3
Step 5. To install the escutcheon
plate (and closure plate if applicable),
align it (them) with and press it (them)
over the sprinkler body until the outer
edge of the escutcheon
(or closure plate) meets the
mounting surface. Do not over or
under tighten the sprinkler to
compensate for inaccurate
escutcheon plate adjustment.
Step 6. Install the tamper resistant
retaining screws through the
escutcheon and into the retaining
collar, thereby drawing the
escutcheon (and closure plate) up
tight against the mounting surface.
The tamper resistant retaining screws
can only be installed or removed
using the special tamper-proof
socket.
Caution: Special care must be taken
when installing with a CPVC system.
Sprinklers must be installed after the
manufacturer's recommended setting
time for the primer and cement to
ensure that neither accumulate within
the sprinkler.
Special care must be taken when
installing with a copper system.
Sprinklers must be installed only after
the inside of the sprinkler nipple and
associated fittings have been wire
brushed to remove any flux.
Residual flux can cause corrosion
and in extreme cases can impair
proper sprinkler operation.
Design Requirements - Standard Coverage Applications
Upon completion of the installation,
the system must be tested per
recognized standards.
In the event of a thread leak,
remove the unit, apply new pipe joint
compound or tape, and reinstall.
Installation Sequence
Step 1. The sprinkler must be
installed in the horizontal position 4"
to 12" below ceiling.
Step 2. Install the steel nipple into
the branch line fitting, then slide the
rigid support collar over the nipple
prior to installing the 1" x 1/2"
reducing coupling. The face of the
sprinkler fitting should be installed:
(a) 1 7/16" (±1/16") behind the
finished wall if no closure
plate is utilized.
(b) 1 3/8" (±1/16") behind the
finished wall if the light gauge
escutcheon closure plate is
utilized.
(c) 1 5/16" (±1/16") behind the
finished wall if the security
closure plate is utilized.
The sprinkler nipple must be fitted
with the rigid support collar to prevent
movement of the sprinkler away from
the finished wall surface (see
installation diagram on page 2).
Step 3. Use only a non-hardening
pipe joint compound or Teflon* tape.
Apply to the male threads only.
Step 4. Hand tighten the sprinkler
into the reducing coupling. Use an
Omega HEC sprinkler wrench to
tighten the unit into the fitting. A leak
tight joint requires the application of
only 7 to 14 ft.-lbs. of torque. A
tangential force of 14 to 28 lbs.
delivered through a 6" long handle
will deliver adequate torque. Torque
levels over 21 ft.-lbs may distort the
orifice seal, resulting in leakage.
Technical
Data
Model: HEC-12 PRO
Style: Horizontal Sidewall
Orifice Size: 1/2"
K Factor: 5.6
Thread Size: 1/2" N.P.T.
Temperature Rating: 160oF/71oC
Approvals: U.L., U.L.C.,
MEA 46-92-M
Maximum Working Pressure: 175 psi
Factory Hydro Test: 100% at 500 psi
Standard Finishes:
Sprinkler: chrome, factory brass
Escutcheon: chrome plated, brass
plated, white painted
Escutcheon Closure: chrome plated,
white painted
Security Closure: chrome plated,
Length: 2 3/8"
Width: 2"
Weight: 6.8 oz.
Installation
ProhibitorTM sprinklers must be
installed in accordance with current
NFPA 13. Deviations from these
requirements and standards, or any
alteration to the sprinkler itself, will
void any warranty made by Central
Sprinkler Company. In addition,
installation must also meet local
government provisions, codes, and
standards as applicable.
The system piping must be properly
sized to ensure the proper flow rate at
the sprinkler.
Prior to installation, check for
proper model, style, orifice size, and
temperature rating. Install sprinklers
after the piping is in place to avoid
mechanical damage; replace any
damaged unit. Wet pipe systems
must be protected from freezing.
The Model HEC-12 PRO Horizontal Sidewall Sprinklers are intended for
standard coverage areas and standard flow and pressure requirements as
specified in the current NFPA 13 for light and ordinary hazard occupancies. The
sprinklers must be installed in the horizontal sidewall position, with the deflector
from 4" to 12" below the ceiling.
Sprinklers must be handled care-
fully. They must not be transported
or stored where ambient tempera-
tures may exceed 100oF/38oC. For
best results, store them in a cool, dry
location in the original shipping
package.
Do not install sprinklers that have
been dropped or visibly damaged.
Sprinklers must never be painted,
coated, plated, or altered in any other
way from manufactured condition or
they may not function properly. Any
sprinklers altered in such a manner
must be replaced.
Care &
Maintenance
*Teflon is a trademark of the DuPont Corp.