Maintenance
Model F1 Res 30 LL, 49 LL, F1 Res 58 LL and F1 Res 44
LL Sprinklers should be inspected quarterly, and the sprin-
kler system maintained in accordance with NFPA 25, 13,
13D, and 13R. Do not clean sprinkler with soap and water,
Ammonia or any other cleaning fluids. Remove dust by us-
ing a soft brush or gentle vacuuming. Remove any sprin-
kler which has been painted (other than factory applied)
or damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non-operation.
Model F1 Res 30 LL, 49 LL & 58 LL Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft2over the listed coverage area. Listed flows
as specified by the manufacturer’s technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer’s installation guide-
lines and the applicable installation standard. Where
pendent residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance
listing shall be 1” to 8” maximum. Sprinkler frame and de-
flector shall be of bronze frame construction having a ½”
NPT thread. Water seal assembly shall consist of a Teflon-
coated Belleville spring washer with top-loaded extruded
or cold head cup with 3 mm glass bulb containing no plas-
tic parts, and having a temperature rating of [155°F (68°C)]
[175°F (79°C)]. Sprinklers shall have a nominal K-factor of
3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome-plated]
[White Polyester] [Special finish– specify]. Residential pen-
dent sprinklers shall be Reliable Model F1 Res 30 LL, 49 LL
& 58 LL, SIN RA3311, RA3316 & RA3313 (Bulletin 033).
Model F1 Res 49 LL & 58 LL Recessed
Pendent/F1
Model F1 Res 30 LL, 49 LL & 58 LL Recessed
Pendent/F2
Model F1 Res 30 LL, 49 LL & 58 LL Recessed
Pendent/FP Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2over the listed coverage area. List-
ed flows as specified by the manufacturer’s technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer’s installation
guidelines and the applicable installation standard. Where
pendent residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance
listing shall be 1” to 8” maximum. Sprinkler frame and de-
flector shall be of bronze frame construction having a ½”
NPT thread. Water seal assembly shall consist of a Teflon-
coated Belleville spring washer with top-loaded extruded
or cold head cup with 3 mm glass bulb containing no plas-
tic parts, and having a temperature rating of [155°F (68°C)]
[175°F (79°C)]. Sprinklers shall have a nominal K-factor of
3.0, 4.9 & 5.8. Standard finish: [Bronze] [Chrome-plated]
[White Polyester] [Special finish– specify]. Recessed es-
cutcheon assembly shall be a steel, two-piece escutcheon
[with ½” adjustment (Model F2)] [with ¾” adjustment (Mod-
el F1)] [of push-on and thread off design with ½” adjust-
ment (Model FP)]. Standard finish shall be [brass][bright
chrome] [white painted]. Residential recessed pendent
sprinklers shall be Reliable [Model F1 Res 30 LL, 49 LL &
58 LL Recessed Pendent/F1] [Model F1 Res 30 LL, 49 LL
& 58 LL Recessed Pendent/F2] [Model F1 Res 30 LL, 49
LL & 58 LL Recessed Pendent/FP] SIN RA3311, RA3316 &
RA3313 (Bulletin 033).
Model F1 Res 30 LL, 49 LL & 58 LL CCP Pendent
(Concealed) Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft2over the listed coverage area. Listed flows
as specified by the manufacturer’s technical data sheets
are to be used. Residential sprinklers shall be installed in
conformance with the manufacturer’s installation guidelines
and the applicable installation standard. Where pendent
residential sprinklers are installed under sloped ceilings
having a pitch from [4/12] to [8/12], the sprinklers shall be
listed for such use. Sprinkler frame and deflector shall be
of bronze frame construction having a ½” NPT thread. Wa-
ter seal assembly shall consist of a Teflon-coated Belleville
spring washer with top-loaded extruded or cold head cup
with 3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of 155°F (68°C). Cover plate as-
sembly shall consist of a brass cover plate and copper al-
loy retainer flange. Method of attaching the cover plate to
the sprinkler cup shall be a push-on and thread-off design
allowing a ½” cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57°C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate is
installed. Standard cover plate finish: [White] [Custom Col-
or– specify]. ]. Concealed pendent sprinklers shall be Reli-
able Model F1 Res 30 LL, 49 LL & 58 LL CCP, SIN RA3311,
RA3316 & RA3313 (Bulletin 033).
8.