
BAS-SVX065E-EN 15
when the controller has the fan controlled to ON, the controller generates a Low Primary Airflow
Diagnostic
Analog Inputs
The UC400 Controller has seven (7) analog inputs
Ground Terminals
Use the terminal as the common ground for all space temperature sensor analog inputs
AI1; Space Temperature
Space Temperature AI1 functions as the local (hard wired or wireless) space temperature input
The UC400 Controller receives the space temperature as a resistance signal from a 10 kΩ
thermistor in a standard Trane space temperature sensor that is wired to analog input AI1 A
space temperature value communicated by means of a BACnet link, can be used for controllers
operating on a BAS When both a hard wired and communicated space temperature value are
present, and in service, the controller uses the communicated value
If neither a hard wired nor a communicated space temperature value is present, the space
temperature local and active points go into a fault state and generates an alarm If neither the
hard wired or communicated space temperature are valid, the equipment will shut down
AI2; Space Temperature Local Setpoint
Space Temperature Local Setpoint AI2 functions as the local (hard wired) space temperature
setpoint input for applications utilizing a Trane space temperature sensor with a temperature
setpoint thumbwheel or digital setpoint input A setpoint value communicated by means of a
BACnet link, can be used for controllers operating on a BAS If both hard wired and
communicated setpoint values are present, and in service, the UC400 Controller uses the
communicated value
In addition, the controller can be configured to use the local (hard wired) input value instead of
the communicated value using the Tracer TU service tool If neither a hard wired nor a
communicated setpoint value is present, the controller uses the space temperature setpoint
default analog value, which is configured using the Tracer TU service tool If a local setpoint
value is not valid or not present, the controller generates a Space Temperature Setpoint Local
alarm
AI3; Local Fan Mode Input
Local Fan Mode Input AI3 functions as the local (hard wired) fan mode switch input for
applications using the Trane space temperature sensor with a fan mode switch option The
various fan mode switch positions (OFF, LOW, MEDIUM, HIGH, AUTO) provide different
resistances that are interpreted by the UC400 Controller
NNoottee:: The local fan speed switch can be disabled by taking out of ser ice the multi-state point,
supply fan speed local and setting the alue for each to AUTO.
A communicated fan mode request by means of the BACnet communications link, can be used
for controllers operating on a BAS If both hard wired and communicated fan mode values are
present and in service, the UC400 Controller uses the communicated value However, the
controller can be configured to use the local (hard wired) input value instead of the
communicated BAS value The supply fan speed source (local or BAS) can be selected on the
Tracer TU Setup Parameters page If neither a hard wired nor a communicated fan mode value is
present, the controller recognizes the fan mode value as AUTO and operates according to the
default configuration If a valid hard wired or communicated fan mode value is established, and
then is no longer present, the controller generates a Supply Fan Speed Local alarm
AI4; Discharge Air Temperature Sensor
Discharge Air Temperature Sensor AI4 functions as the local discharge air temperature input
The UC400 Controller receives the temperature as a resistance signal from a 10 kΩ thermistor
wired to analog input AI4 The thermistor is typically located downstream from all unit heating
TTyyppiiccaall AApppplliiccaattiioonnss aanndd TTeerrmmiinnaattiioonnss