Tornatech MPA Manual

V2024.02
INSTALLATION AND MAINTENANCE MANUAL
FOR MEDIUM VOLTAGE ELECTRIC FIRE PUMP
CONTROLLERS MODEL MPA

V2024.02 2
TABLE OF CONTENTS
Important Safety Information 4
Introduction 6
TechnicalData 6
Installation 7
Storage 7
Environment 7
Electromagneticcompatibility(EMC) 7
Handling 7
FCCRegulationsandRadioStandardsSpecification(RSS)Rules 7
Location 8
Mounting 8
Floormounting 8
Wallmounting 8
MakingSystemPressureConnections 9
MakingElectricalConnections 9
ImportantPrecautions 9
Procedure 10
Operator interface 11
Methods of starting and stopping 12
Methodsofstarting 12
Automaticstart 12
Manualstart 12
Remotemanualstart 12
Remoteautomaticstart,delugevalvestart 12
Emergencystart 12
Sequentialstart 12
Teststart 12
Methodsofstopping 12
Manualstop 12

V2024.02 4
IMPORTANT SAFETY INFORMATION
Warning:
This product can expose you to chemicals including DINP, which is known to the State of Cali-
fornia to cause cancer, and DIDP which is known to the State of California to cause birth
defects or other reproductive harm.
Warning:
This product can expose you to chemicals including lead and lead compounds, which are
know to the State of California to cause cancer and birth defects or other reproductive harm.
Formoreinformationgoto:www.P65Warnings.ca.gov
DANGER
RISK OF ELECTROCUTION
PERSONAL INJURY OR DEATH COULD OCCUR.
ENSURE ALL POWER IS DISCONNECTED BEFORE INSTALLING OR SERVICING
THIS EQUIPMENT.

V2024.02 5
DANGER
Do not attempt to install or perform maintenance on equipment while it is energized! Death,
personal injury or substantial property damage may result from contact with energized equip-
ment. Always verify that no voltage is present before proceeding and always follow generally
accepted safety procedures. Controller disconnect switch must be in the “off” position in
order to open the enclosure door. Tornatech cannot be liable for any misapplication or incor-
rect installation of its products.

V2024.02 6
INTRODUCTION
MediumVoltageElectricFirePumpcontrollersaredesignedtostartanelectricmotordrivenfirepump.
Itcaneitherstartthefirepumpmanuallythroughthelocalstartpushbuttonorautomaticallythrough
thesensingofapressuredropinthesprinklersystem.Thefirepumpcontrollerissuppliedwithapres-
suretransducer.Thefirepumpcanbestoppedmanuallywiththelocalstoppushbuttonorauto-
maticallyaftertheexpirationofafieldprogrammabletimer.
TECHNICAL DATA
Rating Value
RatedOperationalCurrentIe AccordingtotheMotor(HP/kW)
RatedOperationalVoltageUe Accordingtothecontrollerratinglabel
RatedOperationalFrequency 50/60Hz
Standardenvironmentaltemperature 4°Cto40°C
Altitude ≤2000m
Relativehumidity 5%to80%
Pollutiondegree 3
ShortCircuitCurrentRatingIcc(SCCR)(A) Accordingtothecontrollerratinglabel
Standarddegreeofprotection NEMAType2
Standbypowerconsumption 10W

V2024.02 7
INSTALLATION
STORAGE
Ifthecontrollerisnotinstalledandenergizedimmediately,Tornatechrecommendsfollowingthe
instructionsinchapter3ofNEMAICS15.
ENVIRONMENT
MediumVoltageElectricFirePumpcontrollersareintendedtobeinstalledinlocationswhereambient
temperaturesarewithin4°Cand40°Candtherelativehumidityiscontrolledbetween5%and80%.
Optionally,thecontrollercanhaveanextendedtemperatureofupto55°Candaslowas-5°C,provided
thatthecontrollerandthepressurewaterpipesareheatedtopreventwaterfreezinganddamagingthe
electronicsandthepipingsystem.
Theyareintendedforpollutiondegree3andshallbeinstalledatanaltitudeofnomorethan2000
meters.Forabnormalinstallationenvironment,consultfactory.
ELECTROMAGNETIC COMPATIBILITY (EMC)
MediumVoltageElectricFirePumpcontrollershavebeentestedforthemoststringentconditionsfor
emissions(EnvironmentB)andimmunity(EnvironmentA),hencecontrollerscanbeinstalledineither
environment.Allcontrollersvariantssharethesameelectronicsandcomplytothosecriteriawithout
requiringadditionalmeasures.
HANDLING
TheweightofeachMediumVoltageElectricFirePumpcontrollerisindicatedonthepackinglabel.Light-
weightcontrollersdonotrequirespecialhandlinginstructions,whileheavycontrollersareequipped
withliftingmeansandshouldbehandledfollowingtheguidelinesspecifiedinTornatech'sdocument
"LargeEnclosureSafeHandlingRequirements_PN12162021".
FCC REGULATIONS AND RADIO STANDARDS SPECIFICATION
(RSS) RULES
TocomplywithFCCandIndustryCanadaRFexposurecompliancerequirements,aseparationdistance
ofatleast20cmmustbemaintainedbetweentheantennaofthisdeviceandallnearbypersons.This
devicemustnotbeco-locatedoroperatinginconjunctionwithanyotherantennaortransmitter.
Thisdevicecontainslicence-exempttransmitter(s)/receiver(s)thatcomplywithInnovation,Scienceand
EconomicDevelopmentCanada’slicence-exemptRSS(s).Operationissubjecttothefollowingtwocon-
ditions:
1. Thisdevicemaynotcauseinterference.
2. Thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesiredoper-
ationofthedevice.
Compliance:CANICES-003(B)/NMB-003(B)

V2024.02 8
Thisdevicecomplieswithpart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:
(1)Thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptanyinterference
received,includinginterferencethatmaycauseundesiredoperation.
Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,
pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainst
harmfulinterferencewhentheequipmentisoperatedinacommercialenvironment.Thisequipment
generates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordance
withtheinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operationofthis
equipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillbe
requiredtocorrecttheinterferenceathisownexpense.
“Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoid
theuser'sauthoritytooperatetheequipment.”
LOCATION
Consult the appropriate job plans to determine the controller mounting location.
Thecontrollershallbelocatedascloseaspracticaltotheengineormotoritcontrolsandshallbewithin
sightoftheengineormotor.Thecontrollershallbelocatedorprotectedsuchthatitwillnotbedam-
agedbywaterescapingfrompumporpumpconnections.Currentcarryingpartsofthecontrollershall
benotlessthan12in.(305mm)abovethefloorlevel.
WorkingclearancesaroundcontrollershallcomplywithNFPA70,NationalElectricalCode,Article110or
C22.1,CanadianElectricalCode,Article26.302oranyapplicablelocalcodes.
ThestandardcontrollerenclosureisratedNEMAType2.Itistheinstaller’sresponsibilitytoinsurethat
eitherthestandardenclosuremeetstheambientconditionsorthatanenclosurewithanappropriate
ratinghasbeenprovided.Controllersmustbeinstalledinsideabuildingandtheyarenotdesignedfor
outsideenvironment.Thepaintcolormaychangeifthecontrollerisexposedtoultravioletraysfora
longperiodoftime.
MOUNTING
TheMediumVoltageElectricFirePumpcontrollershallbemountedinasubstantialmanneronasingle
incombustiblesupportingstructure.
FLOOR MOUNTING
Floormountedcontrollersshallbeattachedtothefloorusingallholesprovidedonthemountingfeet
withhardwaredesignedtosupporttheweightofthecontroller.Themountingfeetprovidetheneces-
sary12in.(305mm)clearanceforcurrentcarryingparts.
WALL MOUNTING
Refer to the controller dimension drawing for necessary mounting dimensions.
Thecontrolleriswallmountedbyusingatleastfour(4)wallanchors,2anchorsforthetopmounting
bracketsand2anchorsforthebottommountingbrackets.Thebracketsaredimensionallyonthesame
centerlineforeaseinmounting.Thereshouldbeaclearanceofatleast6inches(152mm)aroundthe
controllertoallowproperaircirculationaroundtheequipment.

V2024.02 9
1. Usingeitherthedimensionprintorbymeasuringthedistancebetweenthecenterlinesofthe
lowerbracketslots,transcribethisdimensionontothewall.Note:Thebottomedgeoftheenclos-
ureshouldbeaminimumof12”(305mm.)fromthefloorincasefloodingofthepumproom
occurs.
2. Drillandputanchorsintothewallforthelowermountingbrackets.
3. Markonthewall,thelocationoftheholesintheuppermountingbrackets.
4. Drillandputanchorsintowallfortheuppermountingbrackets.
5. Installboltsandwashersinloweranchors.
6. Alignholesinuppermountingbracketsandinstallboltsandwashersinanchors.
7. Shimanchorsasnecessarytoensurerearofenclosureisverticallevelandenclosureisnot
stressed.
8. Tightenallanchorbolts.
9. Checktobesureenclosuredooropenandclosesfreelyandthatenclosureislevel.
MAKING SYSTEM PRESSURE CONNECTIONS
Thecontrollerrequiresone(1)“SystemPressure”connectionfromthesystempipingtotheenclosure.
Theconnectionfitting,1/2”NPTmaleport,isprovidedontheleftexternalsideoftheenclosureforthis
purpose.RefertoNFPA20forcorrectfieldpipingprocedureofthesensinglinebetweenthepumping
systemandthecontroller.Ifadrainispresent,theconnectiontothedrainisataperedconnectionfor
plastictubing.
MAKING ELECTRICAL CONNECTIONS
TheelectricalwiringbetweenthepowersourceandthefirepumpcontrollershallmeettheNFPA20,
NFPA70NationalElectricalCodeArticle695orC22.1CanadianElectricalCode,Section32-200orany
applicablelocalcodes.Electricalwiringshallbetypicallysizedtocarryatleast125%ofthefullloadcur-
rent(FLCorFLA)ofthefirepumpmotor.
IMPORTANT PRECAUTIONS
Alicensedelectricianmustsupervisetheelectricalconnections.Thedimensiondrawingsshowthearea
suitableforincomingpowerandmotorconnections.Nootherlocationshallbeused.Onlywatertight
hubfittingsshallbeusedwhenenteringthecabinettopreservetheNEMAorIPratingofthecabinet.
The installer is responsible for adequate protection of the Medium Voltage Electric Fire Pump
controller components against metallic debris or drilling chips. Failure to do so may cause
injuries to personnel, damage the controller and subsequently void warranty.
Priortomakinganyfieldconnections
1. Opendoorofenclosureandinspectinternalcomponentsandwiringforanysignsoffrayedor
loosewiresorothervisibledamage.
2. Verifythatthecontrollerinformationiswhatisrequiredontheproject:

V2024.02 10
1. Tornatechcatalognumber
2. Motorelectricalnameplateinformationmatchescontrollerratingforvoltage,frequency,
FLAandHP.
3. Project'selectricalcontractormustsupplyallnecessarywiringforfieldconnectionsinaccordance
withtheNationalElectricalCode,localelectricalcodeandanyotherauthorityhavingjurisdiction.
4. Refertotheappropriatefieldconnectiondrawingforwiringinformation.
PROCEDURE
Allfieldconnections,remotealarmfunctionsandACwiringarebroughtintotheenclosurethroughthe
toporbottomconduitentrancesasindicatedonthedimensionaldrawing.
Donotplaceconduitentrancesonthesidesoftheenclosureunlessaglandplateisprovided.
1. Usingahole(conduit)punch,createaholeintheenclosureforthesizeconduitbeingused.
2. Installnecessaryconduit.
3. Pullallwiresnecessaryforfieldconnections,remotealarmfunctions,ACpowerandallother
optionalfeatures.Bringenoughwireinsidetheenclosuretomakeupconnectionstotheappro-
priateline,loadandcontrolterminalblockpoints.Besuretoconsulttheappropriatefieldcon-
nectiondiagramforconnectionpointsandacceptablewiresize.Forproperwiresizing,referto
theNationalElectricalCode,NFPA70.
4. Makeallfieldconnectionstotheremotealarmfunctionsandanyotheroptionalfeatures.
5. Connectmotortocontrollerloadterminals.
6. FindnameplateonMediumVoltageElectricFirePumpmotorandmakenoteofitsfullloadamp
rating.
7. VerifyAClinevoltage,phaseandfrequencywiththecontrollerdataplateontheenclosuredoor
priortoconnecting.
8. ConnectACpower.
9. Checktoseethatallconnectionsarebothcorrectlywired(inaccordancewiththefieldcon-
nectiondiagram)andtight.
10. Closetheenclosuredoor.
Other manuals for MPA
1
Table of contents
Other Tornatech Controllers manuals

Tornatech
Tornatech VP series Manual

Tornatech
Tornatech GPL Manual

Tornatech
Tornatech GPX Manual

Tornatech
Tornatech HFD Manual

Tornatech
Tornatech VPX Manual

Tornatech
Tornatech VP series Manual

Tornatech
Tornatech GFX Manual

Tornatech
Tornatech JP Manual

Tornatech
Tornatech HFX Manual

Tornatech
Tornatech MPA Manual
Popular Controllers manuals by other brands

Digiplex
Digiplex DGP-848 Programming guide

YASKAWA
YASKAWA SGM series user manual

Sinope
Sinope Calypso RM3500ZB installation guide

Isimet
Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS
LSIS sv-ip5a user manual

Rockwell Automation
Rockwell Automation 1769-L31 installation instructions