• The LEFT button + the UP button is a shortcut to show the Timer-ON value when in NORMAL mode.
• The LEFT button + the DOWN button is a shortcut to show the Timer-OFF value when in NORMAL mode.
• The RIGHT button is use to navigate between the parameters.
• The RIGHT button + the UP button is a shortcut to show the Start Count value when in NORMAL mode.
• The RIGHT button + the DOWN button is a shortcut to show the Elapsed Time Meter value when in NORMAL
mode.
• The MIDDLE/ENTER/CONFIG button is use to confirm and save a parameter value. It is also a shortcut to
navigate between the modes.
• The button in the lower right corner is the OFF button.
• The IPD is always in 1 of its 3 modes: Normal, Non-Auto, or Configuration.
• NORMAL: The controller will start if the pressure is below the cut-in. The controller will start if the START button
is pressed. To activate the Non-automatic mode, press the OFF button for 2 seconds. To activate the
Configuration mode, press the CONFIG button for 5 seconds.
• NON-AUTOMATIC: The controller will not start on a pressure drop. This is the maintenance mode. The
controller will start if the START button is pressed. To activate the Configuration mode, press the CONFIG button
for 2 seconds. To revert to Normal mode, press the OFF button for 2 seconds.
CONFIGURATION: The controller will not start on a pressure drop. This is the configuration mode. The controller
will start if the START button is pressed. Use the LEFT/RIGHT buttons to navigate between the parameters.
Press the ENTER/CONFIG button to select a parameter. This will display the current value. Use the UP+ /
DOWN- buttons to change the selected parameter value. The speed of the changing values will accelerate if the
buttons are maintained. Press the ENTER/CONFIG button to save a value. Press the OFF button to quit without
saving, and to revert to NORMAL mode.
Cut-in: Pressure start value. The controller will start if the pressure is below this value. It can be set from 0 to the
Cut-out value.
Cut-out: Pressure stop value. The controller will stop if the pressure is over this value. It can be set from the cut-in
value to the system maximum pressure.
Unit: Sets the pressure unit between PSI, BAR, KPA, FEET WATER,METER WATER.
Timer ON: Sets the timer between the pressure being below the cut-in and the motor start request.
Timer OFF: Sets the timer between the pressure being above the cut-out and the motor stop request.