
BAS-SVX091A-EN 11
Symbio 500 Controller Features
Table 2. Symbio 500 features
Feature Description
Controller Interface Flexibility:
The Symbio 500 controller allows VAV units to communicate on a BACnet MS/TP, BACnet/Zigbee, or BACnet/IP link and is
compatible with the latest generation of Trane controls. This controller can operate in standalone mode, peer-to-peer with one or
more other units, or when connected to a Tracer SC+ or a 3rd party building automation system that supports BACnet.
Flow Tracking:
The Symbio 500 controller is designed with the ability to be applied in flow tracking applications. This allows the controller to be
paired with one of its peers to mirror the flow of the lead unit, with or without an offset (positive or negative static pressure as
desired).
Ventilation Flow Control with
Tempering:
The Symbio 500 controller is designed with the ability to be applied in ventilation flow control applications. These applications
combine a fresh air unit with ventilation boxes to provide fresh (tempered) air to a zone. This feature also includes a freeze
protection sequence to protect the hot water reheat coil from low supply air temperatures.
Auto-commissioning
Sequence:
The Symbio 500 controller is designed with an auto-commissioning sequence. With a discharge air temperature sensor, this
feature exercises the air valve, fan, and heat in the box and records the temperature before/after the action. This allows the
installer to easily verify the operation of the unit and commission by exception. An auto-commissioning report can be generated
with Tracer TU service
Automatic Calibration:
The Symbio 500 controller is designed to automatically calibrate the flow transducer each time the unit transitions to
unoccupied. This eliminates the need to initiate/schedule calibration for most installations. The exception is 24/7 sites, in which
case, Tracer SC+ can be used to initiate/schedule calibration.
Temporary Heat
(Construction Mode):
Upon reset (and power-up), if the controller does not detect a valid space temperature, the controller will provide temporary heat
by driving the air valve to the heating maximum position.
Note: The unit will provide heat only if the air handler unit provides hot air.
Local Versus Remote Reheat
Flexibility:
The controller can be configured to have local and/or remote heat. In addition, provided configuration flexibility allows the
installer to select priority for either local or remote heat has.
Spare Inputs/Outputs:
The Symbio 500 controller has spare I/Os that are not used by the VAV applications. These spare I/Os can be programmed
using the Tracer Graphical Programming editor (by means of the Tracer TU service tool) to measure and/or control ancillary
devices such exhaust fans, second air valve for dual duct VAV, or sensing relative humidity.
Removable Terminal
Connectors:
The Symbio 500 controller connectors are 2-part connectors with 5.08 millimeter pin separation. The headers are attached on
the Symbio 500 controller itself. The other portion of the connector is either a screw terminal (for field wiring) or a terminal
housing (for factory wiring). Spare screw terminals come factory installed for field mounted wired zone sensors and common
accessories.
Wireless Zone Sensors:
The Symbio 500 controller is compatible with the latest wireless zone sensors available from Trane. Wireless zone sensors
provide flexibility of sensor location and re-location as well as reducing the cost of installation. Wireless zone sensor receivers
are available as a factory or field installed option.
Firmware (Application Code)
Download:
The Symbio 500 controller has been designed with flash memory. This allows the option of upgrading the application code in the
field without changing out the controller.
Drive Min/Max from Zone
Sensor:
When applied with a Trane zone sensor module, that includes a thumbwheel setpoint or a LCD display, the Symbio 500
controller can easily be overridden to minimum and maximum flow. By simply turning the thumbwheel to *or increasing the
setpoint to maximum on display sensors (end of range in one direction), the controller drives the air valve to the minimum flow
setpoint. Likewise, turning the thumbwheel to the ** or decreasing the setpoint to minimum on display sensors (end of range in
the other direction) the controller drives the air valve to the maximum flow setpoint. This feature can be disabled by putting
Airflow Override Local, Multistate Input 2, and Out of Service using Tracer TU.
Auto-commissioning Report
(Tracer SC+ and Tracer TU):
Tracer SC+ and Tracer TU both include auto-commissioning reports that extracts and formats the commissioning data for each
VAV controller. This commissioning report is valuable both for the installer and for the owner. The feature enables the system to
be commissioned by exception, providing a benefit for the installer. The feature also can be used as validation that provides
value to the owner.
Dual pressure inputs Necessary for Dual Duct applications
Easy to Setup VAS: Tracer SC+ includes a VAV Air System (VAS) specifically designed for both BACnet and LonTalk® VAV controllers. This VAS is
designed for easy setup.
Easy to Setup VAS: As a part of the standard application, VAS calculates the duct static pressure setpoint based on the VAV unit with a damper in
the maximum flow position.
Ventilation Optimization:
As a part of the standard application, the VAV system has the ability to calculate the ventilation setpoint for the air handler unit.
In addition, the Symbio 500 controllers have a ventilation ratio limit feature that automatically increases airflow to maintain the
required ventilation while operating within system limits for outside air percent concentrations in the supply air stream.