EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco Fire Product
  6. •
  7. Irrigation System
  8. •
  9. Tyco Fire Product Star Celeste S150 User manual

Tyco Fire Product Star Celeste S150 User manual

Other Tyco Fire Product Irrigation System manuals

Tyco Fire Product Gem F685 User manual

Tyco Fire Product

Tyco Fire Product Gem F685 User manual

Tyco Fire Product CENTRAL GB-LO 17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL GB-LO 17/32 User manual

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL Attic BB1-17/32 User manual

Tyco Fire Product Star Stealth S240 User manual

Tyco Fire Product

Tyco Fire Product Star Stealth S240 User manual

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-25 User manual

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product

Tyco Fire Product CENTRAL A User manual

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TY-B User manual

Tyco Fire Product Star SuperNova S120 User manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S120 User manual

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV-R1 User manual

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR User manual

Tyco Fire Product CENTRAL BV4 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL BV4 User manual

Tyco Fire Product CENTRAL ELO-16 GB User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-16 GB User manual

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product

Tyco Fire Product CENTRAL H User manual

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product

Tyco Fire Product SIN S3244 User manual

Tyco Fire Product CENTRAL TFP1 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL TFP1 User manual

Tyco Fire Product central bvr User manual

Tyco Fire Product

Tyco Fire Product central bvr User manual

Tyco Fire Product Star Mizar S215 User manual

Tyco Fire Product

Tyco Fire Product Star Mizar S215 User manual

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SG User manual

Tyco Fire Product EC-HS User manual

Tyco Fire Product

Tyco Fire Product EC-HS User manual

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESFR-17 User manual

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product

Tyco Fire Product Star Luminous S170 User manual

Tyco Fire Product Gem A User manual

Tyco Fire Product

Tyco Fire Product Gem A User manual

Tyco Fire Product CENTRAL ELO-231 BV User manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 BV User manual

Tyco Fire Product TY-B Series User manual

Tyco Fire Product

Tyco Fire Product TY-B Series User manual

Popular Irrigation System manuals by other brands

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Reliable F1-300 quick start guide

Reliable

Reliable F1-300 quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Reliable F4FR quick start guide

Reliable

Reliable F4FR quick start guide

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Reliable F1FR42 Series manual

Reliable

Reliable F1FR42 Series manual

Reliable F1FR-300 quick start guide

Reliable

Reliable F1FR-300 quick start guide

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Tyco TY-L Series quick start guide

Tyco

Tyco TY-L Series quick start guide

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

Victaulic

Victaulic VicFlex I-VICFLEX.AQC-U installation instructions

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

Std. Response, Std. Coverage
Flush Pendent Sprinklers
Celeste™ S150, K=5.6
GENERAL DESCRIPTION
The Star Celeste S150, 5.6 K-Factor, Standard Re-
sponse, Standard Coverage, Flush Pendent Sprinklers
are decorative fusible solder type sprinklers designed for
use in commercial occupancies such as offices and res-
taurants. When aesthetics is the major consideration, the
Celeste S150 should be your first choice.
The Celeste S150 features a separable escutcheon pro-
viding 3/8 inch (9,5 mm) vertical adjustment. This adjust-
ment reduces the accuracy to which the fixed pipe drops
to the sprinklers must be cut to help assure a perfect fit in-
stallation.
WARNINGS
The Celeste S150 Sprinklers described herein must be in-
stalled and maintained in compliance with this document,
as well as with the applicable standards of the National
Fire Protection Association, in addition to the standards
of any other authorities having jurisdiction. Failure to do
so may impair the integrity of these devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
OPERATION
The sprinkler assembly contains a small fusible solder
element. When exposed to sufficient heat from a fire, the
solder melts and enables the internal components of the
sprinkler to fall away. At this point the sprinkler activates
with the deflector dropping into its operated position (Ref-
erence Figure 1C), permitting water to flow.
TECHNICAL DATA
Approvals
UL and ULC Listed. FM Approved.
(The approvals apply only to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6GPM/psi
1/2 (80,6 LPM/bar1/2)
Temperature Rating
162°F/72°C
Adjustment:
1/2 inch (12,7 mm) vertical
Finishes
Sprinkler: White, Chrome, Black
DESIGN CRITERIA
The Celeste S150 (SIN S4801) Standard Response,
Standard Coverage, Flush Pendent Sprinklers are in-
tended for fire protection systems designed in accord-
ance with the standard installation rules recognized by
the applicable Listing or Approval agency (e.g., UL Listing
is based on NFPA 13 requirements).
INSTALLATION
The Celeste S150 must be installed in accordance with
the following instructions:
NOTES
The Protective Cap is to remain on the sprinkler during in-
stallation and until the ceiling installation is complete. The
Protective Cap must be removed to place the sprinkler in
service.
A leak tight 1/2 inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs. (9,5 to 14,0 Nm). A
maximum of 21 ft.lbs. (28,5 Nm) of torque is to be used to
install sprinklers. Higher levels of torque may distort the
sprinkler inlet with consequent leakage or impairment of
the sprinkler.
Do not attempt to compensate for insufficient adjustment
in an Escutcheon Plate by under- or over-tightening the
Sprinkler. Readjust the position of the sprinkler fitting to
suit.
1. The Sprinkler must be installed only in the pendent posi-
tion and with the Sprinkler waterway centerline perpen-
dicular to the mounting surface.
2. Install the sprinkler fitting so that the distance from the
face of the fitting to the mounting surface will be nomi-
nally 29/32 inches (23,0 mm) as shown in Figure 1A.
3. With pipe thread sealant applied to the pipe threads,
hand tighten the Sprinkler into the sprinkler fitting.
4. Wrench tighten the Sprinkler using only the #4947
Sprinkler Socket or #4948 Wrench & Socket Combina-
tion (Ref. Figure 2). The wrench recess of the #4947 is
to be applied to the sprinkler wrenching area (Ref. Fig-
ure 1A).
5. Use the “ceiling level tolerance limit” indicator on the
Protective Cap to check for proper installation height.
Relocate the sprinkler fitting as necessary.
6. After the ceiling has been completed with the 2 inch (50
mm) diameter clearance hole, push on the Escutcheon
until its flange just comes in contact with the ceiling. Do
not continue to push on the Escutcheon such that it lifts
a ceiling panel out of its normal position. If the Escutch-
eon cannot be engaged with the Sprinkler, or the the Es-
cutcheon cannot be engaged sufficiently to contact the
ceiling, relocate the sprinkler fitting as necessary.
7. Use the Protective Cap Removal Tool (Ref. Figure 3) to
remove the Protective Cap.
SIN S4801
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500 3-01
1-1.2.65
TYCO FIRE PRODUCTS
OBSOLETE
FIGURE 1
INSTALLATION OF CELESTE S150
FIGURE 2
#4947 SPRINKLER SOCKET
#4948 WRENCH & SOCKET COMINATION
FIGURE 3
#4300 PROTECTIVE CAP
REMOVAL TOOL
DRIVE
3/8" SOCKET
ACCEPTS
WREN
C
H
RECESS
WRENCH
COMBINATION
WRENCH & SOCKET
#4948
#4947
SOCKET
A
B
C
SPRINKLER
AREA
WRENCHING
TOLERANCE
CEILING LEVEL
LIMIT
FITTING
FACE OF
SPRINKLER
PROTECTIVE CAP
(23.0±4.8 mm)
29/32±3/16"
MOUNTING
SURFACE
3/32" (2.4 mm) TYP.
2-15/16" (75 mm) DIA.
IN OPERATED
POSITION
DEFLECTOR
15/32"±3/16"
(11.9±4.8 mm)
2" (50 mm) DIA.
DO NOT
OVER-TIGHTEN
COLLECTOR
HEAT
(46.0 mm)
1-13/16"
NOMINAL MAKE-IN
7/16" (11.1 mm)
1/2" NPT
STAR SPRINKLER
Page 2 1-1.2.65
OBSOLETE
CARE AND MAINTENANCE
The Celeste S150 must be maintained and serviced in ac-
cordance with the following instructions:
NOTE
Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.
Absence of an escutcheon, which is used to cover a clear-
ance hole, may delay the time to sprinkler operation in a
fire situation.
Sprinklers which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified or over-heated
sprinklers must be replaced.
Care must be exercised to avoid damage to the sprinklers
— before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench twist/slippage or the
like, must be replaced.
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the standards of any
other authorities having jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be contacted relative
to any questions.
It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.
LIMITED WARRANTY
Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Products neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.
ORDERING PROCEDURE
Please Specify:
1 Celeste S150, 5.6 K-Factor, Standard Response,
Standard Coverage Sprinkler (#4801)
2. Sprinkler Wrench
(#4947 Socket or #4948 Wrench & Socket)
3. Protective Cap Removal Tool (#4300)
Refer to Price List for for complete listing of Part Num-
bers with respect to temperature ratings, finishes, etc.