Tornatech HFX Manual

1
INSTALLATION AND MAINTENANCE MANUAL FOR
ELECTRIC FIRE PUMP CONTROLLERS
MODEL HFX

2
HFX-Manual-EN v1.3.0.0
Table of Contents
1. Introduction
2. Installation
3. Main Features
4. Home
5. Alarms
6. Configuration
7. History
8. Technical Documents

3
Table of Contents
Introduction......................................................................................................................................................................5
Types of Electric Fire Pump Controllers ....................................................................................................................5
Methods of Starting/Stopping.....................................................................................................................................6
Installation.......................................................................................................................................................................7
Location......................................................................................................................................................................7
Mounting ....................................................................................................................................................................7
Storage.......................................................................................................................................................................7
Wiring and Connections.............................................................................................................................................7
Electrical Wiring .........................................................................................................................................................7
Electrical Connections................................................................................................................................................7
Energy Consumption..................................................................................................................................................7
Sizing..........................................................................................................................................................................8
Incoming Power Connections ....................................................................................................................................8
Motor Connections.....................................................................................................................................................8
Terminal Strip Descriptions........................................................................................................................................9
Quick Start-Up Guide...............................................................................................................................................10
Main Features ...............................................................................................................................................................15
The ViZiTouch..........................................................................................................................................................15
First Setup................................................................................................................................................................16
Home.............................................................................................................................................................................17
Home (Membrane button)........................................................................................................................................17
Screen Saver ...........................................................................................................................................................18
Alarms...........................................................................................................................................................................19
Alarms (Membrane button) ......................................................................................................................................19
Configuration.................................................................................................................................................................21
Config (Membrane button).......................................................................................................................................21
NumPad Page..........................................................................................................................................................22
Date and Time Page................................................................................................................................................22
User Login Page / KeyPad Page .............................................................................................................................23
Advanced Configuration Page .................................................................................................................................24
Details of the Advanced Configuration Page...........................................................................................................24
Timers Page.............................................................................................................................................................24
Voltage Calibration...................................................................................................................................................25
Current Calibration...................................................................................................................................................25
Inputs/Outputs Expansion board 1-2-3-4.................................................................................................................26
Update Program Page .............................................................................................................................................27
Factory Settings .......................................................................................................................................................27
Reset to Factory Settings Page ...............................................................................................................................28
Interlock Lockout......................................................................................................................................................29
History...........................................................................................................................................................................31

4
History (Membrane button) ......................................................................................................................................31
Details of the History Page ......................................................................................................................................32
Events Page.............................................................................................................................................................32
Download to USB Device.........................................................................................................................................32
The Statistics............................................................................................................................................................34
All Time Statistics.....................................................................................................................................................34
Technical Documents....................................................................................................................................................35
Pre-Field Acceptance Test.......................................................................................................................................36
Field Acceptance Test Report..................................................................................................................................38

5
Electric fire pump controllers are designed to start an electric motor driven fire pump. It can either start the fire
pump manually through the local start pushbutton or automatically through the sensing of a pressure drop in the
sprinkler system. The fire pump can be stopped manually with the local stop pushbutton or automatically after the
restauration of the pressure in the sprinkler system. In both cases, stopping is only allowed if all starting causes
have disappeared.
Types of Electric Fire Pump Controllers
FIRE PUMP CATALOG NUMBER
MODEL No. EXAMPLE: HFA - 208 / 160KW / 3 / 60
Model Prefix: HFA
Voltage: 208 V
HP/KW Rating: 215HP / 160KW
Phase: 3
Frequency: 60 Hz
ACROSS-THE-LINE STARTER
MODEL HFA:
This model is intended to be used where the local utility or the capacity of the power source permits across-
the-line starting.
Full voltage is applied to the motor as soon as the controller receives a start command.
REDUCED VOLTAGE STARTERS
These models are intended to be used where the local utility or the capacity of the power source does not permit full
voltage starting.
MODEL HFS: SOLID STATE STARTER
This model does not require a multi-connection motor. It only requires 3 conductors between the controller
and the motor.
Upon a start command, a solid-state starter is utilized to supply a step less ramp-up voltage to the motor
until the motor reaches its full speed.
This controller also features a soft motor stopping mode and a hard stop mode. For a hard stop, hold the
stop pushbutton until the motor stop.
MODEL HFW: WYE-DELTA CLOSED TRANSITION STARTER
This model requires a multi-connection motor and 6 conductors between the controller and the motor.
Upon a start command, the motor is connected to the line in the wye connection. After a time delay, the
motor is reconnected to the line in the Delta configuration applying full voltage to the motor windings by a
closed transition switching sequence.
The power source does not « see » any open circuit during the transition from wye to delta. During the
transition from Wye to Delta, a resistor bank is connected in the starting circuit and allows to keep the motor
coils energized. An 80 second delay is then triggered and prevent the motor from stoping. This delay allows
the resistors to cool down and will only be triggered if the transition occur. An emergency stop can still be
perform by pulling the disconnecting mean handle.
MODEL HFY: WYE-DELTA OPEN TRANSITION STARTER
This type of starter requires a multi-connection motor and 6 conductors between the controller and the
motor.
Introduction

6
Upon a start command, the motor is connected to the line in the Wye connection. After a time delay, the
motor is reconnected to the line in the Delta configuration applying full voltage to the motor windings. This
controller is of the open transition type. The motor is disconnected from the line during the transition from
start (wye) to run (delta) mode.
Methods of Starting/Stopping
The controllers are available as combination automatic / non-automatic with provision for manual or automatic
shutdown (an automatic shutdown is only possible after an automatic start).
METHODS OF STARTING
MANUAL START
The motor can be started by pressing the START push button, regardless of the system pressure.
REMOTE MANUAL START
The motor can be started from a remote location by momentarily closing a contact of a manual push button.
REMOTE AUTOMATIC START, DELUGE VALVE START
The motor can be started from a remote location by momentarily opening a contact connected to an automatic
device.
SEQUENTIAL START
In case of a multiple pump application, it may be necessary to delay the automatic (pressure drop) starting of each
motor to prevent simultaneous starting of all motors.
TEST START
The motor can be started manually by pressing the run test button.
METHODS OF STOPPING
MANUAL STOP
Manual stop is done by pressing the priority STOP push button. Note that pressing the stop push button will
prevent the motor from restarting as long as the button is pressed, plus a two second delay.
AUTOMATIC STOP
Automatic stop is possible only after an automatic start and if this function has been activated. When this function
is enabled, the motor is automatically stopped 10 minutes after the starting request is no longer present.

7
The HFX electric fire pump controller is intended to be installed in accordance with the European Standard EN
12845, Fixed firefighting systems –Automatic sprinkler system –Design, installation and maintenance.
Location
The controller shall be located as close as practical to the engine/motor it controls and shall be within sight of the
engine/motor. The controller shall be located or protected such that it will not be damaged by water escaping from
pump or pump connections. Current carrying parts of the controller shall be not less than 12 in. (305 mm) above the
floor level.
The controller is suitable for use in locations subject to a moderate degree of moisture, such as a damp basement.
The pump room ambient temperature shall be between 39°F (4°C) and 104°F (40°C) (If a temperature option is
included, see the rating label for maximum temperature).
The standard controller enclosure is rated IP55. It is the installer's responsibility to insure that either the standard
enclosure meets the ambient conditions or that an enclosure with an appropriate rating has been provided.
Controllers must be installed inside a building and they are not designed for outside environment. The paint color
may change if the controller is exposed to ultraviolet rays for a long period of time.
Mounting
The fire pump controller shall be mounted in a substantial manner on a single incombustible supporting structure.
Wall mounted controllers shall be attached to the structure or wall using all four (4) mounting ears provided on the
controller with hardware designed to support the weight of the controller at a height not less than 12 in. (305 mm)
above floor level. Floor mounted controllers shall be attached to the floor using all holes provided on the mounting
feet with hardware designed to support the weight of the controller. The mounting feet provide the necessary 12 in.
(305 mm) clearance for current carrying parts.
Storage
If the controller is not installed and energized immediately, Tornatech recommend following the instructions from the
chapter 3 of the NEMA ICS 15 standard.
Wiring and Connections
Electrical Wiring
The electrical wiring between the power source and the fire pump controller shall meet the local codes. Electrical
wiring shall be typically sized to carry at least 125% of the full load current (FLC or FLA) of the fire pump motor.
Electrical Connections
A licensed electrician must supervise the electrical connections. The dimension drawings show the area suitable for
incoming power and motor connections. No other location shall be used. Only watertight hub fittings shall be used
when entering the cabinet to preserve the IP rating of the cabinet. The installer is responsible for adequate
protection of the fire pump controller components against metallic debris or drilling chips. Failure to do so may
cause injuries to personnel, damage the controller and subsequently void warranty.
Energy Consumption
Standby power: 10W
Installation

8
Sizing
Incoming power terminals on the controller are suitable to accept wire based on that selection with insulation not
less than 60°C. (Refer to terminal diagram for terminal sizes.)
The electrical wiring between the fire pump controller and the pump motor shall be in rigid, intermediate, or liquid
tight flexible metal conduit or Type MI cable and meet the requirements of the electrical local codes.
The number of conductors required varies depending on the model of starter:
3-wires plus ground sized at 125% of full load current for models HFA and HFS.
6-wires plus ground sized at 125% of 58% of the motor full load current for: HFY and HFW models.
Incoming Power Connections
Incoming normal power is to be connected to terminals located on the disconnecting means IS.
- For 3 phases motor: identified L1-L2 and L3.
- For single phase motor: identified L1 and L3
Motor Connections
The motor wires shall be connected to terminals identified by:
- T1-T2 and T3 are located on the main contactor (1M) for model HFA.
- T1-T2 and T3 are located on the soft starter for model HFS.
- T1-T2 and T3 are located on the contactor (1M) and T6-T4 and T5 are located on the contactor (2M) for models
HFY and HFW.
It is the responsibility of the installer to obtain connection information on the motor and to assure that the motor is
connected as per motor manufacturer recommendations. Failure to do so may cause injuries to personnel, damage
the motor and/or the controller and subsequently void warranty on both items.

9
Terminal Strip Descriptions
Alarm output terminals (SPDT Relay, 11:Common,
12:Normally Closed, 14:Normally Open):
A: Motor Run
B: Power Available (Failsafe relay)
C: Pump on Demand
D: Fail to Start
E: Motor Trouble
F: Factory Reserved
Field input terminal (Dry Contact Only: Voltage Free):
G: Remote Manual Start (NO)
H: Lockout (NO)
I: Remote Automatic Start (NC)
J: Deluge Valve (NC)
K: Water Reservoir Low (NO)
L: Factory Reserved 3 (NO)
M: Factory Reserved 2 (NO)
N: Factory Reserved 1 (NO)
Factory IO:
O: Motor Run auxiliary contact
P: Main Coil power relay
Q: Delay Coil power relay
R: Water Level/Suction Pressure sensor
S: Spare Temperature/Flow sensor
T: PT1 Discharge Pressure sensor
U: PT2 Discharge Pressure sensor (redundant opt. only)
V: Test Solenoid Valve
W: Shunt Trip
X: Factory Reserved
Y: 24VAC input power
Z: CANBUS to IO cards
AA: Not used
AB: CANBUS to ViZiTouch
AC: Ground Fault
AD: Input Current sensing
AE: Ground
AF: Input Voltage sensing

10
Quick Start-Up Guide
The rating label is the most important label. It must be read carefully to ensure the compatibility between the
controller and the installation.
Verify that the controller is installed securely on the wall, or optionally on the mounting stand.

11
Make sure to drill holes for the motor and power connections and run the cables inside the panel, all in accordance
with the specifications in order to minimize interference with other equipment.
Connect the input power and the motor on their respective terminals. Secure with the appropriate torque as
indicated on the torque label and verify all connections. Secure the door in closed position then put the circuit
breaker disconnecting means in ON position. Verify the readings on the controller main screen.

12
Verify the motor rotation to ensure that the pump is turning in the right direction. The START and STOP push
buttons can be used to toggle the motor ON/OFF.
WARNING!
On a Wye-Delta closed transition starter, if the transition from Wye to Delta occurs (after 5 to 8 seconds depending
on the motor HP), the manual stop push button will be disabled for 80 seconds. To stop the engine before the end
of the 80 second delay, use the disconnecting mean handle.

13
The "First Setup" page replaces the Homepage until the "First Setup" is done. Proceed to the setup page and press
the lock to enter your authorization code.
Verify that all other parameters on the setup page are correct.
When satisfied with the controller settings, press the “Home” button on the membrane, then acknowledge the
changes by pressing the "Done" button. If the "Done" button is unavailable, ensure that a sufficient authorization
code has been entered and that at least all three voltages are valid.
Proceed with the download step to save the report.

14
Once the configuration is done, click on the “Home” membrane button. The “First Setup” page will be displayed
The “First Start up” is now completed. The controller is fully installed and configured.

15
The ViZiTouch
A: Power Available LED: Indicates that power is available.
B: Touch Screen: 4.3 inches color touch screen LCD.
C: Alarm LED: Indicates if an alarm is active.
D: Front USB Connector: USB Device connector used for files download, software update, service reports.
E: Home button: Used to navigate to the Home page.
F: Alarm button: Used to navigate to the Alarm page. It also allows the user to silence the alarm bell, hence the
small "no speaker" symbol.
G: Config button: Used to navigate to the Configuration page.
H : History button: Used to navigate to the History page.
I: Start button: Used to manually start the motor.
J: Stop button: Used to stop the motor.
K: Run Test button: Used to start the manual run test. Be aware that water will flow through the drain with models
equipped with a solenoid valve.
L: Contextual navigation pad: Used to facilitate the navigation on specific pages. A small icon representing the
contextual navigation pad will appear at the bottom right corner of a page if the pad is active. By clicking on the
small pad icon, a menu explaining the specific functions of the arrows will appear. For example, it is possible to
switch between the graphical or the table mode on the logs page, as well as navigate through the tables or the help
pages.
M: CAN bus connector to IO cards
N: USB 2.0 connector
O: Ethernet connector
P: Alarm Bell connector
Main Features

16
Warning
After 2 years of service, the Vizitouch battery may become less efficient and could lose the time after a shutdown.
First Setup
The First Setup must be done prior to using the controller. Completing the First Setup is the only way to access the
homepage and enable the automatic mode of the controller.

17
Home (Membrane button)
Home
The home page displays all controller statuses and important values of the controller. All voltages, currents,
pressure, motor state and status, as well as all timers and motor starting sequences.
The entire background will become red if an alarm becomes active. This feature will help the user identify a problem
even from a significant distance away from the controller.
A: Navigation bar which contains general information about:
- The language (the language may be changed by pressing on it)
- The page title
- The alarm banner (warning and alarm messages may be shown)
- The date and time (adjustable in the Configuration page)
B: Voltages. Each box represents an individual phase voltage between the two adjacent lines.
C: Current. Each box represents an individual phase current between the two adjacent lines.
D: The motor contactors are represented here. An animation shows the contactor opened or closed depending on
the signal sent to the main coil.
E: The electric motor. It will be grey if the engine is stopped, green if a “Motor Run” signal is detected and red if a
“Fail to start” occurred. Pressing on the engine will redirect the user to the “Last Service Statistics” page, which
monitors all relevant statistics concerning the controller since the last service.
F: Timers. Sequential start timer (on-delay) will start counting upon activation of an automatic starting demand. The
motor will only start if the starting request is still active after the expiration of this timer. The minimum run period
timer (off –delay) for automatic shutdown, will start counting once the starting request is no longer active. The pump
will stop at the expiration of this timer if no starting request is active. If a periodic test has been programmed, the
remaining time will be displayed. If a manual run test has been energized, the remaining time will be displayed.
G: The alarm/warning notification.
Warning indicator: Exclamation mark in a yellow round icon. If no alarm is in active condition on the controller and at
least one warning is ACTIVE or OCCURRED, the warning indicator will be present.
Home

18
Alarm indicator: Exclamation mark in a red triangle icon. As soon as at least one alarm is active or occurred, the
alarm indicator will be flashing.
H: The motor configuration symbol shows how the motor is wired to the contactor(s). This symbol is used to show if
the motor is in a starting configuration (Wye wiring, for example) or in a permanent running configuration (i.e. delta
wiring)
Permanent delta motor connection.
Temporary wye motor connection.
Temporary auto-transformer motor connection.
Temporary solid state starter motor connection.
I: Representation of the motor starting or stopping cause. A green capsule will indicate the reason why the motor is
running. Possible choices are:
MANUAL: Manual motor starting activated by the START push button.
REMOTE MANUAL: Manual motor starting activated by a remote start contact.
DELUGE: Automatic motor starting activated by a deluge valve.
REMOTE AUTO: Automatic motor starting activated by remote equipment.
MANUAL TEST: Automatic motor starting activated by the run test push button.
A red capsule will indicate the reason why the motor is not running despite the fact that a request is being made.
Possible choices are:
LOCKED: An interlock signal is preventing the motor from running.
J: Displays three statuses that describe the primary configuration of the controller: Pressure actuated or Non-
pressure Actuated, Automatic Controller or Non-automatic, Manual or Automatic Shutdown.
Screen Saver
After 5 minutes of inactivity on the ViZiTouch, the screen will dim it's brightness to 25%. After 10 minutes of
inactivity on the ViziTouch, the “Black Screen” screen saver will activate. Its goal is to expand the lifetime of the
LCD screen. The screen saver will be instantly deactivated if the engine is running or if an alarm is activated. To
manually deactivate it, simply touch the screen or any membrane button. After deactivation, the screen saver will
always redirect to the “Home” page. It will also log off any user by resetting the security level to 0 and save any new
modifications to the settings.

19
Alarms (Membrane button)
Alarms
Displays the list of currently active and occurred alarms. An alarm is called ACTIVE when its triggering condition is
still valid. An alarm is called OCCURRED when its triggering condition has been active, but is no longer true.
Alarms representing serious concerns are colored RED. Alarms representing simple warnings are colored
YELLOW. To silence the bell press the ALARM button or it will silence itself after the expiration of a factory set
timer. Pressing on the RESET button will reset OCCURRED alarms only. Alarms ending with ** are available on
transfer switch models only.
The table displays system events:
- Date and Time: Date and time stamp of the alarm in the YYYY.MM.DD format
- Message: Alarm message
- State: OCCURRED or ACTIVE
- Color Code:
- Red: The event is an alarm
- Yellow: The event is a warning
Complete list of alarms :
- Normal Phase Reversal: Activates when the phase order on the normal power does not match the correct value of
the controller. Each time a service is acknowledged on the ViZiTouch, the controller synchronises the correct phase
order to the one detected on the normal power.
- Phase Loss N1: This alarm is activated if the first phase of the normal power connection does not meet the
qualification criteria.
- Phase Loss N2: Activates if the second phase of the normal power connection does not meet the qualification
criterions.
- Phase Loss N3: Activates if the third phase of the normal power connection does not meet the qualification
criterions.
- Loss of power: Activates when a complete loss of normal power is detected.
- Fail to start: Activates if there is and under-current draw of two phases when the motor should be running. A 20
seconds factory set delay is used to give the motor enough time to start before signalling this alarm.
Alarms

20
- Undercurrent: Activates when current is under 30% of FLA and motor has been running for 15 seconds.
- Overcurrent: Activates when current is above 120% of FLA.
- Under voltage: Activates when normal power voltage is below 80% of nominal voltage.
- Over voltage: Activates when normal power voltage is above 120% of nominal voltage.
- Phase Unbalanced: Activates when there is a difference of more than 10% of nominal voltage between the normal
power voltage readings.
- Ground Fault: Activates when the ground fault input current is above the factory set value after a factory set delay.
- Water Reservoir Low: Activates if the “Water Reservoir Low” contact input is triggered or if the analog readout of
the water reservoir is enabled and is lower than the water reservoir low set point in the “Water Level” sensor page.
- Control Voltage Not Healthy: Activates when the 24VAC power input to the IO cards is below the acceptable
functional range.
- Motor Trouble: Activates when a motor related alarm condition is present (overcurrent, undercurrent, fail to start or
ground fault).
- Pump Room Alarm: Activates when a pump room related alarm condition is present (overvoltage, undervoltage,
phase unbalanced).
- Pump on demand: Activates when an automatic starting request is active.
Table of contents
Other Tornatech Controllers manuals