The 4.2 K-factor, Model F990 Aquarius
Residential Pendent Sprinklers are
listed by Underwriters Laboratories
Inc. and Underwriters’ Laboratories of
Canada. The listings only apply to the
service conditions indicated in the
General Technical Data and Residen-
tial Design Criteria sections.
The Model F990 Aquarius Sprinklers
are approved by the Scientific Ser-
vices Laboratory (Australia).
The Model F990 Aquarius Sprinklers
are accepted by ther City of New York
under MEA 39-92-M.
Any questions concerning an interpre-
tation of NFPA 13, 13D, or 13R sprink-
ler system design/installation stan-
dards, as well as requests for system
design/installation standards not pres-
ently covered by NFPA 13, 130, or
13R. should be addressed to the:
Secretary, Standards Council
National Fire Protection Association
Batterymarch Park
Quincy, MA 02269
WARNINGS
The Model F990 Aquarius Resi-
dential Pendent Sprinklers de-
scribed herein must be installed
and maintained in compliance
with this document, as well as
with the applicable standards of
the National Fire Protection As-
sociation, in addition to the stan-
dards of any other authorities
having jurisdiction. Failure to do
so may impair the integrity of
these devices.
Because of the above cited stipu-
lations and the varied nature of
residential type architecture,
there will be some compartment
designs which cannot be fully
sprinklered in accordance with
the recommendations of NFPA 13,
13D, or 13R. In the event of this
condition, consult the authorities
having jurisdiction for guidance
and approval.
It is the responsibility of an in-
stalling contractor to provide a
copy of this document to the owner
or his representative and, in turn,
it is the obligation of the owner to
provide a copy of this document to
a succeeding owner.
The owner is responsible for
maintaining their fire protection
system and devices in proper op-
erating condition. The installing
contractor or sprinkler manufac-
turer should be contacted relative
to any questions.
Sprinkler Assemblies:
The 4.2 K-factor, Model F990 Aquarius
Residential Pendent Sprinklers are
available in a 16O’F/71 ‘C temperature
rating and they are rated for use at a
maximum service pressure of 175 psi.
They are available with a chrome,
white, or bright brass finish. Escutch-
eon Plates are available with various
finishes and are ordered separately,
as indicated in the following sub-sec-
tion.
The F990 is shipped with a plastic Pro-
tective Cap covering the outside of the
Fusible Element and the lower portion
of the Body. The Protective Cap can
be left in position while the Sprinkler is
being installed and then it is slid off
once the ceiling installation is com-
plete and the sprinkler system is ready
to be put into service.
The nominal discharge curve for the
F990 is plotted in Figure B and it rep-
resents the flow “Q” in U.S. gallons per
minute (GPM) as determined by the
formula:
Q=K$
where the nominal sprinkler discharge
coefficient “K” = 4.2, and “p” = pres-
sure in pounds per square inch (psi).
Listing standards permit the actual
value of K to vary from 4.0 to 4.4.
The Body is bronze per ASTM 8584
(C83600 or C84400) and the Dust Cap
is polyolefin. The Heat Collectors are
copper per ASTM 8152 (Cl 1000) and
the Inner & Outer Loading Plates are
brass per ASTM B16 (CSSOOO) or
ASTM 8140 (C31400 or C31600). The
Loading Screw and two Arms are Type
302 stainless steel per ASTM A276 or
Type 303 per ASTM A582. The Disc
Spring is a chrome plated high
strength carbon steel and the Retain-
ing Ring is titanium per ASTM 8348
(Grade 5). The Gasketed Button-De-
flector consists of a brass button per
ASTM B16 (CSSOOO), brass deflector
per ASTM B36 (C22000), and a Tef-
lonf gasket.
Escutcheon Plates:
The following are the three types of
escutcheon plates that may be used
with the F990 Aquarius Sprinkler:
9 Push-on Escutcheon Plate
l Push-on Escutcheon Plate with Ex-
tension
l Clamp-on Escutcheon Plate
Figures C and D illustrate typical in-
stallations of an F990 using a Push-on
Escutcheon Plate and using a Push-on
Plate with Extension. The Push-on Es-
-2-
cutcheon Plate provides a total of l/4
inch of vertical adjustment and it is
installed by simply slipping it over the
F990 Body; however, when it is used
in conjunction with the Extension, an
additional l/4 inch of adjustment can
be obtained for a total of l/2 inch of
vertical adjustment.
When using the Push-on Plate with
Extension, the installer simply deter-
mines the approximate distance from
the ceiling mounting surface to the bot-
tom of the Heat Collector. The Exten-
sion is used when this distance (Ref.
“D” in Figure D) is greater than 7/8 inch
and, the Extension is discarded for dis-
tances of 718 inch or less.
The Push-on Escutcheon Plate and
Extension are formed from low carbon
sheet steel and they are available with
a chrome, white, or bright brass finish.
Also a color finish other than white can
be provided.
The Clamp-on Escutcheon Plates are
suitable for use with plastic pipe fire
protection systems when they are in-
stalled in accordance with the instruc-
tions given in Technical Data Sheet
TD810.
NOTE
The Push-on Escutcheon Plates
shown in Figures C and D can
NOT be used to hold the F990 in
position. The F990 must be se-
cured inposition by firmly fasten-
ing the sprinkler system piping to
the dwelling structure. If theF990
is not properly secured in posi-
tion, reaction forces resulting
from sprinkler operation could
alter its orientation and water
distribution pattern.
The 4.2 K-factor, Model F990 Aquarius
Residential Pendent Sprinklers must
only be installed and utilized in accor-
dance with the following described cri-
teria which are provided by the manu-
facturer.
NOTES
1. Residential Fire Sprinkler Sys-
tems should only be &signed
and installed by those compe-
tent and completely familiar
with automatic sprinkler sys-
tem design, installation proce-
dures, and techniques.
2. Several criteria may apply to
the installation and usage of
each sprinkler. Consequently,
it is recommended that the
sprinkler system designer re-
view and develop a working un-
derstanding of the complete
t DuPont Registered Trademark