Tyco RAPID RESPONSE RCP-1 User manual

RAPID RESPONSE
Model RCP-1 Residential Control Panel
1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar)
Worldwide
Contacts
www.tyco-fire.com
Page 1 of 12 JANUARY 2014 TFP480
General
Description
The TYCO RAPID RESPONSE Mod-
el RCP-1 Residential Control Panel is
an integrated valve manifold, air pres-
sure, and electronic control package
for controlling the release of water into
residential dry pipe sprinkler systems.
The Model RCP-1 Panel is intended for
use in one- and two- family dwellings
and mobile homes per NFPA 13D when
used with residential sprinklers that
have been listed for use in residential
dry pipe sprinkler systems.
The Model RCP-1 Panel incorporates
the Listed Model 4004R Household Fire
Warning Unit Subassembly installed
within the Model RCP-1 cabinet.
The Model RCP-1 Panel includes the
following features:
•
Pre-wired assembly containing pre-
programmed control panel, system
performance gauges, and an en-
closed compressor
• Pre-engineered riser design
• Supervised system valve system
•
Provision to trip test system without
having water ow into the system.
•
High pressure supervision for indica-
tion of a false trip or failure of the au
-
tomatic air supply cut-out switch
•
Dry contacts for remote connection
(dial-up systems or additional moni-
toring, for example)
• 48-hour battery backup
SECTIONS
General Description.......... 1
Warnings................... 2
Technical Data .............. 2
Operation .................. 3
Operator Interface ........... 6
In Case of Supervisory/
Trouble Condition............ 7
In Case of Alarm Condition .... 7
System Resetting............ 7
Installation .................10
Care and Maintenance .......11
Ordering Procedure ..........12
FIGURES, GRAPHS, AND
TABLES
Pressure Loss Graph ......... 3
Model RCP-1 Assembly....... 4
Manifold Assembly .......... 5
Operator Interface Card
(Front Side) ................. 6
Wiring Diagram.............. 8
Off-Site Remote Relays ....... 9
On-Site Remote Signal ....... 9
Battery Harness .............10
Operator Interface Card
(Back Side) .................11

TFP480
Page 2 of 12
Warnings
General
The RAPID RESPONSE Residential Dry
Pipe System described herein must be
installed and maintained by qualified
personnel in compliance with this doc-
ument, and with the applicable stan-
dards of the National Fire Protection
Association, in addition to the require-
ments of any other authorities having
jurisdiction. Failure to do so may impair
the performance of this device.
Owner Responsibility
Owners are responsible for maintain-
ing their fire protection system and
devices in proper operating condition
and in compliance with all applicable
standards and requirements. The in-
stalling contractor or sprinkler manu-
facturer should be contacted with any
questions.
Do NOT Disconnect Batteries or Turn
Off AC Power to Quiet Unwanted
Alarms.
The Model RCP-1 Panel will not oper-
ate (that is, release water or energize
alarms) if AC power is not connect-
ed, has failed, or has been interrupt-
ed for any reason AND the battery is
disconnected, drained, or improperly
connected.
Household Fire Alarm System
The use of an automatic sprinkler sys-
tem does not allow for omission of a
“Household Fire Alarm System” in-
stalled per NFPA 72. The Model RCP-1
Panel is not intended to be used as part
of a “Household Fire Alarm System”.
Electrical Hazard
Disconnect electrical field power when
making any internal adjustments or re-
pairs. Failure to do so may result in per-
sonal injury. Servicing should be per-
formed by qualified personnel.
Static Hazard
Static electricity can damage com-
ponents. Therefore, qualified person-
nel must be grounded before opening
components, installing components,
and prior to installation. Keep compo-
nents wrapped in anti-static material at
all times.
Radio Frequency Energy
This equipment generates, uses, and
can radiate radio frequency energy,
and if not installed and used in accor-
dance with this technical data sheet,
may cause interference to radio com-
munications. This equipment has been
tested and found to comply with the
limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC
Rules, that are designed to provide rea-
sonable protection against such inter-
ference when operated in a commer-
cial environment. However, operation
of this equipment in a residential area
may cause interference, in which case
the user, at their own expense, will be
required to take whatever measure may
be required to correct the interference.
System Re-Acceptance Test
To ensure proper operation, this prod-
uct must be retested by qualified per-
sonnel in accordance with the Care and
Maintenance section after any modifi-
cation, repair, or adjustment. Retesting
is required to assure that the system is
operating as intended.
Technical
Data
Approvals
The Model RCP-1 Residential Con-
trol Panel is UL Listed for use in res-
idential dry pipe sprinkler systems
installed in one and two-family dwell-
ings and mobile homes per NFPA 13D
when installed in accordance with this
document.
The Model 4004R Household Fire
Warning Unit Subassembly (Electronic
Control) installed within the Model RCP-
1 cabinet is UL and C-UL Listed.
Maximum Water Pressure
175 psi (12,1 bar)
Friction Loss
Refer to Graph A on Page 3.
Input Voltage
120 VAC, 60 Hz, 4 A
Battery Backup
Two 8.0 amp-hour 12 VDC batteries in
series provides a minimum of 48 hours
of standby and a minimum of 15 min-
utes of alarm/system release. The 15
minutes of alarm/system release pro-
vides a 150% safety factor as com-
pared to the 10-minute requirement of
NFPA 13D.
The battery size is pre-calculated
based on a maximum 1A rating for
NAC1 (Notication Appliance Circuit
-Horns), and a maximum 0.25A rating
for auxiliary devices. The battery back-
up does not provide power to the air
compressor in the event of primary 120
VAC power failure.
Battery Charger
Backup batteries provide a 48-hour
standby and 15-minute alarm/system
release. Batteries automatically re-
charge within 24 hours.
Depleted Battery Operation
The system monitors the battery volt-
age and indicates a trouble status when
the battery is outside its normal range.
There are two battery trouble levels:
Low Battery and Depleted Battery.
When Low Battery is detected, the sys-
tem sounds the tone-alert (piezo) and
ashes the trouble LED. The event must
be accepted by pressing the ACCEPT
SIGNAL KEY. If discharge continues
further, and the batteries reach the de-
pleted state, once again the tone-alert
activates and the trouble LED ashes.
Initiating Device Circuit (IDCs)
IDC1 is internally wired to the system’s
low pressure switch, and no other de-
vices are to be connected to IDC1.
IDC2, IDC3, and IDC4 are spares and
are not to be utilized.
Notification Appliance Circuit
(NACs)
NAC1 is rated at 1 A. NAC2 is a spare
and is not to be utilized.
Notification Appliances
NFPA 13D does not require the instal-
lation of a waterow alarm (notication
appliance device).
If needed, notication appliances can
be installed to indicate release of the
Model RCP-1 Panel.
When installed, notication appliances
must be installed in accordance with
the applicable requirements of NFPA
72. Per the requirements of NFPA 72,
re warning equipment for dwelling
units shall provide a sound that is au-
dible in all occupiable dwelling areas.
Auxiliary Device Power Supply
The Auxiliary Device Power Supply is
rated at 0.25A. If desired and where
the system is not otherwise monitored
by a central control station, the Auxil-
iary Device Power Supply can be used
to power a remote visual signal of an
alarm, supervisory, or trouble condition
through use of the relay contacts (Figure
5). This arrangement is especially con-
venient when the Model RCP-1 Panel is
located in an area where its Tone Alert
is not readily heard or the Operator In-
terface is not readily apparent. The cir-
cuitry, while operable by battery backup,
is not a supervised circuit.
LED/Keypad Operator Interface
•
Red Alarm LED for IDC1 and to indi-
cate system release.
•
Yellow Trouble LEDs for each IDC,
NAC, RAC, and SPM.
•
Dedicated Alarm Silence, Superviso-
ry, and Earth Fault Trouble LEDs.
• Green LED for AC Power ON.
•
KEYs for Accept, Silence, and Reset.

TFP480
Page 3 of 12
Tone Alert (Piezo)
•
On trouble conditions, the tone-
alert sounder is on steady to indicate
that a trouble has occurred. It turns
off when ACCEPT SIGNAL KEY is
pressed.
•
On alarm conditions, the tone-alert
pulses until the ACCEPT SIGNAL
KEY is pressed.
Environmental
This equipment operates normally
within the temperature range of 32°F
to 120°F (0°C to 49°C), inclusive. This
equipment operates normally under
non-condensing humidity conditions
up to 93% humidity at 90°F (32°C).
Automatically Controlled System
Air Pressure
10 to 14 psi
System Alarm (Trip/Release) Pres-
sure
8 ± 1 psi
Supervisory High Pressure
16 ± 1 psi
Assembly
The Manifold Assembly (Figure 2) is of
brass and bronze construction.
Trip Ratio
When applying a water delivery cal-
culation program for determining that
the water delivery will not exceed 15
seconds, the trip ratio of the Model
RCP-1 Panel must be entered into the
program. The trip ratio for the Model
RCP-1 Panel is determined by dividing
the available static water supply pres-
sure by 7 psi. The use of 7 psi is based
on the tolerance of the system alarm
trip/release pressure, where 7 psi is the
lowest potential trip pressure. For ex-
ample if the available static water sup-
ply pressure is 30 psi, the trip ratio is 30
divided by 7 (that is, 4.3:1). For an avail-
able 130 psi static water supply, the trip
ratio is 130 divided by 7 (that is, 18.6:1).
Operation
The system is automatically maintained
at a normal system air pressure of 10 to
14 psi (0,7 to 1,0 bar) via the Air Com-
pressor Switch/Air Compressor (Fig-
ure 2). In the standby condition, water
is prevented from entering the system
piping until the Solenoid Valve in the
Manifold Assembly is opened in re-
sponse to the electronic control.
The operation sequence is listed below.
•
The normal standby condition is AC
green light ON.
•
Closure of Main Control Valve, clo-
sure of System Control Valve, or a
high system pressure condition re-
sults in a supervisory condition
(SPM1).
During a Supervisory Condition, the
Yellow SUPERVISORY LED ashes
and the tone-alert sounds steady.
After accepting, the tone-alert si-
lences and the Yellow SUPERVISO-
RY LED stays ON until the condition
clears.
•
Opening of a sprinkler results in a
low air condition of less than nom-
inally 8 psi (0,6 bar) resulting in an
alarm condition ON IDC1, opening of
the Solenoid Valve (RAC1), and op-
eration of alarm notication devices
(NAC1).
During an Alarm Condition, the Red
ALARM LED, corresponding to Zone
or SPM in alarm, ashes and the
tone-alert pulses. After accepting,
the tone-alert silences and the Red
ALARM LED stays ON until the alarm
condition clears.
200 300 500
0,8
0,3
0,4
0,6
0,5
1,0
100
40 10020
0,2
15060 80
80
2.0
3.0
4.0
5.0
6.0
8.0
10.0
20.0
FLOW RATE IN LITRES PER MINUTE (LPM)
(1 GPM = 3,785 LPM)
FLOW RATE IN GALLONS PER MINUTE (GPM)
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0,06895 BAR)
NOMINAL PRESSURE DROP
IN POUNDS PER SQUARE INCH (PSI)
1 INCH (DN25)
1-1/2 INCH (DN40)
400
GRAPH A
MODEL RCP-1 RESIDENTIAL CONTROL PANEL
NOMINAL PRESSURE LOSS VERSUS FLOW

TFP480
Page 4 of 12
SYSTEM
WATER SUPPLY
CONNECTION
HINGED
LOCKING
PANEL DOOR
SYSTEM
DRAIN
CONNECTION
ENCLOSURE
(PANEL DOOR
NOT SHOWN)
50"
(1270 mm)
8"
(200 mm)
14"
(355 mm)
BACKUP
BATTERIES
AIR
PRESSURE
CONTROL
DISCONNECT
"ON/OFF"
SWITCH
MANIFOLD
ASSEMBLY
AIR
PRESSURE
CONTROL
Always consult local jurisdictions for water
supply criteria and requirements.
Nominal Weight:
95 LBS. (43 kg)
MOUNTING
BRACKETS
2-7/8"
(73 mm) ELECTRONIC
CONTROL
1-3/4"
(45 mm)
5"
(127 mm)
OPERATOR
INTERFACE
WINDOW
OPERATOR
INTERFACE
SYSTEM
AIR SUPPLY
PRESSURE
GAUGE
SYSTEM
WATER SUPPLY
PRESSURE
GAUGE
OUTLET
CONNECTION
TO DRY PIPE FIRE
PROTECTION
SYSTEM
*
*
FRONTLEFT SIDE
FIGURE 1
MODEL RCP-1 RESIDENTIAL CONTROL PANEL
ASSEMBLY

TFP480
Page 5 of 12
AIR
COMPRESSOR
1/20 HP, 115 VAC
PRESET
10 PSI MIN.
14 PSI MAX.
MAIN
CONTROL VALVE
(NORMALLY
OPEN)
SOLENOID
VALVE
(NORMALLY
CLOSED UNTIL
ENERGIZED)
WATER SUPPLY
SYSTEM INLET
CONNECTION
(1 or 1-1/2 INCH NPT)
SYSTEM
CONTROL VALVE
(NORMALLY
OPEN)
DRAIN OUTLET
CONNECTION
(1/2 INCH NPT)
DRAIN VALVE
(NORMALLY
CLOSED)
PRESSURE SWITCH,
POTTER ELECTRIC PS10-2:
INCREASE 16±1 PSI
DECREASE 8±1 PSI
TUBING
TO SYSTEM
WATER SUPPLY
PRESSURE
GAUGE
FLOW
TUBING
TO SYSTEM
AIR SUPPLY
PRESSURE
GAUGE
SPRING LOADED
CHECK VALVE
SPRING LOADED
CHECK VALVE
FLOW
TEST VALVE
(NORMALLY
CLOSED)
AIR COMPRESSOR
SWITCH TO AIR
COMPRESSOR
WIRING HARNESS
DRY PIPE
FIRE PROTECTION
SYSTEM OUTLET
CONNECTION
(1 or 1-1/2 INCH NPT)
AIR
COMPRESSOR
SWITCH
CUT-IN: 10 PSI
CUT-OUT: 14 PSI
FIGURE 2
MODEL RCP-1 RESIDENTIAL CONTROL
MANIFOLD ASSEMBLY

TFP480
Page 6 of 12
Operator
Interface
The Model RCP-1 Panel uses LEDs and
KEYs as its primary means of display-
ing status information and controlling
the system. It allows the occupants to
monitor the status of the Model RCP-1
Panel and its circuits.
The LEDs are located along the left
and right sides of the Operator Inter-
face (Figure 3). Three KEYs are located
along the lower edge of the Operator
Interface.
LEDs
• ALARM LEDs
A ashing red LED adjacent to the
SPRINKLER (IDC1) indicates an
alarm.
• TROUBLE LEDs
A ashing yellow Trouble LED for one
of the IDCs, NACs, or RACs indi-
cates the presence of a circuit break
or ground within a system point, or
somewhere in the wiring between the
control panel and one of its points.
• SUPERVISORY LED
A ashing yellow SUPERVISORY LED
indicates a problem with the condi-
tion of the sprinkler system controls
or normal status (for example, closed
valve position for Main Control Valve,
closed valve position for System
Control Valve, or high air condition).
• SYSTEM TROUBLE LED
When a TROUBLE condition occurs,
the SYSTEM TROUBLE LED ash-
es until accepted. When accepted, it
changes from ashing to steady.
• AC POWER LED
When lit steady, the Green AC
POWER LED indicates that the Elec-
tronic Control of the Model RCP-1
Panel is receiving AC power that is
within the specied range.
If the LED is not lit and the Panel is
still functioning, the Electronic Con-
trol is using battery power to oper-
ate. The cause for loss of AC Power
should be determined and correct-
ed. The system is in a normal stand-
by condition when only the Green AC
POWER LED is ON.
• SYSTEM RELEASED LED
The Red SYSTEM RELEASED LED
turns on steady when the RAC circuit
is activated. Activation of the RAC cir-
cuit energizes the Solenoid Valve to
permit water to enter the sprinkler
system piping. RAC1 is utilized, and
RAC2 is spare.
• EARTH FAULT LED
The Yellow EARTH FAULT LED turns
on steady when there is a wiring fault
from circuit to Earth.
• Lamp (LED) Test
A lamp (LED) test can be performed
by pressing and holding the AC-
CEPT SIGNAL KEY for a duration
of ve seconds. Performing a lamp
test lights all LEDs on the system
and veries that all system LEDs are
functioning.
Panel
Reference Description
IDC Initiating Device Circuit
(Low Air Pressure)
NAC Notification Appliance Circuit
(Optional Notication Appliance)
RAC Releasing Appliance Circuit
(Solenoid Valve)
SPM
Special Purpose Monitor
(Main Control Valve Closure,
System Control Valve Closure, or
High System Air Pressure)
KEYS
LEDs
ACCEPT
SIGNAL
SIGNAL
SILENCE
SYSTEM
RESET
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
ALARM
TROUBLE
ALARM SILENCED
AC POWER
SUPERVISORY (SMP1)
SYSTEM TROUBLE
(IDC4)
SPARE (RAC2) TROUBLE
SYSTEM RELEASED
EARTH FAULT
SPARE
SPARE
SPARE (NAC2) TROUBLE
(NAC1) TROUBLE
(RAC1) TROUBLE
SPRINKLER
SPARE
SPARE
(IDC3)
SPARE
(IDC2)
(IDC1)
SPARE
(SMP2)
(SMP1)
DRY PIPE SYSTEM
TROUBLE
ALARM
TROUBLE
FIGURE 3
OPERATOR INTERFACE CARD (FRONT SIDE)
DRY PIPE SYSTEM MODE

TFP480
Page 7 of 12
KEYS
• ACCEPT SIGNAL KEY
The system LEDs (ALARM, SUPER-
VISORY, TROUBLE) ash to indi-
cate the presence of an unaccepted
alarm, supervisory, or trouble condi-
tion somewhere in the system. The
ACCEPT SIGNAL KEY acknowledg-
es the presence of an alarm, super-
visory, or trouble condition.
By momentarily pressing the AC-
CEPT SIGNAL KEY, the ashing LED
turns steady. The ACCEPT SIGNAL
KEY is used to acknowledge every
abnormal status present in the sys-
tem. For example, if there are two
red alarms and three yellow troubles,
the ACCEPT SIGNAL KEY must be
pressed ve times.
The Panel’s tone-alert turns off when
all abnormal conditions are accepted.
• SIGNAL SILENCE KEY
Pressing the SIGNAL SILENCE KEY
silences the audible notication de-
vices (horns). The Yellow ALARM SI-
LENCED LED lights to indicate that
an alarm is still active even if the au-
dible alarms have been silenced.
• SYSTEM RESET KEY
Pressing the SYSTEM RESET KEY
directs the Panel to reset all at-
tached devices and clear all accept-
ed alarms, troubles, and supervisory
conditions. All alarms must rst be
accepted via the ACCEPT SIGNAL
KEY and all devices must be reset
(that is, normal system air pressure
is re-established).
Note: After pressing the SYSTEM
RESET KEY, the panel requires ap-
proximately fifteen seconds to clear.
In Case of
Supervisory/
Trouble
Condition
Step 1. Verify that a re condition does
not exist.
Step 2. Close the Main Control Valve
to prevent inadvertent water ow into
the system.
Step 3. Acknowledge the superviso-
ry/trouble notication by momentarily
pressing the ACCEPT SIGNAL KEY.
Doing so silences the tone-alert.
Step 4. Determine and correct cause
of supervisory/trouble notication, for
example:
• Loss of primary 120 VAC power
• Low battery condition
• High air pressure
•
System or main control valve closure
Step 5. Reset the system as soon as
possible.
In Case of
Alarm Condition
Step 1. Verify that a re condition ex-
ists and take appropriate action (that
is, evacuate the building and call re
department).
Step 2. After the re is extinguished,
reset the system.
If a re condition does not exist and pri-
or to resetting the system, silence the
alarms as follows:
•
First, momentarily press the ACCEPT
SIGNAL KEY a sufcient number of
times to stop the tone-alert.
• Second, momentarily press the SIG-
NAL SILENCE KEY.
System
Resetting
Step 1. Use the ACCEPT SIGNAL KEY
to accept every abnormal status pres-
ent in the system.
For example, when two red ALARM
and three yellow TROUBLE conditions
are present, the ACCEPT SIGNAL KEY
must be pressed ve times. The Panel’s
tone-alert turns off when all abnormal
conditions are accepted.
Step 2. Silence the alarms by pressing
the SIGNAL SILENCE KEY.
Step 3. Close the Main Control Valve.
Step 4. Place the Air Compressor Dis-
connect Switch to the OFF position.
Step 5. Open the Drain and Flow Test
Valves.
Step 6. Replace operated sprinklers.
Step 7. After the system drains com-
pletely, close the Drain and Flow Test
Valves.
Step 8. Place the Air Compressor Dis-
connect Switch to the ON position and
allow the system to automatically rees-
tablish its normal air pressure of 10 to
14 psi.
Step 9. Reset the Electronic Control by
pressing the SYSTEM RESET KEY.
Wait approximately fteen seconds for
the Electronic Control to clear.
A supervisory signal will remain be-
cause the Main Control Valve is still
closed.
Press the ACCEPT SIGNAL KEY to ac-
cept the supervisory signal and silence
the tone-alert.
Step 10. Slowly open the Main Control
Valve. (Opening the Control Valve too
quickly may result in activation of the
pressure switch.)
The supervisory signal should clear and
the system is now set for service.
NOTICE
After pressing the SYSTEM RESET
KEY, the panel requires approximately
fifteen seconds to clear.

TFP480
Page 8 of 12
SELECT NORMALLY OPEN
SELECT NORMALLY OPEN
SELECT NORMALLY OPEN
OR NORMALLY CLOSED
CRIMPED ON
CONNECTOR
NYLON
INSULATED
RING
GROUND
SWITCH
COMPRESSOR
DISCONNECT
120 VAC
WIRED
FIELD
BLK
RED
(NEUTRAL)
CRIMPED ON
CONNECTORS
(LINE)
-+-+
POS NEG POS NEG
24 VDC
+-
BATTERIES
TWIST-ON WIRE
CONNECTORS
CONNECTED
FIELD
RELAY #3
OR NORMALLY CLOSED
RELAY #2
OR NORMALLY CLOSED
AIR
M
COMPRESSOR
TROUBLE RELAY
1/2 W1/2 W
10k Ω
1/2 W
10k Ω
1/2 W
3.3k Ω
1/2 W
3.3k Ω 3.3k Ω
RAC 1 RAC 2
-+ -+
NAC 1 NAC 2
-+ -+
12-18 AWG
1A MAX.
NOTIFICATION
CIRCUIT
IDC 2IDC 1
+ -+-
IDC 4IDC 3
-+ -+
1/2 W
3.3k Ω
SPM 2SPM 1
+ +- -+- R
SOLENOID
PRE-CONNECTED
YELRED
(TYPICAL)
430687
TWIST-ON WIRE
CONNECTOR
RED
SUPERVISION
COIL
MODULE
YEL
S
BLKBLK
PRESSURE
LOW AIR
@ 8 PSI
BLK
VALVE
CONTROL
MAIN
VALVE
CONTROL
SYSTEM
PRE-CONNECTED
LISTED
PRE-CONNECTED
1/2 W
BLK
ANNUNCIATORS
10k Ω
FIELD WIRED
1/2 W
3.3k Ω
HIGH AIR
@ 20 PSI
SWITCH
PRESSURE
1/2 W
3.3k
Ω
USE
DO NOT
24 V POWER
0.25A MAX.
AUXILIARY
DO NOT
USE
DO NOT
USE
DO NOT
USE
DO NOT
USE
OPTIONAL
FIGURE 4
MODEL RCP-1 RESIDENTIAL CONTROL PANEL
ELECTRONIC CONTROL WIRING DIAGRAM

TFP480
Page 9 of 12
TBL
TROUBLE RELAY (SELECT NORMALLY
OPEN OR NORMALLY CLOSED)
RELAY #2 (SELECT NORMALLY
OPEN OR NORMALLY CLOSED)
RELAY #3 (SELECT NORMALLY
OPEN OR NORMALLY CLOSED)
ALARM
SUPERVISORY
RELAY #2 JUMPER
TROUBLE RELAY JUMPER
RELAY #3 JUMPER
#2
#3
JUMPER LEFT
NORMALLY CLOSED
JUMPER RIGHT
NORMALLY OPEN
JUMPERS TO SELECT
NORMALLY OPEN OR
CLOSED CONTACTS
LOWER RIGHT-HAND CORNER
OF ELECTRONIC CONTROL
JUMPER SELECTION OPTIONS
RELAY
CONTACTS
SET ALL
RELAY JUMPERS TO
NORMALLY OPEN
(JUMPER RIGHT)
+-
AUXILIARY
POWER
TERMINALS
UPPER
RIGHT-HAND
CORNER OF
ELECTRONIC
CONTROL
LOWER
RIGHT-HAND
CORNER OF
ELECTRONIC
CONTROL
ADD
JUMPERS AS
SHOWN
REMOTE SIGNAL:
24 VDC, 0.25 AMP
MAXIMUM (LOCATE
CONSPICUOUSLY
IN LIVING SPACE;
YELLOW LIGHT
RECOMMENDED)
NOTICE:
FOR ON-SITE
REMOTE
SUPERVISORY/
TROUBLE SIGNAL
CONNECTIONS
ONLY
FIGURE 5
ELECTRONIC CONTROL
OFF-SITE REMOTE RELAYS
FIGURE 6
ELECTRONIC CONTROL
ON-SITE REMOTE SIGNAL

TFP480
Page 10 of 12
Installation
The RAPID RESPONSE Model RCP-
1 Residential Control Panel described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa
-
tion, in addition to the requirements of
any other authorities having jurisdiction.
Failure to do so may impair the perfor
-
mance of this device.
The Model RCP-1 Residential Control
Panel may be surface-mounted or re-
cessed-mounted with a separately or-
dered bezel. In either case the Model
RCP-1 Panel must be located in an area
not subject to freezing.
Field connections are as follows:
• Water Supply Line
• System Riser Line
• Drain Line
• Electrical
NOTICE
Do not attempt to reprogram the Model
RCP-1 Panel. If assistance is required,
contact Technical Services at Tyco Fire
Suppression & Building Products.
Electrical Field Wiring
The Electronic Control has been
shipped with resistors located across
all required contact points.
NOTICE
Remove resistors only when instruct-
ed to do so. Failure to do so may lead
to improper conditions or failure of
the Model RCP-1 Panel to function
properly.
The cover is electrically bonded to the
enclosure ground terminal by means of
an 18 AWG conductor. Do not remove
the electrical bond.
Do not place any wiring in contact with
CPVC pipe and fittings. Plasticizers,
such as those found in flexible wire in-
sulation, can damage the pipe and fit-
tings through contact resulting in dam-
age/failure to the system.
Wiring Notification Appliances
(Optional)
Notication appliances (horns) are op-
tional for waterow alarms (that is, re-
lease of water into the system).
Adhere to the following guidelines when
wiring NAC1:
•
Remove the 10K, 1/2 W resistor from
the NAC1 terminals.
•
All wiring must be from 12 AWG
(maximum) to 18 AWG (minimum).
•
Conductors must test free of all
grounds.
•
Terminal designations “+” or “-” are
for alarm state.
•
Maximum alarm current is 1A, and
the maximum distance from the
Model RCP-1 Panel to the last de-
vice is as follows:
- 210 feet for 18 AWG wiring
- 334 feet for 16 AWG wiring
- 532 feet for 14 AWG wiring
- 845 feet for 12 AWG wiring.
•
Terminate circuit with a 10K, 1/2 W
end-of-line resistor (Figure 4).
Wiring Relay Connections (Op-
tional)
These connections provide optional
monitoring by a central control station
or for a remote signal on premise. Ad-
here to the following guidelines when
wiring relay modules:
•
All wiring must be from 12 AWG
(maximum) to 18 AWG (minimum).
•
Conductors must test free of all
grounds.
•
Relay circuits are rated for 2 A at 30
VDC, pilot duty (0.35 power factor).
• Circuit is not supervised.
•
All relays are single pole, double
throw. Refer to Figure 5 to set select-
able jumpers for normally open or
normally closed jumpers.
•
Refer to Figure 6 for recommenda-
tion on wiring a remote signal on
premise. As shown, an alarm, super-
visory, or trouble signal will result in
activation of the remote signal.
Wiring AC Power and Batteries
Step 1. Close the Main Control Valve
and open the Main Drain Valve.
Step 2. Place the Air Compressor Dis-
connect switch in the OFF position.
Step 3. Connect the batteries using the
provided harness per Figure 7. Leave
one of the connections unconnected as
shown until directed otherwise.
Step 4. At the power supply junction
box, connect the Model RCP-1 Panel
to a dedicated branch circuit per all lo-
cal codes.
IDC1 will go into alarm. Silence the
alarm by pressing the SIGNAL SI-
LENCE KEY Accept the alarm condi-
tion by momentarily pressing the AC-
CEPT SIGNAL KEY.
System Trouble will be indicated for
lack of the battery connection. Accept
the trouble condition by momentarily
pressing the ACCEPT SIGNAL KEY.
A Supervisory Condition will be indicat
-
ed due to the Main Control Valve being
closed. Acknowledge the supervisory
condition by momentarily pressing the
ACCEPT SIGNAL KEY.
Step 5. Connect the remaining battery
connection.
The system may now be set for service.
TO
ELECTRONIC
CONTROL
BLACK
LEAD
WHITE
LEAD
(SERIES
JUMPER)
RED LEAD
BATTERIES
FIGURE 7
BATTERY HARNESS

TFP480
Page 11 of 12
Care and
Maintenance
Before closing a fire protection system
control valve for inspection or mainte-
nance work on the fire protection sys-
tem that it controls, obtain permission
to shut down the effected fire protec-
tion system from the proper authorities
and notify all personnel who may be af-
fected by this action.
The following inspection/test proce-
dures will result in operation of the as-
sociated alarms. Notify the proper au-
thorities and advise those responsible
for monitoring proprietary and/or cen-
tral station alarms.
After placing a fire protection system
in service, notify proper authorities and
advise those responsible for monitor-
ing proprietary and/or central station
alarms.
The following inspection/test procedure
for the RAPID RESPONSE Model RCP-
1 Residential Control Panel must be
performed as indicated, in addition to
any specic requirements of the NFPA.
Any impairment must be immediately
corrected.
The owner responsible for the inspec-
tion, testing, and maintenance of their
re protection system and devices in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa
-
tion (e.g., NFPA 25), in addition to the
requirements of any authority having
jurisdiction. The installing contractor or
product manufacturer should be con-
tacted relative to any questions.
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
maintained by a qualied Inspection
Service in accordance with local re-
quirements and/or national codes.
Inspection/Test Procedure
The Model RCP-1 Panel can be in-
spected and tested without having to
ow water into the system piping. The
inspection and testing, in accordance
with the requirements of NFPA 25, must
be performed annually.
General Inspection/Test
Step 1. Verify the Air Pressure Gauge
indicates a system air pressure of 10
to 14 psi.
Step 2. Verify the Operator Interface of
the Electronic Control only indicates a
green light for AC Power.
Step 3. Open and then close the Flow
Test Valve. The Water Supply Gauge
should drop to a previously noted re-
sidual pressure and then return to the
normal static pressure.
Step 4. Perform a lamp test by press-
ing and holding the ACCEPT SIGNAL
KEY for a duration of ve seconds. Ver-
ify that all system LEDs are functioning.
Trip Test
Step 1. Close the System Control Valve
and accept the supervisory alarm at the
Operator Interface by pressing the AC-
CEPT SIGNAL KEY.
Step 2. Partially open the Drain Valve
to relieve air pressure. When the sys-
tem trips (releases), completely open
the Drain Valve.
•
Note that the Operator Interface
IDC1 indicates alarm when the air
pressure gauge indicates nominal-
ly 8 psi.
•
Note that the Operator Interface indi-
cates system released.
•
Note that water is discharging from
the drain line.
Step 3. Reset the Model RCP-1 Pan-
el following the appropriate resetting
instructions.
SYSTEM PROGRAMMING MODE
Check
If a malfunction of the Electronic Con-
trol is suspected, verify the pre-pro-
gramming of the panel as follows:
Step 1. With reference to Figure 8, re-
move the Operator Interface card and
reinsert it so that the SYSTEM PRO-
GRAMMING MODE information listed
on the card’s back side faces front.
Step 2. Place the PROGRAM SWITCH
(Figure 8) to the ON position and then
momentarily press the ACCEPT SIG-
NAL KEY to accept the resulting pro-
gramming mode trouble.
Step 3. Press the ACCEPT SIG-
NAL KEY to scroll through MODES 1
through 10 and verify that the POSI-
TION 1 through 10 lights up as follows:
• MODE 1: POSITION 6 for Dry Pipe
• MODE 1/3: POSITION 1
•
MODE 2: POSITION 1 for Class B Ini-
tiating Circuit Style
•
MODE 3: POSITION 1 for 0-Second
Automatic Time Release Delay
•
MODE 4: POSITION 1 for No RAC
Cutout Timer
•
MODE 5: POSITION 1 for 0 Second
Manual Release Time Delay
•
MODE 6: POSITION 1 for Immediate
Abort Release Time Delay
•
MODE 7: POSITION 1 for Temporal
NAC Coding
SYSTEM PROGRAMMING MODE
ACCEPT
SIGNAL
MODE 10
MODE 9
MODE 8
MODE 7
MODE 6
MODE 5
MODE 4
MODE 3
MODE 1
MODE 2
SIGNAL
SILENCE
SYSTEM
RESET
POSITION 10
POSITION 9
POSITION 7
POSITION 8
POSITION 6
POSITION 5
POSITION 4
POSITION 3
POSITION 1
POSITION 2
INTERFACE
CARD
ON
PROGRAM
SWITCH
FIGURE 8
OPERATOR INTERFACE CARD (BACK SIDE)
SYSTEM PROGRAMMING MODE

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP480
Page 12 of 12
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
•
MODE 8: POSITION 1 for On Until Si-
lenced NAC Operation
•
MODE 9: POSITION 2 for Superviso-
ry Latching
•
MODE 10: POSITION 3 for Standard
(LED-Piezo) Supervisory Notication
Step 4. If a POSITION must be correct-
ed for a given MODE number, press the
SYSTEM RESET KEY to scroll through
the positions. When at the correct po-
sition, press the ACCEPT SIGNAL KEY
to conrm a selection and scroll to the
next MODE number.
Step 5. Upon completing the program-
ming check, place the PROGRAM
SWITCH in the OFF position, and then
return the Operator Interface card to its
normal position.
NOTICE
Exercise care to ensure that all MODES
are restored to their proper settings.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name, including de-
scription and Part Number (P/N).
Model RCP-1 Panel
Specify: (size) Model RCP-1 Residential
Control Panel and P/N (specify):
1 Inch .............. 52-310-2-601
1-1/2 Inch ...........52-310-2-602
Separately Ordered Parts
Specify: Bezel for use with the Model
RCP-1 Residential Control Panel,
P/N 52-310-2-603
Replacement Parts
Specify: 8.0 Amp Batteries BT-80
for use with the Model RCP-1
Residential Control Panel,
P/N 2656
Other manuals for RAPID RESPONSE RCP-1
1
Table of contents
Other Tyco Control Panel manuals

Tyco
Tyco AutoPulse Z-10 User manual

Tyco
Tyco T1200 Mounting instructions

Tyco
Tyco MC-2 User manual

Tyco
Tyco DSG Touch SCW9067 User manual

Tyco
Tyco PowerSeries Pro HS3032 User manual

Tyco
Tyco Bentel Security ABSOLUTA Instruction manual

Tyco
Tyco AutoPulse Z-20 User manual

Tyco
Tyco RAPID RESPONSE RCP-1 User manual

Tyco
Tyco T1200-C Series User guide