Trophy 51.2V300E-3UL User manual

TROPHY BATTERY, LLC
Page 1 of 14
51.2V300E-3UL Rack Mountable LiFePO4 Battery
Model 51.2V300E-3UL
Important Information –Read this First
1. Thank you for purchasing our Trophy Battery 51.2V300E-3UL battery.
2. Trophy Battery offers personalized assistance and guidance for you in designing and setting
up your system. If you have any questions or concerns please call us.
Please call us at 803-380-6211 if you need assistance.
Our email is dan@trophybattery.com
If you need to text us or send us photos, use 803-341-2117, as the 803-380-6211 phone line
does not accept texts or photos.
For non-emergency situations, you may call between 8 am and 10 pm Eastern Time (New
York Time).
For emergency situations, you may call us 24/7.
3. This is a 48 Volt class battery which may be used with 48V class Inverters, Chargers, and
Solar Charge Controller.
The nominal voltage of this battery is 51.2 Volts.
The Recommend Charge Voltage is 56.8 Volts, with a Float of 54.0 Volts, and a Battery
Cutoff Voltage of 48 Volts or higher.
Certain inverters such as some EG4, MPP Solar, Sun Gold Power, Rich Solar, and others will
require a Battery Float Voltage of 56.0 Volts.
If your inverter or Solar Charge Controllers seems to stop charging the battery at 54 Volts,
set the Float Voltage to 56.0 Volts.
Only 48 Volt Inverters, 48 Volt Solar Charge Controllers, or 48V LiFePO4 chargers may be
used to charge this battery.
Do not reverse the polarity when connecting to the battery terminals, positive (+) must be
connected to positive and negative (-) to negative.

TROPHY BATTERY, LLC
Page 2 of 14
Never connect AC, of any voltage, such as from a wall outlet to the battery terminals.
An appropriate 48V inverter, charger, or solar charge controller must be used.
Do not expose the battery to water, excessive humidity, excessive temperatures in excess of
105F, to oils or acids, or to direct sunlight.
Do not drill into the battery case, or weld to the battery case.
4. The battery may be oriented vertically, horizontally, or on its side.
We do not recommend setting the battery upside down.
The battery comes with a nice 4-wheel dolly with locking wheels.
Please consider using this dolly. If desired, remove the sides of the wooden battery case,
ensure that the dolly wheels are locked in place, leave the dolly on the bottom of the
battery, then, with help, then lift one end of the battery so that the battery rests on the
dolly.
5. The two short DC Power Cables included with the battery should only be used if you will be
drawing no more than 50 amps from the battery.
If will be using a 3,000 watt or higher inverter, these cables must not be used.
Use 2/0 AWG Pure Copper battery cables, with very high strand count.
You may also use 4/0 AWG Pure Copper battery cables.
To make this easy, we recommend using www.batterycablesusa.com
Use the Marine Grade, UL Listed battery cables, with 5/16” copper lugs for the battery ends.
If you are using a Victron Lynx Power End or Distributor busbars, also use 5/16” copper lugs.
00 Gauge (2/0 AWG) Marine Grade Tinned Copper Battery Cable UL 1426 Flexible with ends
(batterycablesusa.com)
0000 Gauge (4/0 AWG) Marine Grade Tinned Copper Battery Cable UL 1426 Flexible with ends
(batterycablesusa.com)
We highly recommend using the above cables to prevent problems, either immediately, or
in the future. You may call us for advice.
The recommended DC Power Cables for most installations are 2/0 AWG
(Pronounced Two-Aught), using 5/16” Copper Cable Lugs.
Cable Lugs are Cable Terminators (ends) that allow the battery cable to be bolted to the
battery terminal.

TROPHY BATTERY, LLC
Page 3 of 14
There are two positive battery terminals, and two negative battery terminals.
For the connection to the battery terminals, 5/16” cable lugs are best, but 3/8” may be
used.
6. Never connect our batteries in series.
Never connect + to –as this is a series connection.
If connecting multiple batteries, the batteries must be connected in parallel.
Parallel connections are + to + and –to –. (Positive to Positive, Negative to Negative)
7. The best way to connect multiple batteries, if you are using more than one battery,
is to use professional copper busbars.
When using busbars, you use equal length battery cables from each battery to the busbar.
Then you connect your inverter(s) to the busbars. If you have multiple inverters, then each
of the cables to the busbars must be the same length.
Victron makes high quality 1000 amp busbars, called Lynx Power In and Lynx Distributor.
The Lynx devices are expandable, as each unit can bolt to the next.
One Power In has connections to enable four batteries to be connected.
One Distributor also has four connections.
Trophy Battery sells Victron gear, so you may purchase the Lynx busbars from us or other
sources. The Lynx busbars are two busbars in one, one for positive and one for negative.
The Lynx Distributor is a fused busbar, thus you can economically add Mega-Fuses to
protect your inverters or solar charge controllers.
Please feel free to call us for guidance.
The Lynx busbars use M8 –5/16” terminals.
Blue Sea Systems also makes quality busbars.
Avoid at all costs, a cheap, undersized busbars or a busbar that contains brass instead of
copper. These will not work and are a waste of money.

TROPHY BATTERY, LLC
Page 4 of 14
8. When using Multiple Inverters, it is necessary to combine all batteries together, using
busbars, to make one large battery bank, and then connect all inverters to the busbars.
9. Certain Inverters, such as Sol Ark 12K and Sol Ark 15K use 3/8” terminals, so your busbar to
inverter cables must have 3/8” terminals for the inverter ends.
The Sol Ark 15K has dual DC input terminals, two + and two –and you should use two
battery cables to power each Sol Ark 15K inverter.
You may call us for guidance.
10. When you have multiple batteries, you need to have a communication cable from each
battery to the next. You should connect one each of the cable to either of the 485-1 or
485-2 ports of one battery to either 485-1 or 485-2 port of the next battery.
We provide these communication cables with the batteries. But, if you need a longer cable,
please use a straight-thru cable, not a cross-over cable. Use an Ethernet cable, with RJ45
connectors, preferably CAT5e.
When connecting multiple batteries together, it is best to use the same brand and model of
batteries together.
There are cases where it is ok to connect a different brand or model of batteries together.
Please call us so we can advise you in advance.
If you have more than 16 batteries, you can set up one bank of 16 and then have another
bank of up to 16 batteries. Other arrangements are possible, such as 20 batteries in two
banks of 10 each.
If you have a different brand of battery, or a different model of battery, you will need to
break the battery to battery communication cabling. Please call us for advice.
Different types of batteries generally cannot communicate with each other, thus omit the
communications cable between them.
11. The battery has a push-button On-Off Switch to turn the battery on or off.
This turns on the battery’s electronics, the battery’s Battery Management System.
The large circuit breaker is labeled Breaker, and this is to connect or disconnect this one
battery from the load or from charging.

TROPHY BATTERY, LLC
Page 5 of 14
12. If the battery is in storage, or not being used, it is necessary to charge it a little, 5 to 10%
every three months. This is necessary to keep the electrolyte in the battery liquid. Do not
go by battery voltage or state-of-charge to determine if the battery needs to be recharged
after 3 months.
13. This battery is compatible with Victron 48V Inverter/Chargers and 48V Solar Charge
Controllers.
If you have a Cerbo GX as part of your Victron System, please order a Victron Type A cable
to go from the CAN/485 Port on the battery to the BMS CAN port on the Cerbo GX.
If you have a Cerbo S GX, it is possible to use it instead of a Cerbo GX under certain
conditions. Please call us for advice. If you have any VE.CAN devices that you need to
connect and you need to also connect to the battery, then you must have the Cerbo GX and
not the Cerbo S GX.
The Type A cable is labeled “BMS- Battery”on one end, plug this end into the CAN/485 port
on the battery.
Plug the end labeled VE.CAN to either BMS-CAN Port on the Cerbo GX, and not a VE.CAN
Port! Plug a Victron Blue Terminator into the other BMS-CAN port.
If you need assistance, please call us. Trophy Battery is an authorized Victron Dealer and
can provide most any Victron device.
14. This battery has Bluetooth communications so you can easily see the status of your battery.
The iOS/Android app is named yBMS and can be downloaded to you iPhone/iPad or
Android device.
15. This battery is designed to communicate with Sol Ark Inverters. Connect Straight-Thru
Ethernet Cable from the battery’s CAN/RS-485 port to the CAN port on your inverter.
If you have any questions, please call use.
For Sol Ark, please set the option to use Battery Cutoff by Voltage and not State-of-Charge.

TROPHY BATTERY, LLC
Page 6 of 14
51.2V300E-3UL Rack Mountable LiFePO4 Battery
Model 51.2V300E-3UL
MODEL: 51.2V300E-3UL
Nominal Voltage:51.2 (Works with 48V Devices)
Nominal Capacity: 300Ah
Content
1.MODIFIED LIST ..............................................................................................................................................7
2. Scope ..........................................................................................................................................................8
3. Initial Dimension ..........................................................................................................................................8
4. Specification ................................................................................................................................................9
5. BMS parameters ..........................................................................................................................................11
6. General Performance .................................................................................................................................11

TROPHY BATTERY, LLC
Page 7 of 14
7. Environment Performance ..........................................................................................................................11
8. Safety Characteristics .....................................................................................................................................8
9.CAUTIONS IN USE ........................................................................................................................................13
10. Battery operation instruction ....................................................................................................................10
11. Other, The Chemical Reaction ...................................................................................................................13
12. Note: .......................................................................................................................................................14
1. MODIFIED LIST
Product Modified Record List
Revision
Date
Mark
Modified content
Approved by
A1
2023-01-14
A2
2023-01-14
A3
2023-01-14
A4
2023-09-27

TROPHY BATTERY, LLC
Page 8 of 14
2 . Scope
This specification describes the basic performance, technical requirement, testing method,
warnings and cautions for the Trophy Battery 51.2V300E-3UL Lithium Ferrous Phosphate
rechargeable battery .
3. Products assembly drawing and size refers to picture 1

TROPHY BATTERY, LLC
Page 9 of 14
4. Specification
NO.
Item
Specifications
4.1
Cell Type
LiFePO4
4.2
Typical Capacity
300Ah @ 1C Discharge (1C)
Minimum capacity
298Ah @ 1C Discharge (1C)
4.3
Nominal voltage
51.2V
4.4
End-of-charge Voltage
57V±1.0V, 0.2C5A
4.5
End-of-discharge Voltage
42V±2.0V, 0.2C5A
4.6
Max Charge Current
150A
4.7
Max Continuous Discharge Current
200A
4.8
Instantaneous Max Discharge Current
220A±5A /1 Second
4.9
Over Current Protection
250A±15A /100milliseconds
4.10
Protection function
OCVP/ODVP/OCP/SCP/OTP etc.
4.11
Communication interface
RS485/CAN/Bluetooth

TROPHY BATTERY, LLC
Page 10 of 14
4.12
On/Off Switch
Yes
4.13
Operating temperature
Charging:0℃~45℃
Discharging:-10℃~60℃
4.14
Storage temperature
-5℃~35℃
4.15
Storage Humidity
≤75% RH
4.16
Standard environmental condition
Temperature:25±2℃
Humidity :45-75%RH
Atmospheric Pressure:86-106 KPA
4.17
Positive terminals
Two Waterproof terminals Black
4.18
Negative terminal
Two Waterproof terminals RED
4.19
Communication connector
RJ45
4.20
Switch connector
Switch
4.21
Shell Material
Metal
4.22
Shell Color
Black
4.23
Size
442mm*770mm*285mm 17.4”x30.31”x11.22”
4.24
Weight
Approximate:140kg 308.65lbs
5. BMS
NO.
Item
Specifications
5.1
Single cell overcharge protection
3.65V±20mV, 1 Second
5.2
Whole battery overcharge protection
57V±0.5V, 1 Second
5.3
Single cell over discharge protection
2.60V±50mV, 1 Second
5.4
Whole battery over-discharge
protection
43V±2V, 1 Second
5.5
Charging over current protection
150A±10A, 1 Second
5.6
Discharge over current protection
220A±10A, 1 Second
5.7
Discharge over current protection 2
250A±15A, 100milliseconds

TROPHY BATTERY, LLC
Page 11 of 14
5.7
Charging high temperature protection
55℃±2℃
5.8
Charging low temperature protection
0℃±2℃
5.9
Discharge high temperature protection
65℃±2℃
5.10
Discharge low temperature protection
-10℃±2℃
5.11
Short circuit protection
Yes
6 . General Performance
No.
Item
Test Methods and Condition
Criteria
6.1
0.2C Capacity
0.2C
After standard charging, rest battery for 10min, then
discharging at 0.2C to voltage 40V, recording the
discharging time.
≥300Ah
6.2
Capability of
keeping
electricity
20±5℃, After standard charging, rest the battery
28days, discharging at 0.2C to voltage 40.0V,
recording the discharging time.
≥200min
7. Environment Performance
No.
Item
Test Methods and Condition
Criteria
7.1
Discharge at
high
temperature
After standard charging, rest the cells 4h at 60±2℃,
then discharging at 1C to voltage 40.0V, recording the
discharging time.
≥45min
7.2
Discharge at
low
temperature
After standard charging, rest the cells for 16h at
-20±2℃, then discharging at 0.2C to voltage 40.0V,
recording the discharging time.
≥180min
7.4
Thermal
shock
Put the cells in the oven. The temperature of the oven
is to be raised at 5±2℃per minute to a temperature of
100±2℃and remains 30 minutes.
No fire, no
smoke
8 . Safety Characteristics
No.
Item
Test Methods and Condition
Criteria

TROPHY BATTERY, LLC
Page 12 of 14
8.1
Over charge
testing
At 23±5℃, charging cells with constant current 1C to
voltage 60V, Stop test till cells temperature 10℃
lower than max temperature.
No smoke or fire
8.2
Over
discharge
testing
At 23±5℃, According to the requirements of
standard charge, the cells will be discharge to
cut-off voltage, then connect with external load of
30 ohm for 24 hours.
No fire, no smoke,
no leakage.
8.3
Short-circuit
testing
At 23±5℃, After standard charging, connect cells
anode and cathode by wire which impedance less
than 200±20mΩ, keep 6h.
No smoke or fire
※Above testing of safe characteristic must be performed with protective equipment.
9. 1 CAUTIONS IN USE
To ensure proper use of the battery please read the manual carefully before using it.
Proper Handling
Do not expose to, dispose of the battery in fire.
Do not put the battery in a charger or equipment with wrong terminals connected.
Avoid shorting the battery
Avoid excessive physical shock or vibration.
Do not disassemble or deform the battery.
Do not immerse in water.
Do not connect the battery to other different make, type, or model batteries.
Keep out of the reach of children.
Charge and Discharge
Battery must be charged using an appropriate LiFePO4 charger or inverter only.
Never use a modified or damaged charger.
Do not leave battery in charger over 24 hours.
Storage
Store the battery in a cool, dry and well-ventilated area.
Disposal
Regulations vary for different countries.
Dispose of in accordance with local regulations.

TROPHY BATTERY, LLC
Page 13 of 14
10. Battery operation instruction
10.1 Charging
Charging current:Do not exceeded the maximum charging current specified in this document.
Charging voltage:Do not exceeded the maximum charging voltage specified in this document.
Temperatures: Do not exceed the maximum and minimum temperatures specified in this
document.
This battery uses the constant current/constant voltage method of charging.
Do not use reverse voltage to charge the battery.
Do not short circuit the positive and negative terminals of the battery.
Use chargers designed for 51.2 Volt (48V Class) LiFePO4 chargers and/or inverters.
10.2 Discharging Current
The discharging current should not exceed the specifications in this document.
Exceeding the specifications can cause reduced battery capacity and excessive heat
10.3 Discharge Temperature
The battery discharge must be within the ambient temperatures listed in this document.
10.4 Over-Discharges
Avoid over discharging the battery. Multiple over discharges can affect the battery.
10.5 Storing the Batteries
If the battery is stored, ensure that the ambient temperature and humidity conditions in this
document are met.
Storage over 3 months requires the battery to be charged, ideally to 50% to 70% State of Charge.
11. Other
The Chemical Reaction
Because batteries utilize a chemical reaction, battery performance will deteriorate over time
even if stored for a long period of time without being used. In addition, if the various usage
conditions such as charge, discharge, ambient temperature, etc. are not maintained within the
specified ranges the life expectancy of the battery may be shortened or the device in which the

TROPHY BATTERY, LLC
Page 14 of 14
battery is used may be damaged by electrolyte leakage. If the batteries cannot maintain a charge for
long periods of time, even when they are charged correctly, this may indicate it is time to replace the
battery.
12. Notes:
This manual suits for next models
3
Table of contents
Popular Batteries Pack manuals by other brands

Quantum
Quantum Turbo SC Slim Compact operating instructions

KiloVault
KiloVault HLX+ Series Installation & user manual

Lenz
Lenz LITHIUM PACK INSOLE RCB 1200 operating instructions

XD COLLECTION
XD COLLECTION XD P322.62 Series manual

Stryten Energy
Stryten Energy M Series Installation and operating instructions

Panasonic
Panasonic CF-VZSU49U operating instructions