–19–
Error codes and parts to be checked
Wiredremote
controller
display Main defective parts Judging
device Parts to be checked / error description Air
conditioner
status
Indication
E01 No header remote controller Remote
controller
Incorrect remote controller setting --- The header remote
controller has not been set (including two remote controllers). *
Remote controller
communication error No signal can be received from the indoor unit.
E02 Remote controller
transmission error Remote
controller System interconnection wires, indoor P.C. board, remote
controller
--- No signal can be sent to the indoor unit. *
E03 Indoor unit-remote controller
regular communication error Indoor Remote controller, network adapter, indoor P.C. board --- No
data is received from the remote controller or network
adapter. Auto-reset
E04
Indoor unit-outdoor unit
serial communication error Indoor System interconnection wires, indoor P.C. board, outdoor
P.C. board --- Serial communication errorbetween indoor unit
and outdoor unit Auto-reset
IPDU-CDB communication
error
E08 Duplicated indoor addresses Indoor Indoor address setting error --- The same address as the self-
address was detected. Auto-reset
E09 Duplicated header remote
controllers Remote
controller
Remote controller address setting error --- Two remote
controllers are set as header in the double-remote controller
control. *
(* The header indoor unit stops raising alarm and follower
indoor units continue to operate.)
E10 CPU-CPU communication
error Indoor Indoor P.C. board --- Communication error between main
MCU and motor microcomputer MCU Auto-reset
E18 Header indoor unit-indoor
follower unit regular
communication error Indoor Indoor P.C. board --- Regular communication is not possible
between header and follower indoor units or between twin
header (main) and follower (sub) units. Auto-reset
E31 IPDU communication error Outdoor Communication error between IPDU and CDB Entire stop
F01 Indoor unit heat exchanger
sensor (TCJ) error Indoor Heat exchanger sensor (TCJ), indoor P.C. board --- Open-
circuit or short-circuit of the heat exchanger sensor (TCJ) was
detected. Auto-reset
F02 Indoor unit heat exchanger
sensor (TC) error Indoor Heat exchanger sensor (TC), indoor P.C. board --- Open-
circuit or short-circuit of the heat exchanger sensor (TC) was
detected. Auto-reset
F04 Outdoorunitdischargetemp.
sensor (TD) error Outdoor Outdoor temp. sensor (TD), outdoor P.C. board --- Open-
circuit or short-circuit of the discharge temp. sensor was
detected. Entire stop
F06 Outdoor unit temp. sensor
(TE / TS) error Outdoor Outdoor temp. sensors (TE / TS), outdoor P.C. board ---
Open-circuit or short-circuit of the heat exchanger temp.
sensor was detected. Entire stop
F07 TL sensor error Outdoor TL sensor may be displaced, disconnected or short-circuited. Entire stop
F08 Outdoor unit outside air
temp. sensor error Outdoor Outdoor temp. sensor (TO), outdoor P.C. board --- Open-
circuit or short-circuit of the outdoor air temp. sensor was
detected. Operation
continued
F10 Indoor unit room temp.
sensor (TA) error Indoor Room temp. sensor (TA), indoor P.C. board --- Open-circuit or
short-circuit of the room temp. sensor (TA) was detected. Auto-reset
F12 TS (1) sensor error Outdoor TS (1) sensor may be displaced, disconnected or short-
circuited. Entire stop
F13 Heat sink sensor error Outdoor Abnormal temperature was detected by the temp. sensor of
the IGBT heat sink. Entire stop
F15 Temp. sensor connection
error Outdoor Temp. sensor (TE / TS) may be connected incorrectly. Entire stop
F29 Indoor unit, other P.C. board
error Indoor Indoor P.C. board --- EEPROM error Auto-reset
F31 Outdoor unit P.C. board Outdoor Outdoor P.C. board ---- In the case of EEPROM error. Entire stop
H01 Outdoor unit compressor
breakdown Outdoor Current detect circuit, power voltage --- Minimum frequency
was reached in the current releasing control or short-circuit
current (Idc) after direct excitation was detected Entire stop
H02 Outdoor unit compressor
lock Outdoor Compressor circuit --- Compressor lock was detected. Entire stop
H03 Outdoor unit current detect
circuit error Outdoor Current detect circuit, outdoor unit P.C. board --- Abnormal
current was detected in AC-CT or a phase loss was detected. Entire stop
H04 Case thermostat operation
(1) Outdoor Malfunction of the case thermostat Entire stop
H06 Outdoor unit low-pressure
system error Outdoor Current, high-pressure switch circuit, outdoor P.C. board ---
Ps pressure sensor error was detected or low-pressure
protective operation was activated. Entire stop
L03 Duplicated header indoor
units Indoor Indoor address setting error --- There are two or more header
units in the group. Entire stop
L07 Group line in individual
indoor unit Indoor Indoor address setting error --- There is at least one group-
connected indoor unit among individual indoor units. Entire stop
L08 Indoor group address not set Indoor Indoor address setting error --- Indoor address group has not
been set. Entire stop
L09 Indoor power level not set Indoor Indoor power level has not been set. Entire stop
L10 Outdoor unit P.C. board Outdoor In the case of outdoor P.C. board jumper wire (for service)
setting error Entire stop
L20 LAN communication error Network
adapter
central control
Address setting, central control remote controller, network
adapter --- Duplication of address in central control
communication Auto-reset
L29 Other outdoor unit error Outdoor
Other outdoor unit error Entire stop
1) Communication error between IPDU MCU and CDB MCU Entire stop
2) Abnormal temperature was detected by the heat sink temp.
sensor in IGBT.
L30 Abnormal external input into
indoor unit (interlock) Indoor External devices, outdoor unit P.C. board --- Abnormal stop
due to incorrect external input into CN80 Entire stop
L31 Phase sequence error, etc. Outdoor Power supply phase sequence, outdoor unit P.C. board ---
Abnormal phase sequence of the 3-phase power supply
Operation
continued
(thermostat
OFF)
P01 Indoor unit fan error Indoor Indoor fan motor, indoor P.C. board --- Indoor AC fan error
(fan motor thermal relay activated) was detected. Entire stop
P03 Outdoorunitdischargetemp.
error Outdoor An error was detected in the discharge temp. releasing
control. Entire stop
P04 Outdoor unit high-pressure
system error Outdoor High-pressure switch --- The IOL was activated or an error
was detected in the high-pressure releasing control using the
TE. Entire stop
P05 Open phase detected Outdoor The power supply wire may be connected incorrectly. Check
open phase and voltages of the power supply. Entire stop
P07 Heat sink overheat Outdoor Abnormal temperature was detected by the temp. sensor of
the IGBT heat sink. Entire stop
P10 Indoor unit water overflow
detected Indoor Drain pipe, clogging of drainage, float switch circuit, indoor
P.C. board --- Drainage is out of order or the float switch was
activated. Entire stop
P15 Gas leakage detected Outdoor There may be gas leakage from the pipe or connecting part.
Check for gas leakage. Entire stop
P19 4-way valve error Outdoor
(Indoor) 4-way valve, indoor temp. sensors (TC / TCJ) --- An error was
detected due to temperature drop of the indoor unit heat
exchanger sensor when heating. Auto-reset
(Auto-reset)
P20 High-pressure protective
operation Outdoor High-pressure protection Entire stop
P22 Outdoor unit fan error Outdoor Outdoor unit fan motor, outdoor unit P.C. board --- An error
(overcurrent, locking, etc.) was detected in the outdoor unit
fan drive circuit. Entire stop
P26 Outdoor unit inverter Idc
activated Outdoor IGBT, outdoor unit P.C. board, inverter wiring, compressor---
Short-circuit protection for compressor drive circuit devices
(G-Tr / IGBT) was activated. Entire stop
P29 Outdoor unit position error Outdoor Outdoor unit P.C. board, high-pressure switch --- Compressor
motor position error was detected. Entire stop
Wiredremote
controller
display Main defective parts Judging
device Parts to be checked / error description Air
conditioner
status
Indication
37-EN 38-EN