TPI 1008 User manual

Test Products International, Inc.
9615 SW Allen Blvd., Ste. 104
Beaverton, OR 97005
Tel: 503-520-9197 Fax: 503-520-1225
www.tpi-thevalueleader.com
Test Products International, Ltd.
342 Bronte Road South, Unit #9
Milton Ontario Canada L9T5B7
Tel: 905-693-8558 Fax: 905-693-0888
1008
Rev. 2.x Meters
Indoor Air Quality Meter
The Value LeaderTM
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Contents
1. Introduction
2. General Overview
3. Familiarization
3.1 Front View
3.2 Soft Keys
3.3 Back View
4. Operation
4.1 Turning On & Off / Performing a Test / Main Display
4.2 Selecting Temperature Units
4.3 Min / Max Mode
4.4 Activating the Backlight
4.5 Setting CO2 Alarm Level
5. Data Logging
6. Retrieving Logged Data
7. Technical Specifications
8. Maintenance
8.1 Battery Replacement
8.2 Service
9. Technical Information
10. Error Codes & Troubleshooting
Notes:
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

Notes:
1. Introduction
Thank you for purchasing TPI brand products. The TPI 1008 Indoor Air
Quality (IAQ) Meter is a state of the art, easy to use tester designed to
provide you with the necessary measurements to monitor and make
adjustments to air handling devices. The instrument is ruggedly con-
structed and comes with a 3 Year unit and 2 Year sensor Guarantee.
2. General Overview
The 1008 IAQ meter uses state of the art sensors to measure carbon
dioxide (CO2), and temperature. The CO2 sensor in your meter will
need to be replaced periodically and calibration is recommended once
every year.
You should keep battery power applied to your sensors at all times.
The following guidelines will help prevent damage to your sensors:
Always store your unit in a place where the temperature does not get
down to or below freezing.
Always maintain battery power to the sensors. When the batteries get
low replace them as soon as possible.
Never allow foreign objects or material to enter the sensor holes, dam-
age to the sensor may result.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

General Overview (Continued)
This manual will guide you through the functions of the TPI 1008
which will give you many years of reliable service.
Your TPI 1008 Indoor Air Quality meter comes complete with the
following standard accessories:
• TPI 1008 Instrument
• Protective Rubber Boot (A800)
• Soft Carrying Case (A921)
• USB Cable & Software (A803)
• Instruction Manual
Your TPI 1008 Indoor Air Quality meter has the following optional
accessories available:
• Power adapter / Battery eliminator (A804)
• Magnetic strap kit to hang meter (A127)
• Boot hook to hang meter (A103)
• Replacement Software only (A802)
• Replacement USB cable only (A801)
( ) Denotes part number
Notes:
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

10. Error Codes & Troubleshooting
CO2 Sensor Error
If the CO2 sensor fails to initialize or is faulty the
1008 will display an error code. Try turning the 1008
off and on again. If it displays the error code again
the 1008 is in need of service. Please return your
instrument to TPI. See section 9.2 for instructions on
returning your meter.
Temperature Sensor Error
If the temperature sensor fails to initialize or is faulty
the 1008 will display an error code. Try turning the
1008 off and on again. If it displays the error code
again the 1008 is in need of service. Please return
your instrument to TPI. See section 9.2 for instruc-
tions on returning your meter.
3. Familiarization
3.1 Front View
Sensor Locations: Places where the CO and Temperature sensors
are located and protected.
Display : Large 2 Parameter Backlit LCD Display.
Protective Rubber Boot Provides protection to meter housing and sensors.
Keypad Selects all available functions
USB Port Location for connection of USB cable for PC com
munication.
Power Adapter Socket Location to connect power adapter.
Display
Keypad
CO2 &
Temperature
Sensor Location
USB Port Power Adapter
Socket
Protective
Rubber Boot
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

3.2 Soft Keys
On / Off key - Used to turn the IAQ meter on or off. Press to turn
on, press and hold to turn off.
Up Arrow key - Used to select and change parameters.
Down Arrow key - Used to select and change parameters.
Mode key - Used to switch between Celsius and Fahrenheit units
of display and to enter CO2 alarm level input mode. Press to
switch between Celsius and Fahrenheit units. Press and hold to
enter and exit CO2 alarm level mode.
Backlight key - Used to turn the display backlight on and off.
Min / Max key - Used to activate and cycle through minimum,
maximum, and average display modes. Press to activate Min/Max
mode, press repeatedly to cycle through min, max, and avg dis-
plays. Press and hold to deactivate Min/Max mode.
Log key - Used activate and deactivate data logging.
RCL Key - Used to recall (display) logged data.
9. Technical Information
Recommended Levels by Agency
Parameter IDPH1ASHRAE2OSHA PEL3ACGIH TLV4
Humidity 20% - 60% 30% - 60% N/A N/A
Temperature 68 - 75 (winter)
73 - 79 (summer) 68 - 75 (winter)
73 - 79 (summer) N/A N/A
Carbon Dioxide 1,000ppm
(<800ppm preferred) 1,000ppm 5,000ppm 5,000ppm
Carbon Monoxide 9ppm 9ppm 50ppm 25ppm
N/A-Not Applicable or Not Established
1Illinois Department of Public Health (2009)
2American Society of Heating, Refrigerating and Air Conditioning Engineers
3Occupational Safety and Health Administration Permissible Exposure Limit -- this level
is a time-weighted average and is an enforceable standard that must not be exceeded
during any eight-hour work shift of a 40-hour work week.
4American Conference of Governmental Industrial Hygienist Threshold Limit Value -- this
level is a recommended time-weighted average upper limit exposure concentration for a
normal eight to 10-hour workday and a 40-hour work week.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

8. Maintenance
It is recommended that the instrument be calibrated every 12 months.
Please consult Test Products International for further details (800) 368-5719.
8.1 Battery Replacement
When the batteries become low they will require replacement.
1. Turn the meter over so the back is facing you.
2. Loosen the screw holding down the battery cover located under the tilt
stand.
3. Lift the tilt stand up and remove the battery cover.
4. Replace the batteries (3 x AA Alkaline) and install the cover and tighten the
screw.
8.2 Service
To obtain warranty and non-warranty performance or maintenance on your
analyzer: - Include with the product your name, address, phone number, writ-
ten description of the problem and proof of purchase date. Carefully package
and return to:
TPI / Attn. Repair
9615 SW Allen Blvd. Suite 104
Beaverton, OR 97005
3.3 Back View
Tilt Stand
Battery Cover Screw
Hanger Hole
Hanger Hole: Use to hang instrument for hands free operation. Can
be used with A127 magnetic strap kit or A103 hook.
Tilt Stand: Use to stand instrument on a table.
Batter Cover Loosen this screw and open cover to access batteries.
Screw:
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

4. Operation
4.1 Turning On & Off / Performing a Test / Main Display
Enter the area to be tested, the measured values will be displayed.
Carbon dioxide (CO2) in parts per million (ppm) is displayed at the top and
Temperature in °F or °C (selectable)is displayed at the bottom of the main
display.
The battery indicator is located at the left center of the display. When the bat-
teries become low they must be replaced to maintain proper operation.
The 1008 has a CO2 alarm. If the CO2 level measured is at or above the
set alarm level the 1008 will beep and the display will flash red as a
warning. This alarm point is adjustable. Additional functions can be acti-
vated during testing. Please see next sections.
Carbon dioxide (CO2)
Temperature
Battery indicator
Press the key and the 1008 will begin a 30 second countdown. During
this time the 1008 performs a self diagnostic. Once the countdown ends the
1008 will display CO2 and Temperature.
To turn the 1008 off, press and hold the key down until the 1008 turns off.
7. Technical Specifications
Function Range Accuracy
CO2 0 to 5000ppm 50°F~104°F: ±3% of rdg+75ppm
<50°F, >104°F: ±5% of rdg+75ppm
Temperature -5°F to 140°F ±2°F
-20°C to 60°C ±1°C
Data Logging: Up to 50 samples 1 minute to 60 minutes in 1, 2, 3, 5, 10, 20, 30,
40, 50, 60 minute intervals
Display Type: 2 line with annunciators and backlight
CO2 Alarm: Audible and visual, selectable level (factory default off)
Operating Temperature & Humidity
CO and CO2: 14°F to 122°F (-10°C to 50°C)
All Other Function: -4°F to 140°F (-20°C to 60°C)
Humidity 15 ~ 95% non-condensing
Storage Temperature: -4°F to 140°F (-20°C to 60°C)
Power supply
3 AA battery( 4.5V)
AC/DC adapter 5Vout (Center positive)
Battery Life: 40 hours typical without backlight
Output: Serial output via USB connection
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

6. Retrieving Logged Data
Logged data can be displayed on the 1008 display or sent to a PC by using the
USB cable and software included. The PC software also provides the capability of
real time monitoring from a PC.
Recalling and Displaying Logged Data
Retrieving Logged Data via PC
To retrieve logged data the USB cable and PC software (both supplied) must be
used.
Install the PC software on your PC and open it.
Connect the 1008 to the PC using the USB cable.
Run the software and select 1008 when prompted. Click on the connect to PC
button in the software window.
The software can be used to retrieve logged data and for real time monitoring.
COM port setting is:
Baud rate: 19200
Parity: None
Data Bits: 8
Stop Bit: 1
1) Press the key, “LOG 01” and the logged CO2 and temperature reading
will alternately flash. Press the to cycle through all of the logged
data.
2) To deactivate recall mode and return to normal operation, press the
key.
4.2 Selecting Temperature Units
4.3 Min / Max Mode
4.4 Activating the Backlight
Pressing the key activates Min/Max mode and “Max Min” will be displayed.
In this mode the 1008 will keep track of the minimum, maximum, and average
CO2 and Temperature being measured. When “Min Max” is displayed the 1008
will display the real time reading.
Pressing the key switches the temperature display between °F and °C.
To deactivate Min/Max mode and return to normal operation, Press and hold the
key until the 1008 beeps.
Pressing the key turns the display backlight on and off. Power
consumption is much higher when the backlight is activated. The backlight
will automatically turn off 30 seconds after it is activated. To conserve bat-
tery life the backlight should only be used when necessary.
Pressing the key will cause the 1008 to display “MAX”. This indicates the
Maximum CO2 and Temperature measured is displayed.
Press the key again and the 1008 will display “MIN”. This indicates the
Minimum CO2 and Temperature measured is displayed.
Press the key again and the 1008 will display “AVG”. This indicates the
Average CO2 and Temperature measured is displayed.
Pressing the key will cause the 1008 to display “MAX MIN”. This indicates
the real time reading is displayed and the Min/Max mode is still active. The steps
above can be repeated to cycle through the Min, Max, and Avg displays.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

The 1008 is equipped with an audible and visual alarm for carbon dioxide. The
alarm level is factory set to off. When CO2 above the alarm level is measured, the
1008 will beep and the display will flash red.
The alarm level is adjustable and can be set from 1100ppm to 5000ppm in
100ppm increments.
Using the Arrow keys set the alarm point to the desired level. The
keys adjust the alarm level from “Off” to 5000ppm in 100ppm increments.
Once the desired alarm point is set, press and hold the key to return to
normal operation.
1) With the 1008 turned on, press and hold down the
CO2 alarm level in ppm
4.5 Setting CO2 Alarm Level
key until the CO2
alarm screen is displayed.
5. Data Logging
To activate data logging press the key until the logging time setup
screen is displayed. Once the logging function is activated all previously logged
data is written over.
1) The log time interval is displayed in minutes at the bottom of the display.
The logging interval tells the 1008 how often to sample. For example, a logging
interval of 1 minute (01) means the 1008 will log a reading every minute. A log-
ging interval of 10 minutes (10) means the 1008 will log a reading every 10 min-
utes. The log interval time is adjustable from 1 minute to 60 minutes in the fol-
lowing increments: 1, 2, 3, 5, 10, 20, 30, 40, 50, 60 minutes. A maximum of 50
readings can be logged.
2) Use the
3) Once the logging interval is set press the key and the 1008 will return to
the main display and “LOG” will flash indicating the logging function is active. The
1008 will beep each time a reading has been logged.
4) To deactivate data logging press the key and “LOG” will no longer flash.
For data retrieval please see the next section on how to retrieve logged data.
Log time interval in
minutes.
keys to increase or decrease the log interval time.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

The 1008 is equipped with an audible and visual alarm for carbon dioxide. The
alarm level is factory set to off. When CO2 above the alarm level is measured, the
1008 will beep and the display will flash red.
The alarm level is adjustable and can be set from 1100ppm to 5000ppm in
100ppm increments.
Using the Arrow keys set the alarm point to the desired level. The
keys adjust the alarm level from “Off” to 5000ppm in 100ppm increments.
Once the desired alarm point is set, press and hold the key to return to
normal operation.
1) With the 1008 turned on, press and hold down the
CO2 alarm level in ppm
4.5 Setting CO2 Alarm Level
key until the CO2
alarm screen is displayed.
5. Data Logging
To activate data logging press the key until the logging time setup
screen is displayed. Once the logging function is activated all previously logged
data is written over.
1) The log time interval is displayed in minutes at the bottom of the display.
The logging interval tells the 1008 how often to sample. For example, a logging
interval of 1 minute (01) means the 1008 will log a reading every minute. A log-
ging interval of 10 minutes (10) means the 1008 will log a reading every 10 min-
utes. The log interval time is adjustable from 1 minute to 60 minutes in the fol-
lowing increments: 1, 2, 3, 5, 10, 20, 30, 40, 50, 60 minutes. A maximum of 50
readings can be logged.
2) Use the
3) Once the logging interval is set press the key and the 1008 will return to
the main display and “LOG” will flash indicating the logging function is active. The
1008 will beep each time a reading has been logged.
4) To deactivate data logging press the key and “LOG” will no longer flash.
For data retrieval please see the next section on how to retrieve logged data.
Log time interval in
minutes.
keys to increase or decrease the log interval time.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

6. Retrieving Logged Data
Logged data can be displayed on the 1008 display or sent to a PC by using the
USB cable and software included. The PC software also provides the capability of
real time monitoring from a PC.
Recalling and Displaying Logged Data
Retrieving Logged Data via PC
To retrieve logged data the USB cable and PC software (both supplied) must be
used.
Install the PC software on your PC and open it.
Connect the 1008 to the PC using the USB cable.
Run the software and select 1008 when prompted. Click on the connect to PC
button in the software window.
The software can be used to retrieve logged data and for real time monitoring.
COM port setting is:
Baud rate: 19200
Parity: None
Data Bits: 8
Stop Bit: 1
1) Press the key, “LOG 01” and the logged CO2 and temperature reading
will alternately flash. Press the to cycle through all of the logged
data.
2) To deactivate recall mode and return to normal operation, press the
key.
4.2 Selecting Temperature Units
4.3 Min / Max Mode
4.4 Activating the Backlight
Pressing the key activates Min/Max mode and “Max Min” will be displayed.
In this mode the 1008 will keep track of the minimum, maximum, and average
CO2 and Temperature being measured. When “Min Max” is displayed the 1008
will display the real time reading.
Pressing the key switches the temperature display between °F and °C.
To deactivate Min/Max mode and return to normal operation, Press and hold the
key until the 1008 beeps.
Pressing the key turns the display backlight on and off. Power
consumption is much higher when the backlight is activated. The backlight
will automatically turn off 30 seconds after it is activated. To conserve bat-
tery life the backlight should only be used when necessary.
Pressing the key will cause the 1008 to display “MAX”. This indicates the
Maximum CO2 and Temperature measured is displayed.
Press the key again and the 1008 will display “MIN”. This indicates the
Minimum CO2 and Temperature measured is displayed.
Press the key again and the 1008 will display “AVG”. This indicates the
Average CO2 and Temperature measured is displayed.
Pressing the key will cause the 1008 to display “MAX MIN”. This indicates
the real time reading is displayed and the Min/Max mode is still active. The steps
above can be repeated to cycle through the Min, Max, and Avg displays.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

4. Operation
4.1 Turning On & Off / Performing a Test / Main Display
Enter the area to be tested, the measured values will be displayed.
Carbon dioxide (CO2) in parts per million (ppm) is displayed at the top and
Temperature in °F or °C (selectable)is displayed at the bottom of the main
display.
The battery indicator is located at the left center of the display. When the bat-
teries become low they must be replaced to maintain proper operation.
The 1008 has a CO2 alarm. If the CO2 level measured is at or above the
set alarm level the 1008 will beep and the display will flash red as a
warning. This alarm point is adjustable. Additional functions can be acti-
vated during testing. Please see next sections.
Carbon dioxide (CO2)
Temperature
Battery indicator
Press the key and the 1008 will begin a 30 second countdown. During
this time the 1008 performs a self diagnostic. Once the countdown ends the
1008 will display CO2 and Temperature.
To turn the 1008 off, press and hold the key down until the 1008 turns off.
7. Technical Specifications
Function Range Accuracy
CO2 0 to 5000ppm 50°F~104°F: ±3% of rdg+75ppm
<50°F, >104°F: ±5% of rdg+75ppm
Temperature -5°F to 140°F ±2°F
-20°C to 60°C ±1°C
Data Logging: Up to 50 samples 1 minute to 60 minutes in 1, 2, 3, 5, 10, 20, 30,
40, 50, 60 minute intervals
Display Type: 2 line with annunciators and backlight
CO2 Alarm: Audible and visual, selectable level (factory default off)
Operating Temperature & Humidity
CO and CO2: 14°F to 122°F (-10°C to 50°C)
All Other Function: -4°F to 140°F (-20°C to 60°C)
Humidity 15 ~ 95% non-condensing
Storage Temperature: -4°F to 140°F (-20°C to 60°C)
Power supply
3 AA battery( 4.5V)
AC/DC adapter 5Vout (Center positive)
Battery Life: 40 hours typical without backlight
Output: Serial output via USB connection
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

8. Maintenance
It is recommended that the instrument be calibrated every 12 months.
Please consult Test Products International for further details (800) 368-5719.
8.1 Battery Replacement
When the batteries become low they will require replacement.
1. Turn the meter over so the back is facing you.
2. Loosen the screw holding down the battery cover located under the tilt
stand.
3. Lift the tilt stand up and remove the battery cover.
4. Replace the batteries (3 x AA Alkaline) and install the cover and tighten the
screw.
8.2 Service
To obtain warranty and non-warranty performance or maintenance on your
analyzer: - Include with the product your name, address, phone number, writ-
ten description of the problem and proof of purchase date. Carefully package
and return to:
TPI / Attn. Repair
9615 SW Allen Blvd. Suite 104
Beaverton, OR 97005
3.3 Back View
Tilt Stand
Battery Cover Screw
Hanger Hole
Hanger Hole: Use to hang instrument for hands free operation. Can
be used with A127 magnetic strap kit or A103 hook.
Tilt Stand: Use to stand instrument on a table.
Batter Cover Loosen this screw and open cover to access batteries.
Screw:
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

3.2 Soft Keys
On / Off key - Used to turn the IAQ meter on or off. Press to turn
on, press and hold to turn off.
Up Arrow key - Used to select and change parameters.
Down Arrow key - Used to select and change parameters.
Mode key - Used to switch between Celsius and Fahrenheit units
of display and to enter CO2 alarm level input mode. Press to
switch between Celsius and Fahrenheit units. Press and hold to
enter and exit CO2 alarm level mode.
Backlight key - Used to turn the display backlight on and off.
Min / Max key - Used to activate and cycle through minimum,
maximum, and average display modes. Press to activate Min/Max
mode, press repeatedly to cycle through min, max, and avg dis-
plays. Press and hold to deactivate Min/Max mode.
Log key - Used activate and deactivate data logging.
RCL Key - Used to recall (display) logged data.
9. Technical Information
Recommended Levels by Agency
Parameter IDPH1ASHRAE2OSHA PEL3ACGIH TLV4
Humidity 20% - 60% 30% - 60% N/A N/A
Temperature 68 - 75 (winter)
73 - 79 (summer) 68 - 75 (winter)
73 - 79 (summer) N/A N/A
Carbon Dioxide 1,000ppm
(<800ppm preferred) 1,000ppm 5,000ppm 5,000ppm
Carbon Monoxide 9ppm 9ppm 50ppm 25ppm
N/A-Not Applicable or Not Established
1Illinois Department of Public Health (2009)
2American Society of Heating, Refrigerating and Air Conditioning Engineers
3Occupational Safety and Health Administration Permissible Exposure Limit -- this level
is a time-weighted average and is an enforceable standard that must not be exceeded
during any eight-hour work shift of a 40-hour work week.
4American Conference of Governmental Industrial Hygienist Threshold Limit Value -- this
level is a recommended time-weighted average upper limit exposure concentration for a
normal eight to 10-hour workday and a 40-hour work week.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

10. Error Codes & Troubleshooting
CO2 Sensor Error
If the CO2 sensor fails to initialize or is faulty the
1008 will display an error code. Try turning the 1008
off and on again. If it displays the error code again
the 1008 is in need of service. Please return your
instrument to TPI. See section 9.2 for instructions on
returning your meter.
Temperature Sensor Error
If the temperature sensor fails to initialize or is faulty
the 1008 will display an error code. Try turning the
1008 off and on again. If it displays the error code
again the 1008 is in need of service. Please return
your instrument to TPI. See section 9.2 for instruc-
tions on returning your meter.
3. Familiarization
3.1 Front View
Sensor Locations: Places where the CO and Temperature sensors
are located and protected.
Display : Large 2 Parameter Backlit LCD Display.
Protective Rubber Boot Provides protection to meter housing and sensors.
Keypad Selects all available functions
USB Port Location for connection of USB cable for PC com
munication.
Power Adapter Socket Location to connect power adapter.
Display
Keypad
CO2 &
Temperature
Sensor Location
USB Port Power Adapter
Socket
Protective
Rubber Boot
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
Table of contents
Other TPI Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Gigahertz Solutions
Gigahertz Solutions HFW59D manual

Red Seal Measurement
Red Seal Measurement Datamate 2200 operating & maintenance manual

senva
senva AQD Duct Series installation instructions

Swann
Swann AMU Pharmacon Operator's manual

JENCO
JENCO 6179MB Operation manual

NuFlo
NuFlo EZ-IN Series installation manual