Tornatech MPA Manual

V2024.02
INSTALLATION AND MAINTENANCE MANUAL
FOR MEDIUM VOLTAGE ELECTRIC FIRE PUMP
CONTROLLERS MODEL MPA

V2024.02 2
TABLE OF CONTENTS
Important Safety Information 4
Introduction 6
TechnicalData 6
Installation 7
Storage 7
Environment 7
Electromagneticcompatibility(EMC) 7
Handling 7
FCCRegulationsandRadioStandardsSpecification(RSS)Rules 7
Location 8
Mounting 8
Floormounting 8
Wallmounting 8
MakingSystemPressureConnections 9
MakingElectricalConnections 9
ImportantPrecautions 9
Procedure 10
Operator interface 11
Methods of starting and stopping 12
Methodsofstarting 12
Automaticstart 12
Manualstart 12
Remotemanualstart 12
Remoteautomaticstart,delugevalvestart 12
Emergencystart 12
Sequentialstart 12
Teststart 12
Methodsofstopping 12
Manualstop 12

V2024.02 4
IMPORTANT SAFETY INFORMATION
Warning:
This product can expose you to chemicals including DINP, which is known to the State of Cali-
fornia to cause cancer, and DIDP which is known to the State of California to cause birth
defects or other reproductive harm.
Warning:
This product can expose you to chemicals including lead and lead compounds, which are
know to the State of California to cause cancer and birth defects or other reproductive harm.
Formoreinformationgoto:www.P65Warnings.ca.gov
DANGER
RISK OF ELECTROCUTION
PERSONAL INJURY OR DEATH COULD OCCUR.
ENSURE ALL POWER IS DISCONNECTED BEFORE INSTALLING OR SERVICING
THIS EQUIPMENT.

V2024.02 5
DANGER
Do not attempt to install or perform maintenance on equipment while it is energized! Death,
personal injury or substantial property damage may result from contact with energized equip-
ment. Always verify that no voltage is present before proceeding and always follow generally
accepted safety procedures. Controller disconnect switch must be in the “off” position in
order to open the enclosure door. Tornatech cannot be liable for any misapplication or incor-
rect installation of its products.

V2024.02 6
INTRODUCTION
MediumVoltageElectricFirePumpcontrollersaredesignedtostartanelectricmotordrivenfirepump.
Itcaneitherstartthefirepumpmanuallythroughthelocalstartpushbuttonorautomaticallythrough
thesensingofapressuredropinthesprinklersystem.Thefirepumpcontrollerissuppliedwithapres-
suretransducer.Thefirepumpcanbestoppedmanuallywiththelocalstoppushbuttonorauto-
maticallyaftertheexpirationofafieldprogrammabletimer.
TECHNICAL DATA
Rating Value
RatedOperationalCurrentIe AccordingtotheMotor(HP/kW)
RatedOperationalVoltageUe Accordingtothecontrollerratinglabel
RatedOperationalFrequency 50/60Hz
Standardenvironmentaltemperature 4°Cto40°C
Altitude ≤2000m
Relativehumidity 5%to80%
Pollutiondegree 3
ShortCircuitCurrentRatingIcc(SCCR)(A) Accordingtothecontrollerratinglabel
Standarddegreeofprotection NEMAType2
Standbypowerconsumption 10W

V2024.02 7
INSTALLATION
STORAGE
Ifthecontrollerisnotinstalledandenergizedimmediately,Tornatechrecommendsfollowingthe
instructionsinchapter3ofNEMAICS15.
ENVIRONMENT
MediumVoltageElectricFirePumpcontrollersareintendedtobeinstalledinlocationswhereambient
temperaturesarewithin4°Cand40°Candtherelativehumidityiscontrolledbetween5%and80%.
Optionally,thecontrollercanhaveanextendedtemperatureofupto55°Candaslowas-5°C,provided
thatthecontrollerandthepressurewaterpipesareheatedtopreventwaterfreezinganddamagingthe
electronicsandthepipingsystem.
Theyareintendedforpollutiondegree3andshallbeinstalledatanaltitudeofnomorethan2000
meters.Forabnormalinstallationenvironment,consultfactory.
ELECTROMAGNETIC COMPATIBILITY (EMC)
MediumVoltageElectricFirePumpcontrollershavebeentestedforthemoststringentconditionsfor
emissions(EnvironmentB)andimmunity(EnvironmentA),hencecontrollerscanbeinstalledineither
environment.Allcontrollersvariantssharethesameelectronicsandcomplytothosecriteriawithout
requiringadditionalmeasures.
HANDLING
TheweightofeachMediumVoltageElectricFirePumpcontrollerisindicatedonthepackinglabel.Light-
weightcontrollersdonotrequirespecialhandlinginstructions,whileheavycontrollersareequipped
withliftingmeansandshouldbehandledfollowingtheguidelinesspecifiedinTornatech'sdocument
"LargeEnclosureSafeHandlingRequirements_PN12162021".
FCC REGULATIONS AND RADIO STANDARDS SPECIFICATION
(RSS) RULES
TocomplywithFCCandIndustryCanadaRFexposurecompliancerequirements,aseparationdistance
ofatleast20cmmustbemaintainedbetweentheantennaofthisdeviceandallnearbypersons.This
devicemustnotbeco-locatedoroperatinginconjunctionwithanyotherantennaortransmitter.
Thisdevicecontainslicence-exempttransmitter(s)/receiver(s)thatcomplywithInnovation,Scienceand
EconomicDevelopmentCanada’slicence-exemptRSS(s).Operationissubjecttothefollowingtwocon-
ditions:
1. Thisdevicemaynotcauseinterference.
2. Thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesiredoper-
ationofthedevice.
Compliance:CANICES-003(B)/NMB-003(B)

V2024.02 8
Thisdevicecomplieswithpart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:
(1)Thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptanyinterference
received,includinginterferencethatmaycauseundesiredoperation.
Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,
pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainst
harmfulinterferencewhentheequipmentisoperatedinacommercialenvironment.Thisequipment
generates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordance
withtheinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operationofthis
equipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillbe
requiredtocorrecttheinterferenceathisownexpense.
“Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoid
theuser'sauthoritytooperatetheequipment.”
LOCATION
Consult the appropriate job plans to determine the controller mounting location.
Thecontrollershallbelocatedascloseaspracticaltotheengineormotoritcontrolsandshallbewithin
sightoftheengineormotor.Thecontrollershallbelocatedorprotectedsuchthatitwillnotbedam-
agedbywaterescapingfrompumporpumpconnections.Currentcarryingpartsofthecontrollershall
benotlessthan12in.(305mm)abovethefloorlevel.
WorkingclearancesaroundcontrollershallcomplywithNFPA70,NationalElectricalCode,Article110or
C22.1,CanadianElectricalCode,Article26.302oranyapplicablelocalcodes.
ThestandardcontrollerenclosureisratedNEMAType2.Itistheinstaller’sresponsibilitytoinsurethat
eitherthestandardenclosuremeetstheambientconditionsorthatanenclosurewithanappropriate
ratinghasbeenprovided.Controllersmustbeinstalledinsideabuildingandtheyarenotdesignedfor
outsideenvironment.Thepaintcolormaychangeifthecontrollerisexposedtoultravioletraysfora
longperiodoftime.
MOUNTING
TheMediumVoltageElectricFirePumpcontrollershallbemountedinasubstantialmanneronasingle
incombustiblesupportingstructure.
FLOOR MOUNTING
Floormountedcontrollersshallbeattachedtothefloorusingallholesprovidedonthemountingfeet
withhardwaredesignedtosupporttheweightofthecontroller.Themountingfeetprovidetheneces-
sary12in.(305mm)clearanceforcurrentcarryingparts.
WALL MOUNTING
Refer to the controller dimension drawing for necessary mounting dimensions.
Thecontrolleriswallmountedbyusingatleastfour(4)wallanchors,2anchorsforthetopmounting
bracketsand2anchorsforthebottommountingbrackets.Thebracketsaredimensionallyonthesame
centerlineforeaseinmounting.Thereshouldbeaclearanceofatleast6inches(152mm)aroundthe
controllertoallowproperaircirculationaroundtheequipment.

V2024.02 9
1. Usingeitherthedimensionprintorbymeasuringthedistancebetweenthecenterlinesofthe
lowerbracketslots,transcribethisdimensionontothewall.Note:Thebottomedgeoftheenclos-
ureshouldbeaminimumof12”(305mm.)fromthefloorincasefloodingofthepumproom
occurs.
2. Drillandputanchorsintothewallforthelowermountingbrackets.
3. Markonthewall,thelocationoftheholesintheuppermountingbrackets.
4. Drillandputanchorsintowallfortheuppermountingbrackets.
5. Installboltsandwashersinloweranchors.
6. Alignholesinuppermountingbracketsandinstallboltsandwashersinanchors.
7. Shimanchorsasnecessarytoensurerearofenclosureisverticallevelandenclosureisnot
stressed.
8. Tightenallanchorbolts.
9. Checktobesureenclosuredooropenandclosesfreelyandthatenclosureislevel.
MAKING SYSTEM PRESSURE CONNECTIONS
Thecontrollerrequiresone(1)“SystemPressure”connectionfromthesystempipingtotheenclosure.
Theconnectionfitting,1/2”NPTmaleport,isprovidedontheleftexternalsideoftheenclosureforthis
purpose.RefertoNFPA20forcorrectfieldpipingprocedureofthesensinglinebetweenthepumping
systemandthecontroller.Ifadrainispresent,theconnectiontothedrainisataperedconnectionfor
plastictubing.
MAKING ELECTRICAL CONNECTIONS
TheelectricalwiringbetweenthepowersourceandthefirepumpcontrollershallmeettheNFPA20,
NFPA70NationalElectricalCodeArticle695orC22.1CanadianElectricalCode,Section32-200orany
applicablelocalcodes.Electricalwiringshallbetypicallysizedtocarryatleast125%ofthefullloadcur-
rent(FLCorFLA)ofthefirepumpmotor.
IMPORTANT PRECAUTIONS
Alicensedelectricianmustsupervisetheelectricalconnections.Thedimensiondrawingsshowthearea
suitableforincomingpowerandmotorconnections.Nootherlocationshallbeused.Onlywatertight
hubfittingsshallbeusedwhenenteringthecabinettopreservetheNEMAorIPratingofthecabinet.
The installer is responsible for adequate protection of the Medium Voltage Electric Fire Pump
controller components against metallic debris or drilling chips. Failure to do so may cause
injuries to personnel, damage the controller and subsequently void warranty.
Priortomakinganyfieldconnections
1. Opendoorofenclosureandinspectinternalcomponentsandwiringforanysignsoffrayedor
loosewiresorothervisibledamage.
2. Verifythatthecontrollerinformationiswhatisrequiredontheproject:

V2024.02 10
1. Tornatechcatalognumber
2. Motorelectricalnameplateinformationmatchescontrollerratingforvoltage,frequency,
FLAandHP.
3. Project'selectricalcontractormustsupplyallnecessarywiringforfieldconnectionsinaccordance
withtheNationalElectricalCode,localelectricalcodeandanyotherauthorityhavingjurisdiction.
4. Refertotheappropriatefieldconnectiondrawingforwiringinformation.
PROCEDURE
Allfieldconnections,remotealarmfunctionsandACwiringarebroughtintotheenclosurethroughthe
toporbottomconduitentrancesasindicatedonthedimensionaldrawing.
Donotplaceconduitentrancesonthesidesoftheenclosureunlessaglandplateisprovided.
1. Usingahole(conduit)punch,createaholeintheenclosureforthesizeconduitbeingused.
2. Installnecessaryconduit.
3. Pullallwiresnecessaryforfieldconnections,remotealarmfunctions,ACpowerandallother
optionalfeatures.Bringenoughwireinsidetheenclosuretomakeupconnectionstotheappro-
priateline,loadandcontrolterminalblockpoints.Besuretoconsulttheappropriatefieldcon-
nectiondiagramforconnectionpointsandacceptablewiresize.Forproperwiresizing,referto
theNationalElectricalCode,NFPA70.
4. Makeallfieldconnectionstotheremotealarmfunctionsandanyotheroptionalfeatures.
5. Connectmotortocontrollerloadterminals.
6. FindnameplateonMediumVoltageElectricFirePumpmotorandmakenoteofitsfullloadamp
rating.
7. VerifyAClinevoltage,phaseandfrequencywiththecontrollerdataplateontheenclosuredoor
priortoconnecting.
8. ConnectACpower.
9. Checktoseethatallconnectionsarebothcorrectlywired(inaccordancewiththefieldcon-
nectiondiagram)andtight.
10. Closetheenclosuredoor.

V2024.02 11
OPERATOR INTERFACE
A. StatusLED
B. Manualstart
C. Stop
D. Notused
E. Runtest
F. Alarmbuzzer
G. Touchscreendisplay
H. Factoryreserved
I. USBkeyconnectorforlogsdownloadandsoftwareupdates
J. EthernetconnectorforstandardTCP/IPcommunication

V2024.02 12
METHODS OF STARTING AND STOPPING
METHODS OF STARTING
AUTOMATIC START
Thecontrollerwillstartautomaticallyonlowpressuredetectionbythepressuresensorwhenthepres-
suredropsbelowthecut-inthreshold.
MANUAL START
Themotorcanbestartedbypressingthemanualstartpushbutton,regardlessofthesystempressure.
REMOTE MANUAL START
Themotorcanbestartedfromaremotelocationbymomentarilyclosingacontactofamanualpush-
button.
REMOTE AUTOMATIC START, DELUGE VALVE START
Themotorcanbestartedfromaremotelocationbymomentarilyopeningacontactconnectedtoan
automaticdevice.
EMERGENCY START
Themotorcanbestartedmanuallybyusingtheemergencyhandle.Thishandlecanbemaintainedina
closedposition.
Important: to avoid damaging the contactor, it is recommended to start the motor in this
manner:
1. Shutdownthemainpowerbyusingthemaindisconnectmeans,
2. Pulltheemergencystarthandleandlockitinclosedposition,
3. Turnthepowerbackonbyusingthemaindisconnectmeans.
SEQUENTIAL START
Incaseofamultiplepumpapplication,itmaybenecessarytodelaytheautomaticstartingofeach
motortopreventsimultaneousstartingofallmotors.
TEST START
Themotorcanbestartedintestmodemanuallybypressingtheruntestpushbutton,orautomatically
byusingtheperiodictestfeature.
METHODS OF STOPPING
MANUAL STOP
Manualstopisdonebypressingtheprioritystoppushbutton.Notethatpressingthestoppushbutton
willpreventthemotorfromrestartingaslongasthebuttonispressed,plusatwoseconddelay.This
actionhaspriorityoveranyactivedemand,butthemotorwillrestartautomaticallyoncethebuttonis
releasedifthereisany.

V2024.02 13
AUTOMATIC STOP
This function is never activated by default and must be authorized by the authority having
jurisdiction prior to activating.
Automaticstopispossibleonlyafteranautomaticstart.Whenthisfunctionisenabled,themotoris
automaticallystopped10minutesaftertherestorationofthepressuregiventhatnootherruncauseis
present.The10minutesdelayisadjustable.
EMERGENCY STOP
Theemergencystopisalwayspossibleinanystartingconditionandisdonebyusingthemaindis-
connectingmeanslocatedonthedoor.

V2024.02 14
COMMISSIONING
Only an authorized field acceptance provider shall proceed with Medium Voltage Electric Fire
Pump controller commissioning. If you do not have the required training and authorization,
contact factory.
Untilcommissioningiscompleted,thecontrollermainscreenisreplacedbythecommissioningmenu
andtheautomaticmodeisdisabled.
PROCEDURE
Tocommissionthecontroller:
1. SecurethedoorinclosedpositionthenputthecircuitbreakerdisconnectingmeansinONpos-
ition.
2. Loginwithyourpasswordandcompletethefirststartupmenuonthescreen.
3. Forthree-phasemotors,incaseofincorrectrotation,power off the controllerandswaptwo
wiresatthecontactorloadside,thenpowerthecontrollerbackon.
4. Onceallthenecessarystepsarecompletedandthatyouareloggedinwithyourpassword,the
"ServiceDone"buttonwillbecomeonline.
5. Pressthe"ServiceDone"buttononceyouaresatisfiedwiththereadingsandparameters.
6. Downloadthelogstosaveinyourreport.

V2024.02 15
MAINTENANCE
Tornatechcontrollersarecoveredbyalimitedwarrantyandbackedbya10-yearsservicelifeoruntil
supplylast,providedthatproperinstallation,commissioning,useandmaintenanceofthecontrolleris
madeasperthisdocument,NFPA25,andanymaintenancestandardapplicable.
Propercontrollerperformancemustbeassertedatleastonceamonthbyexecutingthefollowing:
1. Withthesystembeingatnominalpressure,ensurethatthepressurereadingiswithintolerances
2. Performateststartsequenceandverifythat
1. Themotorstartswhenthepressurefallsbelowcut-in
2. Therearenoalarms
3. Thereisnonuisancetripping
4. Themotorstartsproperlyandisabletoacceleratewithintheexpectedtime
5. Themotorrotatesintheappropriatedirection
6. Thepumpisabletorisethepressureabovethecut-out
7. Themotorstopswhenthepressureisabovecut-outaftertheconfiguredtestduration
time
Inadditiontotheabove,thefollowingpreventativemaintenancemustbeperformedatleastonceyear:
1. Turnoffthecontroller
2. Doavisualinspectionoftheexteriorofthecontroller
3. Opentheenclosureanddoavisualinspectionoftheinteriorofthecontroller
4. Makesurethatthereisnodustaccumulationinsidethecontroller
5. Inspectthetightnessofeachdeadcable
6. Putthecontrollerbackinservice

V2024.02 16
PATENTS
Country Title Grant NO
CA Mechanicalactivatorforcontactor 2741881
US Mechanicalactivatorforcontactor US8399788B2
CA Mechanicalactivatorforelectricalcontactor 165512
CA Mechanicalactivatorforelectricalcontactor 165514
US Mechanicalactivatorforelectricalcontactor D803794
US Mechanicalactivatorforelectricalcontactor Patentpending
EP Mechanicalactivatorforelectricalcontactor 002955393-0001/2
AE Mechanicalactivatorforelectricalcontactor Patentpending
AE Mechanicalactivatorforelectricalcontactor Patentpending
CA Firepumpdigitaloperator 163254
US Firepumpdigitaloperatorinterface D770313
AE Firepumpdigitaloperatorinterface Patentpending
EP Firepumpdigitaloperatorinterface 002937250-0001
CA Systemandmethodfordetectingfailureinapressure
sensorofafirepumpsystem
Patentpending
US Systemandmethodfordetectingfailureinapressure
sensorofafirepumpsystem
Patentpending

V2024.02 17
AMERICAS
TornatechInc.
HeadOffice
Laval,Quebec,Canada
Tel.:+15143340523
Tollfree:+18003638448
EUROPE
TornatechEuropeSA
Mont-Saint-Gilbert,Belgium