
Lockwashers
5/16-16 Nuts (tighten alternately)
Figure8B-Attachthe Combustion
ChamberTubetotheBurner/Control
Box.Alternatelytighten nuts.
Attach"S" Hook
Attach
"S"
Hook
Attach
"S"
Hook
Figure 9 -
SuspendedBurner/
Control Box with
attached
Combustion
ChamberTube
Combustion Air Restrictor Plate
Warning label which
must be removed
Static Pressure Port
Combustion Airflow Sensor
Tubing to Pressure Switch
IMPORTANT
Qty Description
1 CombustionAir
Inlet Cover
4 Screws, #10 x
1/2" long

Form RZ-NA-I-TR, Page 8
10. Install the Heat ExchangerTube(s),Tail PipeTube, andTurbulator
Strip
Thereare very important steps that must be followed to suspendand assemble these tubular radiant heaters. Preparing the heater, suspension, andfiled
assembly are the responsibility of the installer. Follow all instructions carefully. Throughout the instructions, continued reference to the installation
configuration drawing is required.
1) Identify the Heat Exchanger and Tail Pipe Tubes and the Parts Packaged with them (Refer to the illustrations in Figures 10A-10E and
the configuration drawing in the configuration booklet):
Connect each tube as it is suspended. If your configuration requires a
turbulatorstripbeforea"U"or"L"tube,inserttheturbulatorstripbefore
the "U" or "L" tube is connected. Follow the instructions in Step No. 3)
onpages9-11,andinstalltwosectionsofturbulatorstrip.(Thiswillonly
2) Suspend and Connect the Heat Exchanger Tubes and Tail Pipe
-- Follow the Configuration Drawing Layout
A parts bag is supplied with each
heater tube and tail pipe. The bag
contains hardware needed to
connect two tubes, an "S" hook,
and an instruction sheet.
Figure 10C -
Connection
Hardware Parts Bag,
P/N 116017
Figure 10D - One Section of the
Field-InstalledTurbulatorStrip
Figure 10E -
Reflector,
Reflector
Retainer, and
Reflector
Bracketand
Hardware(U-
boltand nuts)
Reflector
Retainer
Bracket
One 10' reflector and two reflector retainers and two brackets with hardware per 10' straight tube.
Optional 5' heat exchanger tube includes a 5' reflector and two sets of retainers and brackets with hardware.
Follow installation instructions in Paragraph 11.
Figure 10A - Heat Exchanger
Tubes (Straight,"U",and "L")
"U"
Tube
"U"and "L" tube packages include
field-assembledreflectors
Expanded
End
Two Hanger
Brackets
10' Straight Tube
5' Straight Tube
Figure 10B - Tail Pipe Tube (10')
Expanded
End
SwedgedEnd withOne
Hanger Bracket
"L"Tube
Clamping
Rings
Lock
Washers
Square
Nuts
Bolts
9. Install Burner/Control Box and Combustion ChamberTube (cont'd)
3. Suspend the Combustion Chamber Tube/Burner Box Assembly (cont'd)
recommended for use in leveling the heater. If turnbuckles are included in heater suspension, use only optional turnbuckles or field-supplied
turnbuckles of steel or malleable iron.
4. DrawBolts -- There are two 4-1/2" long bolts left in the hardware bag. These bolts are provided as an aid in connecting tubes. Keep the bolts and
follow the tube connection instructions in Paragraph 10.
occur when installing a 40' to 70' system in a configuration where a "U"
or "L" tube connects directly to the tail pipe.)
Suspending Straight (5-ft or 10-ft) Heat Exchanger Tubes and
"U" Tubes - Attach an "S" hook to the hanger bracket and suspend the
tubefromthenexthangingchain.Slidetheexpandedendovertheprevi-
ous tube and make the connection.

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 9
Clamping
Rings
Lock
Washers
Square
Nuts
Bolts
1) Connection Hardware
3) Step 2
Combustion
productsflow
direction
SuspendedTube
Section
Tube Sectionto be
added(suspend at
oppositeend)
2) Step 1 4) Connected Tubes
Tighten
bolts
securely.
IMPORTANT: If tubes do not slide together easily,follow
Installation Tip below.
Installing"L"Heat ExchangerTubes-"L"tubes do not require a suspension point.When the configurationrequiresan"L"tube, slide the expanded
end over the previous tube and make the connection.
Suspending the Tail Pipe -Attach an "S" hook to the hanger bracket and suspend the tube from the last hanging chain. Slide the expanded end over
the previous tube and make the connection.
Connecting the Tubes - Using the hardware in the bag packaged with each tube, follow the steps in Figure 11 to connect the tubes.
Be certain inner tube mates to
bottomofexpansion in outer tube.
Figure 11 - Steps for Connecting Tubes
InstallationTip: If tubes are difficult to slide tubes together, use the two 4-1/2" long bolts from the burner/control box
parts bag to draw the tubes together. Follow illustrated Step 2 (Figure 11, page 9), using the 4-1/2" bolts.Alternate
tightening the upper and lower bolts. When the tubes are in position, remove one of the long bolts, replace with a
connectingbolt,and secure. Repeat, replacing the other bolt. Re-use the 4-1/2" bolts as needed.
Figure 12B - Interlock Sections asTurbulator Strip is
Installed
Figure 12A -Turbulator Strip Section
3) Install the Turbulator Strip -- Locate turbulator strip sections. Instructions: Install a turbulator strip in a tube only after
that tube has been suspended and connected to the previous
tube. Refer to Figures 12A and 12B. Install the turbulator
strip by sliding a section into the tube, connecting the next
section,and slidingtheconnected sectionsonintothe tube(s).
Followtheselectedconfigurationdrawingintheconfigura-
tion booklet and the instructions in the chart on page 11.
Slide Together Turbulators
Turbulators interlocked ready
for insertion into heat exchanger
tubes.
System Length 20 30 40 50 60 70
Tube Package(s) E F E G F G E G G F G G
Full Size Turbulator
Section, 37-1/8" long 333232322322
Small Turbulator
Section, 26" long 101000100000

Form RZ-NA-I-TR, Page 10
10. Installing the System (cont'd)
Configuration
Qty Size** Qty Size**
3 37-1/8" 3 37-1/8"
50 1 26" 1 26"
75 3 37-1/8" 3 37-1/8"
1 26"
50 3 37-1/8" 3 37-1/8"
75
50 3 37-1/8" 3 37-1/8"
75 0 - 8000 ft* All
100
75 3 37-1/8" 3 37-1/8"
100 5 37-1/8" 5 37-1/8"
1 26"
5 37-1/8" 5 37-1/8" 2 long sections before
"U" or "L" is connected Into end of straight
tube before "U" or "L"
1 26" 3 long sections after tail
pipe is connected Into exhaust end of tail
pipe
5 37-1/8" 5 37-1/8"
1 26"
5 37-1/8" 5 37-1/8" 2 long sections before
"U" or "L" is connected Into end of straight
tube before "U" or "L"
1 26" 3 long sections after tail
pipe is connected Into exhaust end of tail
pipe
5 37-1/8" 5 37-1/8"
2 sections before "U" Into end of straight
5 37-1/8" 5 37-1/8" or "L" is connected before "U" or "L"
3 sections after tail pipe
is connected Into exhaust end of tail
pipe
175 2001-8000 ft* All 5 37-1/8" 3 37-1/8" 3 sections after tail pipe
200 2001-6000 ft* is connected
150 0 - 8000 ft* Straight heat exchanger tube adjacent
to the tail pipe (See Figure 12C) 5 37-1/8" 5 37-1/8" All 5 sections after tail
pipe is connected Into exhaust end of tail
pipe
5 37-1/8" 5 37-1/8" 2 sections before "U"
or "L" is connected Into end of straight
tube before "U" or "L"
3 sections after tail pipe
is connected Into exhaust end of tail
pipe
175 2001-8000 ft* All 5 37-1/8" 3 37-1/8" 3 sections after tail pipe
200 2001-6000 ft* is connected
Straight heat exchanger tube adjacent
to the tail pipe (See Figure 12C) 7 37-1/8" 5 37-1/8" 5 sections after tail pipe
is connected Into exhaust end of tail
pipe
60 7 37-1/8" 5 37-1/8" 2 sections before "U" Into end of straight
ft or "L" is connected before "U" or "L"
3 sections after tail pipe
is connected Into exhaust end of tail
pipe
175 2001-8000 ft* All 7 37-1/8" 3 37-1/8" 3 sections after tail pipe
200 2001-6000 ft* is connected
Straight heat exchanger tube adjacent
to the tail pipe (See Figure 12C) 7 37-1/8" 5 37-1/8" 5 sections after tail pipe
is connected Into exhaust end of tail
pipe
65 or 0 - 2000 ft 7 37-1/8" 5 37-1/8" 2 sections before "U" Into end of straight
70 ft or "L" is connected before "U" or "L"
3 sections after tail pipe
is connected Into exhaust end of tail
pipe
175 2001-8000 ft* All 7 37-1/8" 3 37-1/8" 3 sections after tail pipe
200 2001-6000 ft* is connected
* To install a heater above 2000 ft elevation, that heater must either be factory-built for the required elevation or field-converted to that
elevation. Check the ratingplate or field conversion label for allowable altitude.
** Metric equivalent: 37-1/8" is 943mm; 26" is 660mm
Into exhaust end of tail
pipe
Into exhaust end of tail
pipe
Into exhaust end of tail
pipe
All 5 sections after tail
pipe is connected Into exhaust end of tail
pipe
Into exhaust end of tail
pipe
Into exhaust end of tail
pipe
Used in the
Configuration Quantity, Type and
WHEN to Install WHERE to Install
Turbulator Sections (Some sections may not be used; follow instructions.)
Length
of
Strai
g
ht
Tubes
BTUH
Size
(000)
(Must be illustrated in the
Suspension Dimension and
Configuration Booklet.)
In Tube
Packages
Elevation
"U" or "L" tube adjacent to the tail
pipe (See Figure 12D)
"U" or "L" tube adjacent to the tail
pipe (See Figure 12D)
Straight heat exchanger tube adjacent
to the tail pipe (See Figure 12C)
"U" or "L" tube adjacent to the tail
pipe (See Figure 12D)
"U" or "L" tube adjacent to the tail
pipe (See Figure 12D)
Straight heat exchanger tube adjacent
to the tail pipe (See Figure 12C)
Straight heat exchanger tube adjacent
to the tail pipe (See Figure 12C) 5 long sections after tail
pipe is connected
100
125
150 0 - 8000 ft*
"U" or "L" tube adjacent to the tail
pipe (See Figure 12D)
5 long sections after tail
pipe is connected
20 ft
25 ft
30 ft
35 ft
40 ft
45 ft
75
100
125
100
125
50 ft
55 ft
Into exhaust end of tail
pipe
Into exhaust end of tail
pipe
All 3 sections after tail
pipe is connected
All 3 sections after tail
pipe is connected
All 3 sections after tail
pipe is connected Into exhaust end of tail
pipe
Into exhaust end of tail
pipe
"U" or "L" tube adjacent to the tail
pipe (See Figure 12D)
Into exhaust end of tail
pipe
Into exhaust end of tail
pipe
All 4 sections after tail
pipe is connected
3 long sections after tail
pipe is connected
0 - 8000 ft*
0 - 8000 ft*
0 - 8000 ft*
0 - 8000 ft*
0 - 8000 ft*
St raigh t
"U" or "L"
All
All
175
200 0 - 2000 ft
175
200 0 - 2000 ft
175
200
175
200 0 - 2000 ft
150 0 - 8000 ft*

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 11
Straight
Tube
Tail Pipe
Straight
Tube
Tail Pipe
Straight
Tube
Tail Pipe
LTube
Tail Pipe
Straight
Tube
Straight
Tube
U
Tube
Tail Pipe
Figure 12C - Examples of Configurations with theTail PipeAdjacent to a Straight Heat ExchangerTube
To install turbulator:
1) Attachthetailpipeto the straight
pipe.
2) Insertaturbulatorsection intothe
tailpipe.
3) Interlock turbulator sections as
they are inserted (See Figure
12B).
4) Continue until all required sec-
tions are in place.
Figure 12D - Examples of Configurations that require more than three turbulator
strips and have the tail pipe adjacent to an "L" or "U" heat exchanger tube To install turbulator:
1) Beforeattachingthe "U" or "L"tube,
inserttwointerlocked turbulator sec-
tions (See Figure 12B) into the last
straight tube.
2) Attachthe"U"or "L"heatexchanger
tube to the straight tube.
3) Attachthetail pipe to the "U" or "L"
tube.
4) Insert three interlocked turbulator
sections into the tail pipe.
4) Level the System and Close "S" Hooks
Tubes must be level. Use a spirit level and adjust the turnbuckles or chain links. Close all "S" hooks being careful not to change the chain length.When
the system is level, re-check to be sure that all bolts connecting the tubes are tightened securely.
Straight systems should be straight; systems with "L" tubes should be at right angles; and "U" shaped systems should be parallel.
Summary of Number of Sections Required to "Build" Turbulator Strip
(NOTE: There may be sections in the packages that are not used.)
Elevation of
Installation (ft) BTUH Sizes
(000) Length
(Straight) Configuration No. of Sections used in
Turbulator Strip
20 ft Straight 4 (3 long, 1 short)
50-75 20 ft "U" or "L" 3
25 ft 3
0 - 8000 50-75-100 30 ft 3
75-100 35 ft Straight, 3
75-100-125 40 ft "U", 5
100-125 45 ft and 5
100-125-150 "L" 5
0 - 2000 175-200 50 ft 5
2001-8000 175-200* 3
0 - 8000 150 55, 60 ft 5
0 - 2000 175-200 55, 60, 5
2001-8000 175-200* 65, 70 ft 3
*Size 200 - Maximum elevation is 6000 feet.

Form RZ-NA-I-TR, Page 12
3. Install the Reflector, Optional Side Shield, and Reflector
Retainers (Refer to Figure 15)
a) AllInstallations--Nestlethe reflector inside theflangededges
of the reflector brackets.
b) Installations with Optional
Side Shield -- The side shield is
modular with two sections per
10-fttube. When side shields are
includedinthe installation, drill a
9/64" hole in each tube joint and
insert the screw provided (See
Figure 14). Hang the side shield
sections over the ends of the re-
flectorbrackets(Maximum angle
withsideshield is 30°).IMPOR-
TANT: Install side shield on
one side of the system only.
Figure 14 - With
optional side shield,
insert a screw in each
tube joint to prevent
tubes from turning
1/2" (13mm)
Drill
9/64"
hole
Reflector
Reflector
Retainer
U-bolt
Figure 16A -
Optional
ReflectorGap
Cover
c) All Installations -- Position a wire retainer over the reflector and hook the
ends through the holes in the reflector brackets. Install a retainer at each
reflectorbracket.
d) All Installations -- Repeat the instructions to install reflectors on each
straightsectionof tube in the system.Donotoperatetheheaterwithoutall
reflectorsinstalled.
4. Install Optional Reflector Gap Covers -- The optional gap covers are
designed to provide the infrared tubular
systemwithacontinuousreflectorwhile
still allowing for system expansion. If
optionalreflectorgap covers areincluded
in the installation, follow the illustrated
instructions included in the option pack-
age.Reflectorsonsystemswithgap cov-
ers cannot be rotated.
5.Install Optional ReflectorEnd Cover -
-Theoptionalendcoversaredesigned to
"close"the verticalspaceon boththecom-
bustionchamberendandthetailpipeend
ofthe reflectorlength.The endcoversmay
only be installed on units that have op-
tional reflector gap covers. Follow the il-
lustrated instructions included in the op-
tionpackage.
6.RotatingReflectors -- Reflectors on straight systems without reflector gap
covers or a side shield may be angled up to 45° by rotating the U-bolt and
reflectorbracket.
Reflectors with gap covers cannot be rotated.
Reflectors on straight systems with a side shield may be angled up to 30°.
The side shield must hang vertically.
Figure
16B -
Optional
Reflector
End
Covers
WARNING: Do not operate heater without reflectors. See Hazard Intensity Levels, page 2.
Packagedwitheachstraighttubeisareflector, two reflector brackets with hardware, and two reflector retainers (Refer to Figure 10E on page 7). Follow
the instructions to install a reflector on all straight tubes.
NOTE: If the installation includes an optional side shield, the side shield package (Options CD13-20) includes two additional reflector brackets and
retainers for each 10-ft tube.All four brackets must be attached to each 10-ft tube before installing the reflector.
Reflector Installation Instructions
11. Install Reflectors (including Standard Reflectors, Optional Side
Shield and Optional Reflector Gap and End Covers)
1. From thetable, determinethe
number of brackets (and re-
tainers)required pertube and
select the appropriate illus-
tration(Figure13Aor 13B).
2. InstallReflector Brackets
(See Figure 13A or 13B)
a) Slide the U-bolt over the tube at the determined location.
b) Positionthereflectorbracketasillustrated(endflangesextend-
ingupward)and slide the bracketover the bolt ends.Adjustthe
bracket to the desired reflector angle (0-45o). Use the nuts to
attach the reflector bracket to the U-bolt.
c) Repeat the procedure to install all required brackets.
Tube
Length Side
Shield Number of
Brackets Refer to
Figure
10-ft Without 2 13A
10-ft With 4 13B
5-ft Without 2 13A
5-ft With 2 13B
Figure 13A - Locations for Reflector Brackets for
Systems withoutan Optional Side Shield Figure 13B - Locations for Reflector Brackets for Systems
with an Optional Side Shield
Optional
Side
Shield Reflector
Bracket
Figure 15 - Install Reflector,
SideShield (Optional), and
ReflectorRetainers
12
(305mm) 36 (914mm) 12
(305mm)
Optional 5-ft Heat Exchanger Tube
6 feet (1.8M) 2 ft
(610mm)
approximate
Reflector Bracket
U-Bolt
10-ft Heat Exchanger Tube
10-ft Heat Exchanger Tube
Optional
5-ft Heat
Exchanger
Tube
13
(330mm)
13
(330mm)
32-3 4
(832mm)
32-3 4
(832mm)
24-1 2
(622mm)
32-3 4
(832mm)

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 13
SpecificVent Requirements
1.Vent Pipe Length -The vent lengths shown in theVent Table are based on
(1) the maximum permissible resistance to flow at which each model size will
operate and (2) the potential for continuous condensing. Condensing in the
vent pipe should not occur after equilibrium has been reached when the sur-
rounding ambient temperature is 60°F unless otherwise noted (See Require-
ment No. 6, Condensation).
Do not exceed maximum vent length. Minimum vent length is 5 feet.
Use equivalents listed when calculating for elbows and optional dual vent
adapter (Option CC5).
12.Venting
Venting must be inaccordancewiththe National Fuel Gas Code Z223.1(NFPA
54) or CAN/CGA B149.1 and B149.2, Installation Code for Gas Burning
Appliances and Equipment, and all local codes.
ANSI standard applicable to this heater does not require venting categoriza-
tion; if such a requirement existed, this heater would be in Category III. (Cat-
egory III appliances have a positive-pressure vent requiring a gastight sealed
vent system.) These tubular infrared heaters have been designed to operate
safely and efficiently with vent pipe lengths shown in theVent Length Table.
Vent systems may either be vertical or horizontal. The type of vent required
depends on the size of heater and the vent run configuration.
Type ofVent Required byVent Category
Model Sizes 50-125 150-200
- with a Horizontal Vent Run Category III Category III
- with a Vent Run that is at least one-half Category I
vertical (using equivalent lengths from the or Category III
Vent Length Table below) Category III
- with a Dual Vent Adapter (Option CC5) Category III Category III
Vent terminal end may be either single-wall pipe or double-wall pipe.A vent
terminal cap is required. Install a vent cap supplied as Option CC1 or a fully-
comparable, field-supplied vent terminal cap such as a Type L BreidertAir-x-
hauster®. (Type L Air-x-hauster®is a trademark of The G. C. Breidert Com-
pany.) Dual venting of two units is permissible when using an Optional Dual
Vent Kit (Option CC5).
Comply with the specific requirements and instructions in the following para-
graphs.
2.Vent Pipe Type - Use only 4-inch diameter vent pipe.
If the type of vent required is Category III (refer to table
above),useeither a vent pipe approved for a Category III heater or
appropriatelysealed 26-gauge galvanizedsteelor equivalentsingle-
wall pipe.
Ifthe type of vent required isCategory I (refer to table above),
unsealed26-gauge galvanized steel or equivalent single-wall pipe
or double-wall (Type B) vent pipe may be used.
3. Vent Pipe Joints - Vent system joints depend on the vent cat-
egory and the type of pipe being used.
If installed as a Category III appliance and using single-wall
vent pipe, join pipes with at least two non-corrosive screws per
vent pipe joint and seal all joints to prevent leakage of flue gases
into the building. For sealing joints, the use of Aluminum or
TEFLON®(trademark of DuPont Corporation) tape suitable for
550°F is recommended (required in California).Vent tape of this
type is available from the heater manufacturer as P/N 98266.
If installed as a Category III appliance and using vent pipe
specifically approved for Category III vent systems, follow
the pipe manufacturer's instructions for proper sealing.
If installed as a Category I appliance (allowed only for Sizes
50-125 when at least half of the total equivalent length of the
ventsystemisvertical), use at least two non-corrosive screws per
ventpipejoint on single-wallpipeorfollow the pipemanufacturer's
instructions for joining double-wall pipe.
4.Attach Vent Pipe to Heater - The last heat exchanger section
(tail pipe) is designed to permit direct attachment of a vent pipe,
either straight or elbow.
Attach metal vent pipe using three non-corrosive screws spaced
equal distance apart. See Figures 17A and 17B.
Suspended
Tail Pipe
Non-corrosivesheetmetal
screws spaced approximately
120° apart
Single wall straight pipe section
Single wall
elbow or
Figure 17A -
AttachMetal
Vent Pipe to
Tail Pipe
If the system includes a "U" or "L" heat exchanger tube, the reflectors on
either adjacent side of the "U" or "L" reflector cannot be rotated and must
remain horizontal. All reflectors in a section or leg of the tubular system
should be at the same angle.
Tape joint with high temperature
aluminum tape or seal with high
temperaturesiliconerubbersealant.
Figure 17B - Seal
Tail Pipe and Vent
Pipe Joint
5.Vent System Support - Vent pipe support is especially impor-
tant with the tubular infrared system because of the added stress
which may be caused by expansion and contraction of the overall
system. Support lateral runs a minimum of every six feet using
non-combustiblematerial, such as steel strap or chain. Do not rely
on the heater for support of either horizontal or vertical vent pipe.
Vent Length Equivalent Length for
Max Min Max Min ft M ft M ft M
50 20, 25, 30 4 20 5 6.1 1.5 3 0.9 1-1/2 0.5 3 0.9
20, 25 4 45 5 13.7 1.5 6 1.8 3 0.9 6 1.8
75 30, 35 4 35 5 10.7 1.5 5 1.5 2-1/2 0.8 5 1.5
40 4 20 5 6.1 1.5 3 0.9 1-1/2 0.5 3 0.9
30, 35 4 45 5 13.7 1.5 6 1.8 3 0.9 6 1.8
100 40, 45 4 35 5 10.7 1.5 5 1.5 2-1/2 0.8 5 1.5
50 4 20 5 6.1 1.5 3 0.9 1-1/2 0.5 3 0.9
125 40, 45, 50 4 60 5 18.3 1.5 12 3.7 6 1.8 12 3.7
150 50, 55, 60 4 60 5 18.3 1.5 12 3.7 6 1.8 12 3.7
175 50, 55, 60,
65, 70 4 60 5 18.3 1.5 12 3.7 6 1.8 12 3.7
200 50, 55, 60,
65, 70 4 60 5 18.3 1.5 12 3.7 6 1.8 12 3.7
*Must be deducted from the total vent length of each heater.
Vent Length Table for Tubular InfraredHeaters
feet M 90°
Elbow 45°
Elbow
Dual
Vent
Adapter
Box*
Input Size (000)
Straight
Tube
Length
(ft)
Vent Diameter
(inches)

Form RZ-NA-I-TR, Page 14
6 ft
(1829mm)
minimum
Roof Flashing
Roof pitched
from 0 to 45°
6 (152mm)
minimum
Clearance to be
as specified on
Type B
(double wall)
vent pipe
Follow the instructions above to join double wall and single
wall pipe and to attach a vent cap to double wall pipe.
Vertical flue extension
to be 6 (152mm)
higher than anticipated
snow depth but no less
than 24 (610mm) above
the roof. Vertical pipe
extension must be
insulated.
Parapet or adjoining building
3 ft (914mm)
minimum
If the fresh air intake is
within 10 feet (3M) of the
flue extension, the flue
extension must be at least
12 (305mm) higher than
the fresh air intake.
Fresh air intake must
be 6 (152mm)
higher than antici-
pated snow depth.
6 ft
(1829mm)
minimum
Roof Flashing
Vertical flue extension must
be 6 (152mm) higher than
anticipated snow depth but no
less than 24 (610mm) above
the roof. Vertical pipe extension
must be insulated.
Parapet or adjoining building
Roof pitched
from 0 to 45°
An approved clearance
thimble for single-wall
vent pipe is required when
the flue piepe extends
throu
g
h combustible maerial.
Figure 18A -Vertical Vent Terminal Arrangements (drawings are not proportional; read all information)
6 ft
(1829mm)
minimum
Roof Flashing
Roof pitched
from 0 to 45°
Vertical flue extension
to be 6 (152mm) higher than
anticipated snow depth but no
less than 24 (610mm) above
the roof. Vertical pipe extension
must be insulated.
Parapet or adjoining building
Follow the instructions above to join double wall and
single wall pipe and to attach a vent cap to double wall pipe.
Clearance to be as specified on
Type B (double wall) vent pipe
6 (152mm)
minimum
Figure 18B -VerticalVent Terminal/Air IntakeArrangements (drawings are not proportional; read all information)
6 ft
(1829mm)
minimum
Roof Flashing
Roof pitched
from 0 to 45°
An approved clearance
thimble for single wall
vent pipe is required
when the flue pipe extends
through combustible
mat
e
rial
.
Vertical flue extension
to be 6 (152mm)
higher than antici-
pated snow depth
but no less than 24
(610mm) above the roof.
Vertical pipe extension
must be insulated.
3 ft (914mm)
minimum
Fresh air intake must
be 6 (152mm)
higher than antici-
pated snow depth.
If the fresh air intake is
within 10 feet (3M) of the
flue extension, the flue
extension must be at least
12 (305mm) higher than
the fresh air intake.
Parapet or adjoining building
INSTRUCTIONS FOR DOUBLE WALL PIPE INSTALLA-
TION: Material Required: Double wall (Type B) Vent Pipe (Note:
Use only one piece of double wall vent pipe.); a thimble designed for
double wall pipe (if construction is combustible); six 3/4" long
sheetmetal screws; the vent cap; and a tube of silicone sealant.
11.Venting (cont'd)
6. Condensation- If single-wall vent pipe is exposed to cold air or run
through unheated areas, it must be insulated. Where extreme conditions
are anticipated, install a means of condensate disposal.
7.VentTerminal andVent Cap- The vent system must be terminated
with the type of vent cap approved for use with this heater. The vent
terminal and vent cap must be the same diameter as the vent run. Use
either an optional (Option CC1) vent cap or equivalent such as a Type L
BreidertAir-x-hauster®.(Type LAir-x-hauster®is a trademark ofTheG.
C. Breidert Company.) A different style vent cap could cause nuisance
problems and/or unsafe conditions.
See the illustrations in Figures 18 and 19 for requirements of both verti-
cal and horizontal vent termination. Using either single or double wall
ventterminals is illustrated. Many local codes require the use of double-
wall (Type B) vent for the portion of vent pipe (terminal) on the outside
of the building.
If double-wall pipe is used in the vent terminal, follow the instructions
below to attach the vent cap and to connect the double-wall pipe to the
single-wall vent system.
Instructions to attachVENT CAP to DOUBLE WALL (Type B)
VENT TERMINAL
Look for the "flow" arrow on the vent pipe.Attach the vent cap to the
"exhaust" end of the double wall pipe.
1) Slide the vent cap inside the pipe.
2) Drill a hole through the pipe and the vent cap. (Hole should be
slightly smaller than the sheet metal screw being used.) Using a 3/4"
long sheet metal screw, attach the cap to the pipe.
3) Repeat Step 2) drilling and inserting two additional screws evenly
spaced (120° apart) around the pipe.
Instructions to connect the SINGLE WALL VENT system to a
DOUBLE WALL (Type B) VENT TERMINAL:
1) Slide the single wall pipe inside the inner wall of the double-wall
terminalpipe.
2)Drilla hole through both walls of the double wall pipeandthesingle
wallpipe.(Holeshouldbe slightly smaller than the sheet metal screws
being used .) Using a 3/4"long sheet metal screw, attach the two pieces
of pipe. Do not overtighten.
3) Repeat Step 2) drilling and inserting two additional screws evenly
spaced (120° apart) around the pipe.
4)To seal the annular opening (the gap between the single and double
wallpipe),runalargebead of silicone sealant in the opening. The bead
of sealant must be large enough to seal the opening, but it is not
necessary to fill the full volume of the annular area.
SINGLE WALL - Single wall vent run and single wall
terminalend DOUBLEWALL- Single wall vent runanddouble
wall terminal end
SINGLE WALL - Single wall vent run; single wall
terminal end; and single wall fresh air intake DOUBLE WALL - Single wall vent run; double wall
terminal end; and single wall fresh air intake

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 15
Air Inlet Terminal Clearance -- The bottom of the air inlet
terminal shall be located not less than one foot (30 cm) above
gradeandat least 6 inches (15 cm) above anticipated snow depth.
The distance of termination of the horizontal vent from adjacent
public walkways, adjacent buildings, openable windows, and
building openings must be in accordance with local codes , or in
the absence of local codes, must conform with the National Fuel
Gas Code. More stringent local codes supersede all provisions in
these instructions and in the National Fuel Gas Code. Minimum
clearances for the horizontal vent terminal are shown in the table
on the right.
NOTE:Maintaintherequired18"clearancefromthe wall to
the vent terminal cap for stability under wind conditions
and to protect the building. Products of combustion can cause
discoloration of some building finishes and deterioration of ma-
sonry materials.Applyinga clearsiliconesealantthatisnormally
usedtoprotectconcrete driveways can protect masonry materials.
If discoloration is an esthetic problem, relocate the vent or install
averticalvent.
HorizontalVentTerminal Clearances (See Figure 19)
Wall
Pitch flue pipe
down toward outlet
1/4 per foot for
condensate drainage. Note position of
vent cap openings.
18
(457mm)
minimum
6 ft (1829mm)
minimum
3 ft (914mm)
minimum
Roof or building overhang
Parapet or adjoining building
Clearance to be
as specified on
Type B (double
wall) vent pipe
Follow the
instructions
on page 14
to join double
wall and single
wall pipe and
to attach a vent
cap to double
wall pipe.
6 (152mm)
minimum
Wall
Approved
clearance
thimble is
required
when flue
pipe extends
through
combustible
material.
18
(457mm)
minimum
Pitch flue pipe
down toward outlet
1/4 per foot for
condensate drainage.
Note position of
vent cap openings.
6 ft (1829mm)
minimum
Parapet or adjoining building
Roof or building overhang
3 ft (914mm)
minimum
Wall
18 (457mm)
minimum
18
(457mm)
minimum
Fresh air intake cap
9
(
229mm
)
maximum
Pitch flue pipe
down toward outlet
1/4 per foot for
condensate drainage.
Note position of
vent cap openings.
Roof or building overhang
3 ft (914mm)
minimum
6 ft (1829mm)
minimum
Parapet or adjoining building
Approved
clearance
thimble is
required
when flue
pipe extends
through
combustible
material.
Note position of
vent cap openings.
6 ft (1829mm)
minimum
3 ft (914mm)
minimum
18
(457mm)
minimum
Clearance to be
as specified on
Type B (double
wall) vent pipe
Fresh air intake cap
9 (229mm)
maximum
6 (152mm)
minimum
Pitch flue pipe
down toward outlet
1/4 per foot for
condensate drainage.
Roof or building overhang
Parapet or adjoining building
Follow the
instructions
on page 14
to join double
wall and single
wall pipe and
to attach a vent
cap to double
wall pipe.
18 (457mm)
minimum Wall
Figure 19A - HorizontalVent TerminalArrangements (drawings are not proportional; read all information)
Figure 19B - HorizontalVent Terminal/Air IntakeArrangements (drawings are not proportional; read all information)
Structure Minimum Clearances for Vent
Termination Location (all
directions unless specified)
Forced air inlet within 10 ft (3.1m) 3 ft (0.9m) above*
Combustion air inlet of another
appliance 6 ft (1.8m)
Door, window or gravity air inlet 4 ft (1.2m) horizontally
(any buildingopening) 4 ft (1.2m) below
3 ft (0.9m) above
Electric meter, gas meter ** and
relief equipment 4 ft (1.2m) horizontally
Gas regulator ** 3 ft (0.9m)
Adjoining building or parapet 6 ft (1.8m)
Grade (ground level) 7 ft (2.1m) above
*This heater is approved for installation as illustrated in Figure 19B.
**Do not terminate the vent directly above a gas meter or service regulator.
SINGLE WALL - Single wall vent run and single wall
terminalend DOUBLEWALL - Single wall ventrun and double
wall terminal end
SINGLE WALL - Single wall vent run; single wall
terminal end; and single wall fresh air intake DOUBLE WALL - Single wall vent run; double wall
terminal end; and single wall fresh air intake

Form RZ-NA-I-TR, Page 16
6 (152mm)
clearance to combustibles
Dual Vent
Adapter Box
Approved thimble required when the flue pipe
extends through combustible materials.
6 ft (1829mm)
maximum
6 ft (1829mm)
minimum
Vent pipe
from heater
Vent pipe
from heater
Vertical extension must be 6 (152mm)
higher than anticipated snow depth
but not less than 24 (610mm) above
the roof
Roof Flashing
Parapet or adjoining bulding
Single wall outer dual vent pipe
Single wall inner dual vent pipe
Roof or building overhang
3 ft (914mm)
minimum
6 ft (1829mm)
minimum
18 (457 mm)
minimum
6 (152mm)
clearance to combustibles
Dual Vent
Adapter Box
Wall
6 ft (1829mm)
maximum
Parapet or adjoining building
Pitch flue pipe down toward outlet 1/4 inch
per foot for condensate drainage.
Approved thimble required when the flue pipe
extends through combustible materials.
Single wall outer dual vent pipe
Single wall inner dual vent pipe
Figure 20B - Horizontal DualVent
TerminalArrangement
Figure 20A -Vertical
DualVentTerminal
Arrangement
11.Venting (cont'd)
VentTerminal Arrangements (cont'd)
UnventedInstallation -- These tubular radiant heaters areapproved for
operation without an outdoor vent. Before installing a tubular infrared
heater in the unvented mode, extreme care should be exercised in exam-
ining the building atmosphere and structure. Fresh air requirements
are4 CFM/1000 BTUH fornatural gas and 5CFM/1000 BTUH for
propane gas.
•Do not operate in the unvented mode when dust or dirt are present.
•Do not operate in the unvented mode in a building where contami-
nants are in the air that will produce a toxic gas when burned or
exposed to high temperatures.
NOTE:If either of the above situations exist, it is recommended that
a vented system with an optional combustion air inlet be installed.
•Do not operate in the unvented mode if there is any doubt about the
quality of the insulation in the building. Unvented operation in a
building that has an uninsulated roof or that may have uninsulated
structural members partially exposed to the outdoors may result in
condensation. The condensation may be severe enough to drip and/
or cause corrosion.
•Do not install in the unvented mode with outside combustion air
unless the inlet air cap is at or below the plane of the heater.
When installing a tubular infrared heater in the unvented mode, a vent
cap must be used and must be installed inverted as illustrated in Figure
21.
When a heater is operated without being vented to the outdoors, "TOP"
clearance to combustibles changes to 18 inches (See Paragraph 4).
WARNING: Dual venting of two heaters is permitted only when using the Dual Vent Kit, Option
CC5.(RefertoFigures 20A and 20B.) Noothermanifoldingofventruns is permitted due topossible
backpressureandrecirculationofcombustion products into the building. See Hazard Levels, page
2.
Duel Venting -- By using the Dual
Vent Option Kit, Option CC5, two
heatersmayusethe same vent termi-
nal. No other dual venting arrange-
ment is approved.
Follow the installation instructions
andrequirementsincluded in theOp-
tionKit.SeeVentTerminalArrange-
ments in Figures 20A and 20B.

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 17
Figure 21 - InvertTerminal Cap on IndoorVent
90°
Elbow
VentCap
Suspended
Tail Pipe
Attachvent cap to 90°
elbowusing three non-
corrosive sheetmetal
screwsspaced
approximately 120° a part.
Attach90° elbow to tail pipe using three non-
corrosive sheetmetal screws spaced
approximately 120° a part.
13. Combustion Air
The burner is equipped with a centrifugal blower to provide combus-
tionair.The air for combustion can come eitherfrom the heated space
orbepipeddirectlyfromthe outside. Combustion air should be piped
from the outside if (1) the pressure in the building is negative, (2) the
atmosphere is dirt laden, (3) the atmosphere contains any substance
that will cause toxic gas when passed through a flame, or (4) the
heater is installed in a tightly closed room that does not provide re-
quired air for combustion.
If drawing combustion air from the heated space, the screened
combustion air opening on the burner box must be kept clean. Main-
tain a minimum 12" clearance from the combustion air inlet opening.
If the heater is located in a tightly closed room and is not equipped
withacombustionairinletpipe,provisionmustbemadetosupplyair
for combustion to the room.
The requirements for combustion and ventilation air depend upon
whether the unit is located in a confined or unconfined space. An
"unconfined" space is defined as a space whose volume is not less
than 50 cubic feet per 1000 BTUH of the aggregate input rating of all
appliances installed in that space. Under all conditions, enough air
must be provided to ensure there will not be a negative pressure
condition within the equipment room or space.
Donot install a unit in a confined space without providing wall open-
ings leading to and from this space. Provide adequate openings near
floor and ceiling for ventilation and air for combustion, as shown in
Figure 22, depending on combustion air source as noted below.
AddtotalBTUHofall appliances in the confined space and divide by
figures below for square inch free area size of each (top and bottom)
opening.
1. Air from inside building -- openings 1 square inch free area per
1000 BTUH. Never less than 100 square inches free area for each
opening. See (1) in Figure 22 above.
Confined
Space
(3)
(3)
(1)
(1) (2)
(2)
Figure22-ConfinedSpace:
Aspace whose
volume is less
than 50 cubic
feet per 1000
BTUHof the
installed
appliance
inputrating.
2. Airfromoutside through duct -- openings 1 square inch free area per
2000 BTUH. See (2) in Figure 22 above.
3. Air direct from outside -- openings 1 square inch free area per 4000
BTUH. See (3) in Figure 22 above.
NOTE: For further details on supplying combustion air to confined space,
see National Fuel Gas Code Z223.1 (latest edition).
If directly piped outside combustion air is required, the burner/control box
is designed to accommodate attachment of a 4" diameter inlet air pipe. For
outside combustion air, use optional inlet air kit, Option DE2. Follow the
instructions included with the kit. The inlet air pipe should be 4" diameter
pipe of a noncorroding material. The maximum length of the inlet air pipe
mustnotexceedthe length shownin the CombustionAirInletLengthTable
below. If the inlet air pipe passes through moisture-laden air, insulation or
doublewalltubingmaybe needed to prevent condensation on the outside of
the pipe. Use the combustion air inlet cap supplied with the option kit.A
different type of combustion air inlet cap could cause nuisance problems
and/or unsafe operating conditions.
Iftheairinletterminalislocatedadjacenttothe exhaust terminal, the termi-
nals must be separated by a minimum distance of three feet. The only
exception is when the air inlet is located directly below the horizontal vent
cap. The required clearance between an air inlet terminal located directly
below the vent cap is 18 inches as illustrated in Figure 19B. See Figures
18B and 19B in Paragraph 12 for illustrations and clearance requirements
ofan air inlet terminal located adjacent to the heater vent terminal.
14. Gas Piping and Pressures
Allpipingmustbe in accordance with requirements outlined in theNational
Fuel Gas Code ANSI/Z223.1a (latest edition) or CAN/CGA-B149.1 and
B149.2, published by the Canadian Gas Association (See Paragraph 1).
Gassupply piping installation should conform with good practice and with
local codes.
Heaters for natural gas are orificed for operation with gas having a heating
value of 1000 (± 50) BTUH per cubic ft. If the gas at the installation does
not meet this specification, consult the factory for proper orificing.
The gas supply must have sufficient pressure to supply the burner plus any
other gas-fired appliances. Gas Supply pressure required at the burner
(measuredwith a manometer):
BTUH Gas SupplyPressure
Input Type Minimum Maximum
50,000 - 150,000 Natural 4.5" w.c. 14" w.c.
175,000 - 200,000 Natural 6" w.c. 14" w.c.
50,000 - 150,000 Propane 11" w.c. 14" w.c.
Maximum Length of Outside Combustion Air Inlet Pipe
Type of BTUH Heater Length Maximum Equivalent Length for
Inlet Pipe Size (Straight Tubes) Length 90oElbow 45oElbow
50 20/25/30
c75 20/25/30/35/40 5 ft (1.5M)
4" 100 30/35/40/45/50
Smooth 125 40/45/50
Wall 150 50/55/60
175 50/55/60/65/70
200 50/55/60/65/70
50 20/25/30
4" 75 20/25/30/35/40 N/A N/A
Corrugated 100 30/35/40/45/50
or 125 40/45/50
Flexible 150 50/55/60 N/A N/A
175 50/55/60/65/70
200 50/55/60/65/70
cAssumes the use of three feet of flexible pipe at the combustion
air inlet on the burner/control box.
80 ft
(24.3M) 10 ft (3M)
10 ft (3M) 5 ft (1.5M)
60 ft
(18.3M)
40 ft
(12.2M)
30 ft
(9.1M)

Form RZ-NA-I-TR, Page 18
10-12 (254-305mm) diameter
expansion curve or flexible gas
line MUST BE horizontal with
or above the gas connection.
Install a manual shutoff
valve with 1/8 NPT test
gauge port
10-12
(254-305mm)
diameter
expansion
curve
End
View
Side
View
Allow slack in the electrical cord.
Loop excess and bind loosely with
wire tie or electrical tape.
rounded Plug-in Cord
Drip
Leg
Capacity of Piping
Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)
Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)
Length Diameter ofPipe
of 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
Pipe Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane
20' 92 56 190 116 350 214 730 445 1100 671 2100 1281
30' 73 45 152 93 285 174 590 360 890 543 1650 1007
40' 63 38 130 79 245 149 500 305 760 464 1450 885
50' 56 34 115 70 215 131 440 268 670 409 1270 775
60' 50 31 105 64 195 119 400 244 610 372 1105 674
70' 46 28 96 59 180 110 370 226 560 342 1050 641
80' 43 26 90 55 170 104 350 214 530 323 990 604
90' 40 24 84 51 160 98 320 195 490 299 930 567
100' 38 23 79 48 150 92 305 186 460 281 870 531
125' 34 21 72 44 130 79 275 168 410 250 780 476
150' 31 19 64 39 120 73 250 153 380 232 710 433
175' 28 17 59 36 110 67 225 137 350 214 650 397
200' 26 16 55 34 100 61 210 128 320 195 610 372
Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.
Refer to National Fuel Gas Code for additional information on line sizing.
Sizing Gas Supply Lines
WARNING
Thisapplianceisequippedforamaximum gas supply pressure of 1/2 pound, 8
ounces, or 14 inches water column.
NOTE: Supply pressurehigher than1/2 pound requiresinstallation ofan additional serviceregulator
external to the unit.
PRESSURE TESTING SUPPLY PIPING
Test PressuresAbove1/2PSI: Disconnect the heater and manual valve from the gas supply line which is to be
tested. Cap or plug the supply line.
Test Pressures Below 1/2 PSI: Before testing, close the manual valve on the heater.
14. Gas Piping and Pressures (cont'd)
DANGER: Do not install gas piping where it
maybeexposedtoradiantorconvectionheat.
See Hazard Levels, page 2.
Figure 23 - Gas and Electrical Connections

Form RZ-NA-I-TR, Mfg No. 121027 Rev 5,
Page 19
WARNING: All components of the gas supply
system must be leak-tested prior to placing
equipment in service. NEVER TEST FOR
LEAKSWITHAN OPEN FLAME. See Hazard
Levels, page 2.
Manifold or Orifice Pressure Settings
Measuring manifold gas pressure cannot be done until the heater is in
operation.Itisincludedinthesteps of the "Check-Test-Start" procedure
in Paragraph 16. The following warnings and instructions apply.
Before attempting to measure or adjust manifold gas pressure, the inlet
(supply) pressure must be within the specified range for the gas being
used both when the heater is in operation and on standby. Incorrect inlet
pressure could cause excessive manifold gas pressure immediately or at
some future time.
Instructions for Checking Manifold Pressure:
1) With the manual valve (on the combination valve) positioned to pre-
vent flow to the main burners, connect a manometer to the 1/8" pipe
outletpressure tap in the valve.NOTE:A manometer (fluid-filled gauge)
is recommended rather than a spring type gauge due to the difficulty of
maintaining calibration of a spring type gauge.
Since the tubular heater does expand and contract, the connection be-
tween the supply line and the heater must allow for expansion and con-
traction. Use either an expansion coil (12" minimum diameter) or, if
permitted by local code, a flexible connection. If a flexible connector is
installed, use only an CSA certified, stainless steel connector with a
maximum length of 24" and a minimum size of 1/2" I.D. If a flexible
connector, Option CE3 or CE4, was ordered with the heater, it will be
shippedseparately.Optional flexibleconnectorshavethefollowingpres-
sure drops.
WARNING: Strong cleaning solutions or
chemicalsubstancesmustnotcomeincontactwith
theflexibleconnector.
Figure 24 -
Thermostat
Connections
Terminal
Strip
ManifoldPressure Settings
BTUHInput Gas Manifold Pressure
50,000 - 150,000 Natural 3.5" w.c.
175,000 - 200,000 Natural 5" w.c.
50,000 - 150,000 Propane 10" w.c.
15. Electrical Supply and
Connections
All electrical wiring and connections, including electrical grounding
MUST be made in accordance with the National Electric CodeANSI/
NFPA No. 70 (latest edition) or, in Canada, the Canadian Electrical
Code, Part I-C.S.A. Standard C22.1. In addition, the installer should be
aware of any local ordinances or gas company requirements that might
apply. The heater must be electrically grounded and connected to a sepa-
ratelyfusedcircuitwithadisconnectasrequiredbythe National Electri-
cal Code.
Heaters equipped for 115, 208, or 230 supply voltage have a grounded
plug-in cord. Be sure the outlet used provides the appropriate supply
voltage. Heaters equipped for 460 supply voltage require a separate
disconnect switch and line voltage supply run directly from the main
electrical panel to the unit.All external wiring must be within approved
conduit and have a minimum temperature rise of 60°C. The electrical
supply connects at the rear (valve end) of the burner/control box. Make
connections as shown on the wiring diagram located on the inside of the
service door.
WARNING: If you turn off or disconnect the
electrical power supply, turn off the gas. See
Hazard Levels, page 2.
Iftheheater has field-installed options thatrequireelectricalconnections,
consult the instruction sheet and wiring diagram supplied in the option
package.
Control Thermostat
The heater is designed for automatic
control from a remotely positioned
oroptional unit-mounted24-volt ther-
mostat and is equipped with a termi-
nal strip to facilitate thermostat con-
nections. See Figure 24.
Use either an optional thermostat
(OptionCL1) or a field-supplied 24-
voltthermostat.Do notattempttoop-
erate with a line voltage thermostat.
Locatea remote thermostat on an in-
sidewallintheheatedareabutnotin
the direct path of the infrared rays.
See the wiring diagram on page 20
or inside the heater door panel.
Multiple-Heater Control
Options are available to permit control of up to six heaters from a single
thermostat or a time clock and single/multiple thermostats. For maxi-
mumsafety,themultiplecontrolisdoneinthe low voltage circuit.Com-
plete instructions are included in each Option Kit. See Paragraph 24.
BTUH Pressure Drop(Inches W.C.)
Input Option CE3, 1/2" I.D. Option CE4, 3/4" I.D.
50,000 0.25 0.05
75,000 0.25 0.05
100,000 0.25 0.10
125,000 0.50 0.15
150,000 0.75 0.20
175,000 0.80 0.40
200,000 0.90 0.50
A shutoff valve and a drip leg or sediment trap must be provided in the
gas supply line at each heater. See Figure 23.
Use a joint compound that is resistant to propane gas at all connections.
Test all gas lines using a leak-detecting solution.
2)Openthevalve and operatethe heater. Measure the gaspressure to the
manifold. Normally, adjustments should not be necessary to the factory
presetregulator.
If adjustment is necessary, set pressure to correct settings by turning the
regulatorscrew IN (clockwise)toincreasepressure.Turnregulatorscrew
OUT (counterclockwise) to decrease pressure.
Consult the valve manufacturer's literature provided with the heater for
moredetailedinformation.

Form RZ-NA-I-TR, Page 20
WIRING DIAGRAM
This manual suits for next models
1
Table of contents
Other Thomas&Betts Heater manuals
Popular Heater manuals by other brands

Pro-Elec
Pro-Elec PELL0206 manual

Burda
Burda BHS3024 Instructions for use

Almost Heaven Saunas
Almost Heaven Saunas KIP-30-B1/FLB-30 Owner's/operator's manual

Beko
Beko CLEARPOINT S040 TWC Control Instructions for installation and operation

Micasa
Micasa MA0138OH-7F instruction manual

HEATSTRIP
HEATSTRIP Classic product manual