Tornatech GPX Manual

V2024.02
INSTALLATION AND MAINTENANCE MANUAL
FOR ELECTRIC FIRE PUMP CONTROLLERS
MODEL GPX+GPU

V2024.02 2
TABLE OF CONTENTS
Important Safety Information 4
Introduction 6
TechnicalData 6
Installation 7
Storage 7
Seismic 7
Environment 7
Electromagneticcompatibility(EMC) 7
Handling 7
FCCRegulationsandRadioStandardsSpecification(RSS)Rules 7
Location 8
Mounting 8
Floormounting 9
Wallmounting 9
MakingSystemPressureConnections 9
MakingElectricalConnections 9
ImportantPrecautions 10
Procedure 10
Operator interface 12
Methods of starting and stopping 13
Methodsofstarting 13
Automaticstart 13
Manualstart 13
Remotemanualstart 13
Remoteautomaticstart,delugevalvestart 13
Emergencystart 13
Sequentialstart 13
Teststart 13
Methodsofstopping 13

V2024.02 4
IMPORTANT SAFETY INFORMATION
Warning:
This product can expose you to chemicals including DINP, which is known to the State of Cali-
fornia to cause cancer, and DIDP which is known to the State of California to cause birth
defects or other reproductive harm.
Warning:
This product can expose you to chemicals including lead and lead compounds, which are
know to the State of California to cause cancer and birth defects or other reproductive harm.
Formoreinformationgoto:www.P65Warnings.ca.gov
DANGER
RISK OF ELECTROCUTION
PERSONAL INJURY OR DEATH COULD OCCUR.
ENSURE ALL POWER IS DISCONNECTED BEFORE INSTALLING OR SERVICING
THIS EQUIPMENT.

V2024.02 5
DANGER
Do not attempt to install or perform maintenance on equipment while it is energized! Death,
personal injury or substantial property damage may result from contact with energized equip-
ment. Always verify that no voltage is present before proceeding and always follow generally
accepted safety procedures. Controller disconnect switch must be in the “off” position in
order to open the enclosure door. Tornatech cannot be liable for any misapplication or incor-
rect installation of its products.

V2024.02 6
INTRODUCTION
ElectricFirePumpcontrollersaredesignedtostartanelectricmotordrivenfirepump.Itcaneitherstart
thefirepumpmanuallythroughthelocalstartpushbuttonorautomaticallythroughthesensingofa
pressuredropinthesprinklersystem.Thefirepumpcontrollerissuppliedwithapressuretransducer.
Thefirepumpcanbestoppedmanuallywiththelocalstoppushbuttonorautomaticallyaftertheexpir-
ationofafieldprogrammabletimer.
Itisequippedwithanautomatictransferswitchthatfeedsthecontrollerfromeitherthenormalorthe
alternatepowersource.
TECHNICAL DATA
Rating Value
RatedOperationalCurrentIe AccordingtotheMotor(HP/kW)
RatedOperationalVoltageUe Accordingtothecontrollerratinglabel
RatedOperationalFrequency 50/60Hz
Standardenvironmentaltemperature 4°Cto40°C
Altitude ≤2000m
Relativehumidity 5%to80%
Pollutiondegree 3
ShortCircuitCurrentRatingIcc(SCCR)(A) Accordingtothecontrollerratinglabel
Standarddegreeofprotection NEMAType2
Standbypowerconsumption 13W

V2024.02 7
INSTALLATION
STORAGE
Ifthecontrollerisnotinstalledandenergizedimmediately,Tornatechrecommendsfollowingthe
instructionsinchapter3ofNEMAICS15.
SEISMIC
ElectricFirePumpcontrollersareoptionallyseismicapprovedandhasbeentestedinaccordancewith
theICC-ESAC156,IBC2015&CBC2013standards.Properinstallation,anchoringandmountingis
requiredtovalidatethiscompliancereport.Refertothismanualanddrawingstodeterminetheseismic
mountingrequirementsandlocationofthecenterofgravity(youmayneedtocontactfactory).The
equipmentmanufacturerisnotresponsibleforthespecificationandperformanceofanchoragesys-
tems.Thestructuralengineerofrecordontheprojectshallberesponsibleforanchoragedetails.The
equipmentinstallationcontractorshallberesponsibleforensuringtherequirementsspecifiedbythe
structuralengineerofrecordaresatisfied.Ifdetailedseismicinstallationcalculationsarerequired,
pleasecontactthemanufacturerfortheperformanceofthiswork.
ENVIRONMENT
ElectricFirePumpcontrollersareintendedtobeinstalledinlocationswhereambienttemperaturesare
within4°Cand40°Candtherelativehumidityiscontrolledbetween5%and80%.Optionally,thecon-
trollercanhaveanextendedtemperatureofupto55°Candaslowas-5°C,providedthatthecontroller
andthepressurewaterpipesareheatedtopreventwaterfreezinganddamagingtheelectronicsand
thepipingsystem.
Theyareintendedforpollutiondegree3andshallbeinstalledatanaltitudeofnomorethan2000
meters.Forabnormalinstallationenvironment,consultfactory.
ELECTROMAGNETIC COMPATIBILITY (EMC)
ElectricFirePumpcontrollershavebeentestedforthemoststringentconditionsforemissions(Envir-
onmentB)andimmunity(EnvironmentA),hencecontrollerscanbeinstalledineitherenvironment.All
controllersvariantssharethesameelectronicsandcomplytothosecriteriawithoutrequiringadditional
measures.
HANDLING
TheweightofeachElectricFirePumpcontrollerisindicatedonthepackinglabel.Lightweightcon-
trollersdonotrequirespecialhandlinginstructions,whileheavycontrollersareequippedwithlifting
meansandshouldbehandledfollowingtheguidelinesspecifiedinTornatech'sdocument"LargeEnclos-
ureSafeHandlingRequirements_PN12162021".
FCC REGULATIONS AND RADIO STANDARDS SPECIFICATION
(RSS) RULES
TocomplywithFCCandIndustryCanadaRFexposurecompliancerequirements,aseparationdistance
ofatleast20cmmustbemaintainedbetweentheantennaofthisdeviceandallnearbypersons.This

V2024.02 8
devicemustnotbeco-locatedoroperatinginconjunctionwithanyotherantennaortransmitter.
Thisdevicecontainslicence-exempttransmitter(s)/receiver(s)thatcomplywithInnovation,Scienceand
EconomicDevelopmentCanada’slicence-exemptRSS(s).Operationissubjecttothefollowingtwocon-
ditions:
1. Thisdevicemaynotcauseinterference.
2. Thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesiredoper-
ationofthedevice.
Compliance:CANICES-003(B)/NMB-003(B)
Thisdevicecomplieswithpart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:
(1)Thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptanyinterference
received,includinginterferencethatmaycauseundesiredoperation.
Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,
pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainst
harmfulinterferencewhentheequipmentisoperatedinacommercialenvironment.Thisequipment
generates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordance
withtheinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operationofthis
equipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillbe
requiredtocorrecttheinterferenceathisownexpense.
“Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoid
theuser'sauthoritytooperatetheequipment.”
LOCATION
Consult the appropriate job plans to determine the controller mounting location.
Thecontrollershallbelocatedascloseaspracticaltotheengineormotoritcontrolsandshallbewithin
sightoftheengineormotor.Thecontrollershallbelocatedorprotectedsuchthatitwillnotbedam-
agedbywaterescapingfrompumporpumpconnections.Currentcarryingpartsofthecontrollershall
benotlessthan12in.(305mm)abovethefloorlevel.
WorkingclearancesaroundcontrollershallcomplywithNFPA70,NationalElectricalCode,Article110or
C22.1,CanadianElectricalCode,Article26.302oranyapplicablelocalcodes.
ThestandardcontrollerenclosureisratedNEMAType2.Itistheinstaller’sresponsibilitytoinsurethat
eitherthestandardenclosuremeetstheambientconditionsorthatanenclosurewithanappropriate
ratinghasbeenprovided.Controllersmustbeinstalledinsideabuildingandtheyarenotdesignedfor
outsideenvironment.Thepaintcolormaychangeifthecontrollerisexposedtoultravioletraysfora
longperiodoftime.
MOUNTING
TheElectricFirePumpcontrollershallbemountedinasubstantialmanneronasingleincombustible
supportingstructure.

V2024.02 9
FLOOR MOUNTING
Floormountedcontrollersshallbeattachedtothefloorusingallholesprovidedonthemountingfeet
withhardwaredesignedtosupporttheweightofthecontroller.Themountingfeetprovidetheneces-
sary12in.(305mm)clearanceforcurrentcarryingparts.
WALL MOUNTING
Refer to the controller dimension drawing for necessary mounting dimensions.
Thecontrolleriswallmountedbyusingatleastfour(4)wallanchors,2anchorsforthetopmounting
bracketsand2anchorsforthebottommountingbrackets.Thebracketsaredimensionallyonthesame
centerlineforeaseinmounting.Thereshouldbeaclearanceofatleast6inches(152mm)aroundthe
controllertoallowproperaircirculationaroundtheequipment.
1. Usingeitherthedimensionprintorbymeasuringthedistancebetweenthecenterlinesofthe
lowerbracketslots,transcribethisdimensionontothewall.Note:Thebottomedgeoftheenclos-
ureshouldbeaminimumof12”(305mm.)fromthefloorincasefloodingofthepumproom
occurs.
2. Drillandputanchorsintothewallforthelowermountingbrackets.
3. Markonthewall,thelocationoftheholesintheuppermountingbrackets.
4. Drillandputanchorsintowallfortheuppermountingbrackets.
5. Installboltsandwashersinloweranchors.
6. Alignholesinuppermountingbracketsandinstallboltsandwashersinanchors.
7. Shimanchorsasnecessarytoensurerearofenclosureisverticallevelandenclosureisnot
stressed.
8. Tightenallanchorbolts.
9. Checktobesureenclosuredooropenandclosesfreelyandthatenclosureislevel.
MAKING SYSTEM PRESSURE CONNECTIONS
Thecontrollerrequiresone(1)“SystemPressure”connectionfromthesystempipingtotheenclosure.
Theconnectionfitting,1/2”NPTmaleport,isprovidedontheleftexternalsideoftheenclosureforthis
purpose.RefertoNFPA20forcorrectfieldpipingprocedureofthesensinglinebetweenthepumping
systemandthecontroller.Ifadrainispresent,theconnectiontothedrainisataperedconnectionfor
plastictubing.
MAKING ELECTRICAL CONNECTIONS
TheelectricalwiringbetweenthepowersourceandthefirepumpcontrollershallmeettheNFPA20,
NFPA70NationalElectricalCodeArticle695orC22.1CanadianElectricalCode,Section32-200orany
applicablelocalcodes.Electricalwiringshallbetypicallysizedtocarryatleast125%ofthefullloadcur-
rent(FLCorFLA)ofthefirepumpmotor.

V2024.02 10
IMPORTANT PRECAUTIONS
Alicensedelectricianmustsupervisetheelectricalconnections.Thedimensiondrawingsshowthearea
suitableforincomingpowerandmotorconnections.Nootherlocationshallbeused.Onlywatertight
hubfittingsshallbeusedwhenenteringthecabinettopreservetheNEMAorIPratingofthecabinet.
The installer is responsible for adequate protection of the Electric Fire Pump controller com-
ponents against metallic debris or drilling chips. Failure to do so may cause injuries to per-
sonnel, damage the controller and subsequently void warranty.
Priortomakinganyfieldconnections
1. Opendoorofenclosureandinspectinternalcomponentsandwiringforanysignsoffrayedor
loosewiresorothervisibledamage.
2. Verifythatthecontrollerinformationiswhatisrequiredontheproject:
1. Tornatechcatalognumber
2. Motorelectricalnameplateinformationmatchescontrollerratingforvoltage,frequency,
FLAandHP.
3. Project'selectricalcontractormustsupplyallnecessarywiringforfieldconnectionsinaccordance
withtheNationalElectricalCode,localelectricalcodeandanyotherauthorityhavingjurisdiction.
4. Refertotheappropriatefieldconnectiondrawingforwiringinformation.
PROCEDURE
Allfieldconnections,remotealarmfunctionsandACwiringarebroughtintotheenclosurethroughthe
toporbottomconduitentrancesasindicatedonthedimensionaldrawing.
Donotplaceconduitentrancesonthesidesoftheenclosureunlessaglandplateisprovided.
1. Usingahole(conduit)punch,createaholeintheenclosureforthesizeconduitbeingused.
2. Installnecessaryconduit.
3. Pullallwiresnecessaryforfieldconnections,remotealarmfunctions,ACpowerandallother
optionalfeatures.Bringenoughwireinsidetheenclosuretomakeupconnectionstotheappro-
priateline,loadandcontrolterminalblockpoints.Besuretoconsulttheappropriatefieldcon-
nectiondiagramforconnectionpointsandacceptablewiresize.Forproperwiresizing,referto
theNationalElectricalCode,NFPA70.
4. Makeallfieldconnectionstotheremotealarmfunctionsandanyotheroptionalfeatures.
5. Connectmotortocontrollerloadterminals.
6. FindnameplateonElectricFirePumpmotorandmakenoteofitsfullloadamprating.
7. VerifyAClinevoltage,phaseandfrequencywiththecontrollerdataplateontheenclosuredoor
priortoconnecting.
8. ConnectACpower.
Other manuals for GPX
2
This manual suits for next models
1
Table of contents
Other Tornatech Controllers manuals

Tornatech
Tornatech GPL Manual

Tornatech
Tornatech MPA Manual

Tornatech
Tornatech GFD Manual

Tornatech
Tornatech VP series Manual

Tornatech
Tornatech HFX Manual

Tornatech
Tornatech GPX Manual

Tornatech
Tornatech GPL Manual

Tornatech
Tornatech GFX Manual

Tornatech
Tornatech VP series Manual

Tornatech
Tornatech VPX Manual
Popular Controllers manuals by other brands

Digiplex
Digiplex DGP-848 Programming guide

YASKAWA
YASKAWA SGM series user manual

Sinope
Sinope Calypso RM3500ZB installation guide

Isimet
Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS
LSIS sv-ip5a user manual

Rockwell Automation
Rockwell Automation 1769-L31 installation instructions