Tyco T1200-C Series User guide

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 1 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
TYCO T1200-C
MarineFire Detection/Alarm Control Panel and Repeater
Application Guide

T1200
MARINEC-P-A
3 02/14
PAGE 2 of 67
List of Contents
1. LIST OF FIGURES...................................................3
2. LIST OF TABLES ....................................................3
3. INTRODUCTION......................................................4
4. GENERAL DESCRIPTION.........................................4
4.1 CABINET SPECIFICATIONS.............................4
4.1.1 ORDER CODES &DESCRIPTIONS .................7
4.1.2 REPLACEMENT PART ORDER CODES AND
DESCRIPTIONS.............................................8
4.1.3 OPTIONAL LANGUAGE DISPLAY INSERTS.......9
4.1.4 OPTIONAL DOOR STAY ASSEMBLY...............9
4.2 FIRE DETECTION AND ALARM PANEL
DESCRIPTION.............................................10
4.2.1 C1626 4ZONE MOTHERBOARD .................13
4.2.2 C1627 16 ZONE MOTHERBOARD ...............13
4.2.3 C1632 32 ZONE EXPANSION BOARD..........13
4.2.4 C1628 16-ZONE DISPLAY BOARD AND C1629
32-ZONE DISPLAY BOARD ..........................13
4.2.5 DISPLAY OVERLAY AND INSERTS................13
4.2.6 C1631 REPEATER INTERFACE BOARD........13
4.2.7 C1665 MUSTER INTERFACE BOARD...........13
4.2.8 OUTPUT EXPANSION SYSTEM ....................13
4.2.9 C1630 OUTPUT INTERFACE.......................14
4.2.10 C1714 –VDR OUTPUT MODULE .............14
4.3 T1200-C REPEATER DESCRIPTION.............14
5. FUNCTIONAL SPECIFICATION ...............................16
5.1 T1200 PANEL INPUT/OUTPUT LIST..............16
5.2 FEATURES LIST ..........................................17
6. T1204 MOTHERBOARD (C1626) FEATURES.........21
7. T1216-C/T1232-C MOTHERBOARD (C1627)
FEATURES........................................................22
8. T1200-C1632 16-ZONE EXPANSION BOARD
FEATURES........................................................23
9. T1200-C DISPLAY BOARD FEATURES..................23
10. C1714 VOYAGE DATA RECORDER INTERFACE
MODULE...........................................................24
10.1 C1714 VDR INTERFACE MODULE
DESCRIPTION.............................................24
10.2 VDR RS422 OUTPUT SENTENCE STRUCTURE
.................................................................26
10.2.1 ZONAL FIRE SENTENCE STRUCTURE.....26
10.2.2 ZONAL FAULT SENTENCE STRUCTURE..27
10.2.3 GENERAL FAULT SENTENCE STRUCTURE
.................................................................28
10.2.4 MAINS FAULT SENTENCE STRUCTURE ..28
10.2.5 BATTERY FAULT SENTENCE STRUCTURE
.................................................................28
10.2.6 ZONAL DISABLEMENT SENTENCE
STRUCTURE...............................................29
10.2.7 STATUS MESSAGE SENTENCE
STRUCTURE...............................................30
10.2.8 HOURLY STATUS MESSAGES...........31
10.2.9 COMMS FAULT SENTENCE STRUCTURE 32
10.2.10 PANEL RESET SENTENCE STRUCTURE33
11. C1630 OUTPUT EXPANSION INTERFACE FEATURES
........................................................................34
12. C1631 REPEATER INTERFACE BOARD FEATURES
........................................................................34
13. C1665 MUSTER INTERFACE BOARD FEATURES..34
14. POWER SUPPLIES............................................. 35
14.1 GENERAL................................................... 35
14.2 T1204A1 110V AC AND T1204A2 230V AC
MAINS POWERED PSUS.............................. 35
14.2.1 SUPPLY INPUT ........................................ 35
14.2.2 SUPPLY OUTPUT..................................... 35
14.2.3 FUSING .................................................. 35
14.2.4 BATTERY CHARGER................................ 35
14.2.5 BATTERY MONITORING............................ 35
14.2.6 VISUAL INDICATIONS ............................... 35
14.2.7 FAULT CONDITIONS................................. 36
14.2.8 BATTERY DISCONNECT ........................... 36
14.3 PS40-1-09 AND PS136-1-09 POWER
SUPPLIES .................................................. 36
14.3.1 PS40-1-09, T1204 24 VDC PSU............ 36
14.3.2 PS136-1-09, T1216-C AND T1232-C 4A
110/230VAC PSU ..................................... 36
14.3.3 INPUT SUPPLIES ..................................... 36
14.3.4 FUSING .................................................. 36
14.3.5 DC OUTPUT ........................................... 36
14.3.6 BATTERY CHARGER................................ 37
14.3.7 PS40-1-09 AND PS136-1-09
TEMPERATURE COMPENSATION.................. 37
14.3.8 PS40-1-09 AND PS136-1-09 CHARGER
MONITOR................................................... 37
14.3.9 PS40-1-09 AND PS136-1-09 BATTERY
HEALTH FUNCTIONS................................... 37
14.3.10 PS40-1-09 AND PS136-1-09 BATTERY
TEST......................................................... 37
14.3.11 PS40-1-09 AND PS136-1-09 BATTERY
DISCONNECT ............................................. 37
14.3.12 PS40-1-09 AND PS136-1-09 INDICATIONS
ON THE PSU.............................................. 37
14.4 PS40-1-09 AND PS136-1-09 FAULT OUTPUTS
................................................................. 37
14.4.1 SAFETY EARTH....................................... 37
14.5 PS40-1-09 &PS136-1-09 MECHANICAL
PROTECTION.............................................. 37
14.5.1 T1200 POWER SUPPLY FEATURES AND
CONNECTIONS........................................... 38
15. COMPATIBLE FIELD DEVICES............................. 39
15.1 FIELD DEVICE PART NUMBERS ................... 39
16. OVERVIEW OF USER FUNCTIONS....................... 41
16.1 USER INDICATIONS..................................... 41
16.2 USER CONTROLS....................................... 42
16.3 SELECTION OF ZONES OR OUTPUTS FOR
DISABLEMENT,ENABLEMENT OR TEST........ 43
16.4 DISABLEMENT/RE-ENABLEMENT OF DETECTION
ZONES AND OUTPUTS ................................ 43
16.5 DETECTOR ZONE ONE MAN TEST............... 43
16.6 ALARM SOUNDER ONE MAN TEST............... 43
16.7 TURNING THE DELAY MODE ON/OFF............ 43
16.8 OVERRIDING THE DELAY MODE................... 44
16.9 ADJUSTABLE DISPLAY LED BRIGHTNESS .... 44
17. OVERVIEW OF ENGINEERS FUNCTIONS .............. 44
17.1 ENGINEER’S CONFIGURATION PROCESS....... 44
17.2 ZONE/OUTPUT SELECTION.......................... 44
17.3 CONFIGURE DELAYED OUTPUTS................. 44
17.4 CONFIGURE MACHINERY SPACE ZONES...... 45

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 3 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
17.5 CONFIGURE NON-LATCHING ZONES............ 45
17.6 CONFIGURE INTRINSICALLY SAFE ZONES .... 45
17.6.1 MIXED I.S. AND NON-I.S. ZONES ............. 45
17.7 THE DELAY MODE FEATURE....................... 46
17.7.1SELECTION OF OUTPUTS TO BE DELAYED. 46
17.8 SELECTABLE ZONAL OR GENERAL ALARM
SOUNDER OPERATION ................................ 46
17.9 PULSE NON-ALARM ZONES ........................ 46
17.10 ALARMS IN CREW AREAS............................ 46
17.11 DELAY RESTART DIL SWITCH..................... 46
17.12 SELECTABLE MUSTER/MANUAL FIRE ALARM
SOUNDER OPERATION ................................ 46
17.13 INHIBIT FIRE PROTECTION ON NON-LATCHED
ZONE DIL SWITCH ..................................... 47
17.14 DELAY ALARM SILENCE AND RESET CONTROLS
DIL SWITCH............................................... 47
17.15 DELAY ON AUTO DIL SWITCH .................... 47
17.16 ALARMS ON EVAC ONLY DIL SWITCH.......... 47
17.17 SILENCE BEFORE RESET DIL SWITCH ......... 47
17.18 CONTINUOUS OR PULSED SOUNDER
OPERATION DIL SWITCH ............................ 47
17.19 SILENT ZONE TEST DIL SWITCH ................. 47
17.20 BUZZER DISABLE DIL SWITCH .................... 47
17.21 LATCHED FAULTS DIL SWITCH.................... 47
17.22 REPEATER CONFIGURATION ....................... 47
17.23 OUTPUT RELAY CONFIGURATION................ 47
17.24 EARTH FAULT MONITORING......................... 48
18. PANEL REPEATERS........................................... 48
18.1 REPEATER USER INDICATIONS.................... 49
18.2 REPEATER USER CONTROLS...................... 49
19. CIRCUIT CONNECTION DETAILS ......................... 50
19.1 T1204 (C1626) 4-ZONE PANEL TERMINATION
DETAILS .................................................... 50
19.2 T1216-C AND T1232-C (C1627) 16-ZONE
MOTHERBOARD TERMINATION DETAILS....... 50
19.3 32-ZONE EXPANSION BOARD TERMINATION
DETAILS .................................................... 50
19.4 AUXILIARY SUPPLY..................................... 51
19.5 FIRE PROTECTION,FIRE OUTPUT AND FAULT
OUTPUT SIGNAL OUTPUTS ......................... 51
19.6 USE OF AUXILIARY INPUTS.......................... 51
19.7 SOUNDER CIRCUITS................................... 51
19.8 ELECTRICAL DESIGN OF DETECTION ZONES 53
19.8.1 MAXIMUM NUMBER OF DEVICES ON A ZONE
................................................................. 53
19.8.2 INTRINSICALLY SAFE ZONES.................... 53
19.9 REPEATER PANEL AND REPEATER MUSTER
WIRING...................................................... 55
20. MECHANICAL,ELECTRICAL AND ENVIRONMENTAL
SPECIFICATION................................................. 56
21. T1200-C INPUT AND OUTPUT SPECIFICATION .... 59
22. APPENDIX......................................................... 62
22.1 EN54 OPTIONAL FUNCTIONS WITH
REQUIREMENTS ......................................... 62
22.2 ANCILLARY FUNCTIONS NOT REQUIRED BY
EN54........................................................ 62
22.3 POWER SUPPLY LOAD CALCULATION.......... 63
22.4 MINIMUM STANDBY BATTERY CAPACITY
CALCULATION ............................................ 63
22.5 A1466 INTERFACE RELAY .......................... 65
22.6 PANEL CONFIGURATION DESIGN CHART...... 66
1. List of Figures
FIGURE 1–4-ZONE PANEL ENCLOSURE EXTERNAL
VIEW........................................................5
FIGURE 2–CONSOLE MOUNT PANEL ENCLOSURES
EXTERNAL VIEW .......................................6
FIGURE 3–BATTERY BOX .........................................7
FIGURE 4–T1204 PANEL –GENERAL ASSEMBLY.....10
FIGURE 5–T1216-C PANEL –GENERAL ASSEMBLY.11
FIGURE 6–T1232-C PANEL –GENERAL ASSEMBLY.12
FIGURE 7–T1216R-C REPEATER –GENERAL
ASSEMBLY.............................................15
FIGURE 8–C1626 MOTHERBOARD LAYOUT..............21
FIGURE 9–C1627 MOTHERBOARD LAYOUT..............22
FIGURE 10 –C1632 16-ZONE EXPANSION BOARD.....23
FIGURE 11 –REAR RIGHT HAND SIDE OF DISPLAY PCB
.............................................................23
FIGURE 12 –C1714 VDR INTERFACE MODULE ........24
FIGURE 13 –C1630 OUTPUT EXPANSION INTERFACE
.............................................................34
FIGURE 14 –C1631 REPEATER INTERFACE BOARD..34
FIGURE 15 –C1665 MUSTER INTERFACE BOARD .....34
FIGURE 16 –PS40-1-09 1.5 AMP 24VOLT DC POWER
SUPPLY LAYOUT ....................................38
FIGURE 17 –PS136-1-09 4AMP 110/230VAC POWER
SUPPLY LAYOUT ....................................38
FIGURE 18 –REPEATER DISPLAY.............................48
FIGURE 19 –C1626 FIELD TERMINATIONS ................50
FIGURE 20 –C1627 FIELD TERMINATIONS ................50
FIGURE 21 –C1632 17-32 ZONE EXPANSION BOARD
FIELD TERMINATIONS ..............................50
FIGURE 22 –AUXILIARY I/P CONNECTION DETAIL.......51
FIGURE 23 –ALARM CIRCUIT CONFIGURATION ..........51
FIGURE 24 –FIRE PROTECTION,FIRE AND FAULT
SIGNAL OUTPUT CONNECTIONS..............52
FIGURE 25 –RESET RELAY CONTACT CONNECTION
DETAILS.................................................52
FIGURE 26 –TYPICAL T1200-CWIRING DIAGRAM ....54
FIGURE 27 –REPEATER WIRING DIAGRAM ...............55
FIGURE 28 –MUSTER INTERFACE WIRING DIAGRAM.55
FIGURE 29 –A1466 INTERFACE RELAY SPECIFICATION
.............................................................65
2. List of Tables
TABLE 1–MOTHERBOARD DIL SWITCH
CONFIGURATION DESIGN/RECORD..........66
TABLE 2–ZONE CONFIGURATION DESIGN/RECORD..67
TABLE 3–OUTPUT DELAY CONFIGURATION
DESIGN/RECORD ...................................67

T1200
MARINEC-P-A
3 02/14
PAGE 4 of 67
3. Introduction
This document contains technical information
necessary for application design using the T1200-C
Marine Conventional Fire Detection control panel.
The following supporting documentation is also
available:
•T1200-CSales Literature
•T1200-CUser Manual
•T1200-CInstallation and Commissioning Manual
•T1200-CLog Book
•Display Insert Templates
Note: References are made throughout this
document to “Fire Protection Output” and “Fire
Output”. These refer to particular outputs from the
T1200-C panels and are provided for specific
purposes:
•Fire Protection Output: An output used to
activate ancillary fire protection equipment or
systems. For example, fire doors or plant
shutdown.
•Fire Output: An output used to send a common
fire warning signal to a remote fire monitoring
station.
References are also made to “Manual Fire Alarm”
and “Muster”. These relate to fire alarm sounder
operating modes which are activated manually from
the fire panel display. The panel is configurable to
one or other of the two modes.
Detailed descriptions of both outputs are provided
within the following text.
4. General Description
The T1200-C Panel range is fully compliant with the
mandatory requirements and selected optional
requirements of EN54 parts 2 and 4 as well as the
relevant requirements of SOLAS 74.
The T1200-C equipment range consists of the
following:
•Panels: 4, 16 and 32 zone versions.
•Repeater: 16 and 32 zone versions.
Each panel in the range is housed in a metal
enclosure incorporating a door-mounted display
board fitted with a polyester overlay providing user
controls and indications. All display text is printed
on polyester inserts that slide into pockets in the
overlay. User controls are locked & unlocked via a
Keyswitch. All indications are implemented using
LEDs. The power supply is housed within the panel
enclosure and the standby batteries are housed in
a separate battery box.
Cable entry can be top or bottom. The T1204 has
gland plates at the top & the bottom. The T1216-C
& T1232-C have only one gland plate but the
enclosure can be inverted to allow cable entry top
or bottom. Factory default is bottom cable entry for
the T1216-C & T1232-C.
4.1 Cabinet Specifications
Enclosure construction:
•High quality, robust welded mild steel enclosure
with fully welded seams.
•Lockable door with trapped screws top &
bottom.
•Gland plate with 20mm knock-outs.
•Reversible door to allow enclosure to be
inverted to allow cable entry from top or bottom
(not T1204).
•Door, gland plate and display plate fitted with
neoprene seals.
•Display-mounted access control key switch fitted
with weatherproof cover.
•Motherboard and power supply mounted to a
removable chassis for easy installation.
•Optional door stay available.
Enclosure material gauge:
•Enclosure – 1.6mm thick.
•Gland plate – 2mm thick.
Paint finish:
•High quality, durable 2 stage system.
•Pre treatment – Electro-zinc plated and full
passivation.
•Polyester powder coat, semi gloss leatherette at
70-80 microns.

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 5 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Figure 1 – 4-Zone Panel Enclosure external view
A
CB
1.
2.
3.
4.
0 1
FIRE
POWER SUPPLY ON
POWER SUPPLY FAULT
SYSTEM FAULT
GENERAL FAULT
EARTH FAULT
FUSE FAILED
REPEATER FAULT
FAULT OUTPUT FAULT/DISABLED
SOUNDER FAULT/DISABLED
SOUNDER TEST
FIRE PROTECTION FAULT/DISABLED
FIRE OUTPUT ACTIVE
FIRE OUTPUT FAULT/DISABLED
BUZZER
SILENCE
RESET
ENABLE
DISABLE
TEST
TEST DISPLAY
ALARMS
RESOUND
SELECT
ON/OFF
SELECT
SILENCE/
ALARM
MUSTER
FIRE
1. THE RED ZONE INDICATOR
WILL PULSE SHOWING THE
LOCATION OF THE FIRE.
2. CARRY OUT THE
REQUIRED FIRE DRILL.
3. TO SILENCE ALARMS
PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE
CONDITION PRESS RESET.
FAULT
1. DETERMINE THE CAUSE OF
THE FAULT.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE
ENGINEER.
SYSTEM FAULT
THE PANEL IS INOPERATIVE.
ARRANGE FOR ALTERNATIVE
FIRE DETECTION MEASURES.
DISABLEMENT AND TEST
1. PRESS SELECT ON/OFF.
THE LED WILL ILLUMINATE.
2. SELECT THE ZONE OR
OUTPUT USING
AND
. THE
FAULT LED WILL PULSE.
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT
THE ZONE OR OUTPUT AND
PRESS ENABLE.
OVERRIDE
DELAY
T1204
20mm knock-outs
(Top entry gland plate) 10
Bottom entry gland plate
[without knock-outs]
Dim A [mm]
270
Dim B [mm]
335
Dim C [mm]
148

T1200
MARINEC-P-A
3 02/14
PAGE 6 of 67
Figure 2 – Console Mount Panel Enclosures external view
E
DF
B
A
C
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
0 1
FIRE
POWER SUPPLY ON
POWER SUPPLY FAULT
SYSTEM FAULT
GENERAL FAULT
EARTH FAULT
FUSE FAILED
REPEATER FAULT
FAULT OUTPUT FAULT/DISABLED
SOUNDER FAULT/DISABLED
SOUNDER TEST
FIRE PROTECTION FAULT/DISABLED
FIRE OUTPUT ACTIVE
FIRE OUTPUT FAULT/DISABLED
BUZZER
SILENCE
RESET
ENABLE
DISABLE
TEST
TEST DISPLAY
ALARMS
RESOUND
SELECT
ON/OFF
SELECT
SILENCE/
ALARM
MUSTER
FIRE
1. THE RED ZONE INDICATOR
WILL PULSE SHOWING THE
LOCATION OF THE FIRE.
2. CARRY OUT THE
REQUIRED FIRE DRILL.
3. TO SILENCE ALARMS
PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE
CONDITION PRESS RESET.
FAULT
1. DETERMINE THE CAUSE OF
THE FAULT.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE
ENGINEER.
SYSTEM FAULT
THE PANEL IS INOPERATIVE.
ARRANGE FOR ALTERNATIVE
FIRE DETECTION MEASURES.
DISABLEMENT AND TEST
1. PRESS SELECT ON/OFF.
THE LED WILL ILLUMINATE.
2. SELECT THE ZONE OR
OUTPUT USING
AND
. THE
FAULT LED WILL PULSE.
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT
THE ZONE OR OUTPUT AND
PRESS ENABLE.
OVERRIDE
DELAY
T1216-C
T1232-C
T1216R-C
T1232R-C
20mm knock-outs
in removable gland plate 24 36 24 36
Dim A [mm]
327
351
327
351
Dim B [mm]
274
280
274
280
Dim C [mm]
134
160
134
160
Dim D [mm]
18
18
18
18
Dim E [mm]
300
300
300
300
Dim F [mm]
380
400
380
400

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 7 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Figure 3 – Battery Box
B
C
A
T1200B-C
Battery Box
20mm knock-outs
1 at top
1 at bottom
Dim A [mm]
235
Dim B [mm]
395
Dim C [mm]
106
4.1.1 Order Codes & Descriptions
Tyco Part No.
Description
Standby SLA Battery
508.023.001 T1204DC – 4-Zone Panel c/w 1.5A 24Vdc PSU.
24V, 7Ah
in T1200B enclosure
508.023.002 T1204A1 – 4-Zone Panel c/w 1.5A 110Vac PSU.
24V, 7Ah
in T1200B enclosure
508.023.003 T1204A2 – 4-Zone Panel c/w 1.5A 230Vac PSU.
24V, 7Ah
in T1200B enclosure
508.023.023
T1200B B1 Battery box for T1204 – 4 zone panel.
24V, 3/7Ah
508.023.104
T1216-C – 16-Zone Panel c/w voyage data recorder output module and 4A
110/230Vac PSU.
24V, 17Ah
in T1200B-C enclosure
508.023.105
T1216W-C – 16-Zone Watermist Panel with 2x C1634 Relay output boards
and 4A 110/230Vac PSU.
24V, 17Ah
in T1200B-C enclosure
508.023.106
T1232-C – 32-Zone Panel c/w voyage data recorder output module and
5Amp 110/230Vac PSU.
24V, 17Ah
in T1200B-C enclosure
508.023.111
T1216R-C – 16 Zone Repeater - 24Vdc powered [including 2x C1631
repeater interfaces – one fitted, one spare for site fitting to panel].
N/A
508.023.114
T1232R-C – 32 Zone Repeater - 24Vdc powered [including 2x C1631
repeater interfaces – one fitted, one spare for site fitting to panel].
N/A
508.023.122
T1200E-C Expansion box for 4 output boards, without power supply
N/A
508.023.123
T1200B-C Battery enclosure for 2x 17Ah batteries.
24V, 17Ah
508.023.036
A1466 Relay Board [2x volt-free changeover contacts rated 2A, 30V Max].
N/A

T1200
MARINEC-P-A
3 02/14
PAGE 8 of 67
4.1.2 Replacement Part Order Codes and Descriptions
Tyco Part No.
Description
Used in
509.023.006 C1626 – 4-zone panel motherboard. With AC PSU
T1204A1
T1204A2
509.023.007
C1626 – 4-zone panel motherboard. With no PSU
T1204DC
509.023.008
C1627 – T1216-C panel motherboard
T1216-C
509.023.009
C1627 – T1232-C panel motherboard
T1232-C
509.023.012 C1626 – Repeater motherboard
T1216R-C
T1232R-C
509.023.021 C1628 – 4-zone panel display 2605041 fitted with 4 zone overlay
[No inserts]
T1204A1
T1204A2
T1204DC
509.023.022
C1628 – 16-zone panel display 2605043 fitted with 16 zone overlay
[No inserts]
T1216-C
509.023.023
C1629 – 32-zone panel display 2605044 fitted with 32 zone overlay
[No inserts]
T1232-C
509.023.031
C1628 – 16-zone repeater display 2605054 fitted with 16 zone overlay
[No inserts]
T1216R-C
509.023.032
C1629 – 32-zone repeater display 2605055 fitted with 32 zone overlay
[No inserts]
T1232R-C
2605061 C1631 – Repeater interface Board
T1216-C [with repeater]
T1232-C [with repeater]
T1216R-C
T1232R-C
2605060 C1630 – Output Expansion Interface Board
T1216-C
T1232-C
509.023.042
C1632 – 16-zone expansion board (provides zones 17 to 32)
T1232-C
2605064 C1634 Relay Output Board
T1216-C
T1232-C
508.023.035 C1665 – Muster interface (Optional add-on)
T1216-C
T1232-C
T1216R-C
T1232R-C
509.023.071 C1714 VDR Interface Board
T1216-C
T1232-C
509.023.052
24 VDC PSU [PS40-1-09]
T1204DC
509.023.051 110/230V AC PSU [PS136-1-09]
T1216-C
T1232-C
509.023.061
T1200/T1200-C Spare key set - 2 off access controls keys
All panels and repeaters

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 9 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
4.1.3 Optional Language Display Inserts
Tyco Part No
Description
Insert set comprises
508.023.051 T1216/T1216-C insert set
LED Insert – Standard Version
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 1 – Standard Version (Fire Alarm Switch). Side 1 –
Chinese. Side 2 – Japanese
Switch Insert 2 – Standard Version (Muster Alarm Switch). Side 1 –
Chinese. Side 2 – Japanese
Switch Insert 3 – Std Version (No Fire/Muster Alarm Switch). Side 1
– Chinese. Side 2 – Japanese
Zone Location Insert
Side 1 – Chinese. Side 2 – Japanese
Instruction Insert – 16 Zone Standard Panel
Side 1 – Chinese. Side 2 – Japanese
508.023.052 T1232/T1232-C insert set
LED Insert – Standard Version
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 1 – Standard Version (Fire Alarm Switch)
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 2 – Standard Version (Muster Alarm Switch)
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 3 – Std Version (No Fire/Muster Alarm Switch). Side 1
– Chinese. Side 2 – Japanese
Zone Location Insert x 2
Side 1 – Chinese. Side 2 – Japanese
Instruction Insert – 32 Zone Standard Panel
Side 1 – Chinese. Side 2 – Japanese
508.023.053 T1216R/T1216R-C insert set
LED Insert – Repeater Version
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 1 – Repeater Version (Fire Alarm Switch)
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 2 – Repeater Version (Muster Alarm Switch)
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 3 – Repeater (No Fire/Muster Alarm Switch). Side 1 –
Chinese. Side 2 – Japanese
Zone Location Insert
Side 1 – Chinese. Side 2 – Japanese
Instruction Insert – 16 Zone Repeater Panel
Side 1 – Chinese. Side 2 – Japanese
508.023.054 T1232R/T1232R-C insert set
LED Insert – Repeater Version
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 1 – Repeater Version (Fire Alarm Switch)
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 2 – Repeater Version (Muster Alarm Switch)
Side 1 – Chinese. Side 2 – Japanese
Switch Insert 3 – Repeater (No Fire/Muster Alarm Switch)
Side 1 – Chinese. Side 2 – Japanese
Zone Location Insert x 2
Side 1 – Chinese. Side 2 – Japanese
Instruction Insert – 32 Zone Repeater Panel
Side 1 – Chinese. Side 2 – Japanese
4.1.4 Optional Door Stay Assembly
Tyco Part No
Description
Used On
508.023.025
T1200 Door Stay Assembly
T1216-C, T1216W-C, T1232-C, T1216R-C, T1232R-C, T1200E-C

T1200
MARINEC-P-A
3 02/14
PAGE 10 of 67
4.2 Fire Detection and Alarm Panel Description
See exploded general assembly drawings below.
Figure 4 – T1204 Panel – General Assembly
DISPLAY BOARD
EARTH BAR
EARTH POST
EARTH POST
MAINS TERMINAL BLOCK
MAINS CABLE CLAMP
MOTHERBOARD
EARTH STRAP
EARTH POST
POWER SUPPLY
RIBBON CABLE ASSEMBLY
EARTH POST
EARTH POST
INSULATION PLATE
CABLE TIE
9V BATTERY
CABLE CLIP
DISPLAY PLATE
KEYSWITCH
BUZZER
Fuse:
Input:
Serial No:
Part No:
Product:
Standards:
Approval:
FireAlarmSystem
0086-CPR-607217
Made in Great Britian
RATING LABEL

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 11 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Figure 5 – T1216-C Panel – General Assembly
SWITCH INSERT
LED INSERT
MEMBRANE
KEYSWITCH MOUNTING NUT
20 WAY
RIBBON
CABLE
EARTH POST
EARTH POST
MAINS TERMINAL BLOCK
WITH 5A FUSE
P.C.BOARD SUPPORTS (2 OFF)
POWER SUPPLY (110V/230V)
16 ZONE
MOTHERBOARD
(C1627)
C1714 SERIAL VDR I/F BOARD
C1630 EXPANSION INTERFACE
POWER SUPPLY LEAD
BATTERY HOLDER
BATTERY LEAD
20WAY RETAINING CLIP
RETAINING
CLIP
BUZZER MOUNTING BRACKET
EARTH POST
RIBBON CABLE CLAMPS - 4 OFF
CABLE CLIP
INSULATION PLATE
CABLE TIE USED
TO SECURE BATTERY
10 WAY RIBBON CABLE
CONNECTPP3 BATTERY
LEADTO
J4ON DISPLAY BOARD
IMMEDIATELYBEFORE
POWERINGUP THE PANEL
SEE
"POWERINGUP" IN THE
INSTALLATIONMANUAL
Fuse:
Input:
SerialNo:
PartNo:
Product:
Standards:
Approval:
0086/14
Fire Alarm System
Thorn Security Ltd
IsolateSupply Before
0086-CPR-607217
Madein Great Britian
OpeningCover
THISUNIT MUST
BEEARTHED
RATING LABEL
ZONE LOCATION INSERT
INSTRUCTION INSERT
4 WAY PSU TERMINAL BLOCK
TERMINAL BLOCK LABEL
L
N
Fuse
Mains
ReplaceFus
WithSame Type
THERM
THERM
BAT +
BAT -
EARTH POST
CABLE TIE (3 OFF)
9V BATTERY
RIBBON CABLE TO MOTHERBOARD
12 WAY EARTH BAR
TERMINAL BLOCK MOUNTING
ENCLOSURE
CHASSIS
DOOR
KEYSWITCH
MAINS TERMINAL LABEL
LOGO
CHASSIS EARTH CABLE
DOOR EARTH CABLE
GLAND EARTH CABLE
EARTH POST
DISPLAY BOARD (C1628)
DISPLAY SUPPORT PLATE

T1200
MARINEC-P-A
3 02/14
PAGE 12 of 67
Figure 6 – T1232-C Panel – General Assembly
EARTH POST
EARTH POST
MAINS TERMINAL BLOCK 5A0 FUSE
MAINS TERMINAL LABEL
POWER SUPPLY (110V/230V)
MEMBRANE
DISPLAY BOARD (C1629)
ZONE LOCATION INSERT - 2 OFF
SWITCH INSERT
LED INSERT
INSTRUCTION INSERT
EARTH POST
12 WAY EARTH BAR (2 OFF)
PANEL MOTHERBOARD
(C1627)
C1714 SERIAL VDR I/F BOARD
CHASSIS EARTH CABLE
C1632 EXPANSION BOARD
C1632 + C1714 MTG DETAILS
M3x22 HEX SPACER (4 OFF)
10 WAY RIBBON CABLE ASSEMBLY
LOGO
P.C.BOARD SUPPORTS (2OFF)
L
N
Fuse
Mains
ReplaceFu
WithSame Typ
POWER SUPPLY LEAD
BATTERY CLAMP
BATTERY LEAD
KEYSWITCH
BUZZER MOUNTING BRACKET
GLAND EARTH CABLE
DOOR EARTH CABLE
EARTH POST
INSULATION PLATE
9V BATTERY
CABLE TIE USED
TO SECURE BATTERY
CONNECTPP3 BATTERY LEAD
TO
J4ON DISPLAY BOARD
IMMEDIATELYBEFORE
POWERINGUP THE PANEL
SEE
"POWERINGUP" IN THE
INSTALLATIONMANUAL
RATING LABEL
Fuse:
Input:
SerialNo:
PartNo:
Product:
Standards:
Approval:
0086/14
Fire Alarm System
IsolateSupply Before
0086-CPR-607217
OpeningCover
THISUNIT MUST
BEEARTHED
4 WAY PSU TERMINAL BLOCK
SERIAL VDR I/F BOARD MOUNTING BRACKET
ENCLOSURE
CABLE TIE (3 OFF)
THERM
THERM
BAT +
BAT -
TERMINAL BLOCK LABEL
EARTH POST
Thorn Security Ltd
Madein Great Britian
KEYSWITCH MOUNTING NUT
CABLE CLIP
20 WAY RIBBON
CABLE TO DISPLAY
RETAINING
CLIP
20W RETAINING CLIP
RIBBON CABLE CLAMPS - 4 OFF
RIBBON CABLE TO MOTHERBOARD
14 WAY CABLE
ASSEMBLY
C1630 EXPANSION
INTERFACE BOARD
DISPLAY SUPPORT PLATE

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 13 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
4.2.1 C1626 4 Zone Motherboard
This board is used on the T1204 panel. It provides
terminals for all the field wiring, connectors for the
repeater interface and connections to the display
board. It accommodates the microcontroller
(including Firmware and RAM) and all of the vessel-
specific configuration features (DIL switch &
EEPROM).
It is also used, in a depopulated form, as the
motherboard for the T1216R-C and T1232R-C
repeater panels.
Power supply components for the mains powered
4-zone panels are located on this PCB. The
components are depopulated for the DC powered
panel and repeaters.
4.2.2 C1627 16 Zone Motherboard
This board is common to the T1216-C and T1232-C
panels.
It provides terminals for all the field wiring, interface
connectors for the repeater, zonal expansion
connectors and connections to the display board. It
accommodates the microcontroller (including
Firmware and RAM) and all of the vessel-specific
configuration features (DIL switch & EEPROM).
4.2.3 C1632 32 Zone Expansion Board
This board provides an additional 16 detection
zones, labelled as zones 17 to 32. It is connected to
the C1627 motherboard via a ribbon cable to
provide a total of 32 zones for the T1232-C panel.
4.2.4 C1628 16-Zone Display Board and
C1629 32-Zone Display Board
These boards provide visible [LED] user indications
and user control buttons. The display board
connects to the motherboard via a ribbon cable.
The C1628 is common to the T1204, T1216-C and
T1216R-C panels. The C1629 is common to the
T1232-C and T1232R-C. The Enable, Disable, Test
Select On/Off & Select Up/Down buttons are not
fitted on the repeater versions. A jumper link is
provided on the internal face of the display boards
[on the control panels only] to allow the Manual Fire
Alarm button, located on the display, to operate in
one of the following modes:
•Manual fire alarm Sounder response.
•Muster Sounder response.
•No response [button disabled].
4.2.5 Display Overlay and Inserts
The display overlay is bonded to the display PCB
and is used with a series of text label inserts to
identify the various user controls and indications.
The inserts slip into pockets in the overlay and
facilitate foreign language variants without affecting
the overlay. The panel is provided with one set of
Standard English text inserts fitted. These inserts
are reversible and the rear is blank to allow small
volume language variants to be typed. Since one of
the panel’s configurable options allows manual
activation of the fire alarms in either the Manual
Fire Alarm or Muster mode, an additional English
text insert is provided for the user controls section;
one side identifies the top left hand button and LED
as “Manual Fire Alarm” the other side identifies the
button as “Muster”.
4.2.6 C1631 Repeater Interface Board
This optional plug-in board provides an RS485
serial interface for communication with up to 5
repeaters connected to a T1216-C or T1232-C
panel. It is fitted to the panel & repeater
motherboards via two connectors. The panel does
not have the C1631 board fitted as standard. Each
repeater is supplied with a C1631 fitted and a
C1631 in the spares bag for fitting to the panel if
required.
Three DIL switches on the C1631 configure the
panel with the number of repeaters connected. At
each repeater these DIL switches configure the
address of the repeater.
4.2.7 C1665 Muster Interface Board
This optional plug-in board provides an additional
fault monitored link between the fire alarm panel
and the repeaters. It allows the muster alarm to be
initiated on the panel by operating the Muster
button on a repeater. It is capable of operating the
Muster even if the microcontrollers have failed on
the fire panel and repeaters. One C1665 needs to
be fitted to the fire alarm panel and one to each
repeater. If the muster alarm is to be initiated by the
Manual Fire Alarm/Muster push button on the
repeaters then the Muster Interface has to be fitted.
There are no configuration requirements for this
board. This board is not required for Manual Fire
Alarm [general alarm] operation.
4.2.8 Output Expansion System
The output expansion system is an expandable
modular output system, for use local to the
T1216-C and T1232-C panels. It comprises of an
Output Interface Board and four types of Output
board that provide various output expansion
options.
General features:
•8 outputs per output board (except VDR output
board).
•4 application types:
oType 1 – Indication output module (C1633).
oType 2 – Fire protection output module

T1200
MARINEC-P-A
3 02/14
PAGE 14 of 67
(C1635 – Monitored, C1634 – Non-
monitored).
oType 3 – Sounder output module (C1635).
oType 4 – Voyage data recorder output
module (C1714).
•Pre defined zone group allocation for types 1, 2
and 3 which allocates a group of 8 sequential
zones to each board as follows. Zone groups
are:
Zones 1-8, 9-16, 17-24 and 25-32
•All terminals for field cabling are suitable for
2.5mm conductors.
•Ribbon Cable connection to panel providing 2-
wire RS485 Serial Communications to all boards
and DC power for C1634 (and other signals).
•DC Power supply input from panel or an external
PSU depending upon application.
•A maximum of thirteen output boards can be
connected to a single panel [4 off type 1, 4 off
type 2, 4 off type 3, 1 off type 4].
Overviews for the C1630 interface and the C1714
Voyage Data Recorder are provided below, further
details of the Output Expansion Modules can be
found in the Output Expansion Module Manual.
4.2.9 C1630 Output Interface
This PCB is fitted as standard to the T1216-C and
T1232-C motherboard and is required when output
expansion modules are used. It provides the
communication path between panel and output
modules. A 7-way DIL switch is used to set up the
total quantity of each type of O/P board connected
to the panel.
4.2.10 C1714 – VDR Output Module
The VDR output module provides outputs to signal
critical Fire Alarm Panel conditions to the vessel’s
Voyage Data Recorder unit. It is fitted as standard
to the T1216-C and T1232-C. The VDR is not
supported on the T1204.
Five volt-free changeover contacts provide the
following signals:
•Common Fire.
•Machinery space fire detected. [Any zone or
number of zones can be configured to operate
this output].
•Common Fault – Fail-Safe.
•Mains Failed – Fail-Safe.
•Back-up Supply Failed – Fail Safe.
A 2-wire serial data output (RS422) is also
provided, which conforms to IEC 61162-1. This
provides zonal status information as well as the
above signals (see section 10. on page 24).
4.3 T1200-C Repeater Description
The repeaters use the same display (de-populated
& different overlay) and enclosures as for the
T1216-C & T1232-C fire alarm panels. The
motherboard is a de-populated C1626 board. The
repeater and fire panel mechanical arrangements
are similar. The C1631 Repeater interface board is
fitted to the repeater motherboard and must also be
fitted to the fire panel motherboard. Repeaters are
powered directly from the 24Vdc output from the
T1216-C & T1232-C panels. An optional Muster
Interface board (C1665) is available and must be
fitted to all repeater panels and the fire alarm panel
if a muster fire condition is required to be initiated
from repeater panels.
Repeaters are not provided for the T1204.

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 15 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Figure 7 – T1216R-C Repeater – General Assembly
REPEATER SWITCH INSERT
REPEATER LED INSERT
MEMBRANE
REPEATER DISPLAY BOARD (C1628)
EARTH POST
EARTH POST
EARTH POST
P.C.BOARD SUPPORTS 6mm (2OFF)
REPEATER MOTHERBOARD (C1626)
C1631 REPEATER I/F BOARD
CHASSIS EARTH CABLE
DOOR EARTH CABLE
LOGO
KEYSWITCH
BUZZER MOUNTING BRACKET
Fuse:
Input:
SerialNo:
PartNo:
Product:
Standards:
Approval:
0086/14
Fire Alarm System
IsolateSupply Before
0086-CPR-607216
OpeningCover
THIS UNIT MUST
BEEAR THED
RATING LABEL
ZONE LOCATION INSERT
INSTRUCTION INSERT
ENCLOSURE
GLAND EARTH CABLE
EARTH POST
EARTH POST
Thorn Security Ltd
Madein Great Britian
EARTH POST
RIBBON CABLE TO DISPLAY.
20 WAY RETAINING CLIP
KEYSWITCH MOUNTING NUT
20 WAY RETAINING CLIP
RIBBON CABLE CLAMPS - 4 OFF
RIBBON CABLE TO MOTHERBOARD
CABLE CLIP
DOOR
DISPLAY SUPPORT PLATE

T1200
MARINEC-P-A
3 02/14
PAGE 16 of 67
5. Functional Specification
5.1 T1200 Panel Input/Output List
Input/Output
T1204
T1216-C
T1232-C
Detection zones
4
16
32
Remote silence alarm I/P [non monitored]
1
1
1
Remote reset I/P [non –monitored]
1
1
1
Remote Manual Fire Alarm/Muster I/P [non –monitored]
1
1
1
Class change I/P [non –monitored]
1
1
1
Sounder circuits
4 @ 0.5A
4 @ 1A
4 @ 1A
Zonal O/Ps [open collector] 4
4 on Motherboard,
additional outputs via O/P
expansion system
Disablement active [open collector]
1
1
1
Manual Fire Alarm/Muster active [open collector] – not
activated when panel microprocessor fails. 1 1 1
Buzzer active [open collector]
1
1
1
Monitored Fire Output
1
1
1
Monitored Fire Protection O/P
1
1
1
Monitored Fault Output
1
1
1
Volt-free Reset Relay
1
1
1
Aux DC Supply [fused]
1 @ 0.5A
1 @ 1A
1 @ 1A
Repeater facility
N/A
Optional
Optional
Remote Muster I/P [from repeater] via optional muster
interface N/A Optional Optional
T1216-C & T1232-C only:
Voyage data recorder O/P module providing 1 x volt-
free changeover relay contact for each of the following
alarms:
Common Fire.
Machinery Space Fire.
Common Fault.
Mains Failed.
Battery Failed.
(All contacts rated 1A @ 30Vdc)
1xRS422 output also provided, conforming to
IEC 61162-1.
N/A 1 1
Additional Outputs via O/P expansion system
N/A
Optional
Optional

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 17 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
5.2 Features List
Enclosures
Tough welded mild steel enclosures with high quality paint finish.
Removable gland-plate for termination and looming.
Optional door stay available for all panels except T1204A1,
T1204A2, T1204DC.
Temperature-compensated battery
charging
Battery charging voltage is automatically adjusted between
28.25 and 26.72V DC over an ambient temperature range of
-10°C to +55°C.
Battery disconnect
Protects the battery from permanent damage due to deep
discharge by automatically disconnecting it when the battery
voltage falls below 21V.
Mains Failed Indication Delay
The indication of main power failure is delayed by 90 seconds to
allow the power to be switched from ship to shore and vice versa
without generating a false fault indication.
Total power failure warning on the fire
panels
A separate, non-rechargeable 9V battery provides the power for
an audible warning should the primary [ship’s] supply and the
panel’s standby battery fail (or be disconnected).
Class change input
Operates all sounders for up to 5 seconds without giving any
panel indications (this is a land-based feature).
Configurable detection zones
Simple and flexible configuration process utilising the LED
display, allowing detection zones to be configured for any or all
of the following:
•Latching or non-latching Fire indication.
•Normal or Intrinsically-Safe zone monitoring.
•Machinery Space Zones.
Factory configuration: Latching, standard [non-I.S.], no zones
programmed as Machinery Space Zones.
Selectable Zonal or General Alarm
Sounder operation with sounders in alert
or silent in non-alarm zones
Selectable via DIL switches on the motherboard.
The standard sounders on the T1204 panel can be used in
General or Zonal modes. [On T1216-C and T1232-C panels
these sounders always operate in General mode regardless of
DIL switch setting].
The output expansion system provides additional sounder
circuits for General or Zonal use on the T1216-C and T1232-C
panels.
General sounder operation continuous or
pulsed
DIL switch selectable on the motherboard. All sounders operate
continuously or pulsed as selected.
Restart sounders or restart sounder delay
DIL switch selectable on the motherboard. With the panel in the
silence alarms condition, a 2nd zone fire condition restarts the
sounder delay or immediately operates all sounders. [This is
available only when panel is configured to the Crew Alarm
Mode.]

T1200
MARINEC-P-A
3 02/14
PAGE 18 of 67
Configurable Fire Output, Fire Protection
and Fault Output Relays
Configuration Links on the motherboard allow each Output Relay
to be individually selected to the EN54 powered/fault-monitored
mode or non-EN54-compliant volt-free changeover contacts.
Factory configuration - Fully Monitored (EN54 Mode).
Reset Relay
A volt-free changeover contact operating for 10 seconds on
panel fire alarm reset.
Auxiliary 24Vdc power supply output
Protected by an electronic fuse. Operation of the fuse is
indicated on the display. Operation of the Reset button on the
panel display resets the electronic fuse.
Open collector outputs
•Manual Fire Alarm/Muster active.
•Buzzer Active.
•Disablement Active.
•Zonal fire for each zone up to zone 4. [additional zonal
output expansion on T1216-C and T1232-C panel via open
collector output expansion boards].
Remote Inputs
•Remote Manual Fire Alarm or Muster as configured.
•Remote Silence Alarms.
•Remote Reset.
•Fully monitored Muster activation from repeater panel [via
optional plug in board at panel and repeater].
Earth Fault monitoring
Can be disabled via link on the motherboard.
Zone/Output disablement feature
The following circuits can be independently disabled/enabled:
•Each Zone
•Fire Output
•Fire Protection
•Fault Output
•All Sounders
One Man Zone Test
Each zone can be independently set to the One Man test
condition. Sounders can be configured to operate briefly to
confirm the panel has detected the test fire or not to operate
during the test fire.
One Man Sounder Test
Operates the sounders intermittently.

EQUIPMENT: T1200-C
PUBLICATION: MARINEC-P-A
ISSUE No. & DATE: 3 02/14
© 2014 Thorn Security Ltd PAGE 19 of 67
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Delay Mode Facility
(NOTE: This facility does not fully comply
with the requirements of EN54-2
because the delay length is fixed)
Flexible system allowing:
•Activation of the delay by operation of an automatic fire
detector on any zone.
•Single-stage, 2-minute fixed delay.
•Selection of the outputs to be delayed [Fire O/P and/or Fire
Protection and/or Sounders] – can be any combination
(Crew Alert mode automatically sets sounder delay on all
circuits except 1 & 2; circuit 1 is delayed for all fires except
for machinery space zones; circuit 2 is never delayed).
•Delay can be overridden by operating a manual call point
on any zone or pressing the Delay Override button on the
panel or repeater.
•In Crew Alert Mode the delay can also be overridden by
pressing Resound Alarms after alarms have been silenced.
•In Crew Alert Mode the delay can be extended by pressing
the Silence alarms button.
Crew Alert Mode
•Operation of an automatic fire detector or alert manual call
point on any zone operates sounder circuit 2 only
[Bridge/Crew areas].
•Operation of an automatic fire detector or alert manual call
point on any machinery space zone operates sounder
circuits 1 & 2 only (circuit 1 is for machinery spaces only).
•After 2 minute delay, all delayed sounder circuits (including
any expansion sounder outputs) operate.
•Operation of an Evacuate manual call point overrides the
delay and operates all sounders.
•Manual Fire Alarm/Muster activation overrides delay and
operates all sounders.
•Fire O/P and/or Fire Protection O/P can be optionally
configured to be delayed along with the sounder circuits.
•DIL switch option to allow delay to restart on a new fire
condition if Alarms are silenced before the end of the delay.
Selectable Manual Fire Alarm or Muster
sounder response
Manual Fire Alarm response: All sounders operate until silenced.
Muster response: International Marine Muster signal, capable of
operation even if the panel processor fails.
Optional manual muster activation from
repeater panel
Allows the muster condition to be manually initiated from the
repeater panel even if the repeater panel processor fails.
Dimmable LED indicators on fire panels
and repeater panels
All display-mounted LEDs can be manually dimmed for night
time operation where bright indications may be too obtrusive.
Panel has 8 selectable brightness levels.
Repeater has two selectable brightness levels.
Automatic fire detector and manual call
point fire event discrimination
Each zone is capable of recognising whether a fire condition has
been caused by an automatic fire detector or a manual call point.
This is used in conjunction with the output delay features.

T1200
MARINEC-P-A
3 02/14
PAGE 20 of 67
Output expansion system for the T1216-C
and T1232-C panels
Three different modules each providing eight switched outputs:
•Open collector, suitable for LED mimics.
•Volt-free relays for external signalling or equipment control.
•Fault-monitored, powered outputs for EN54-
2 type Fire
Protection control or additional sounder circuits.
Voyage Data Recorder Output Board
Provides output signals for the Voyage Data Recorder:
•Common Fire.
•Common Fault.
•Mains Failed.
•Back-up Supply Failed.
•Machinery space fire. [Zonally configurable]
•IEC 61162-1 compliant RS422 output.
Other configuration features
•Prevent the Fire Protection output operating for a fire
condition on a “Non-Latch” zone.
•Inhibit the silencing and resetting of the panel for 3 minutes
following the occurrence of a fire alarm. [Does not apply to
Muster Alarm].
•Set the sounders to operate only when the panel is in the
Manual Fire Alarm/Muster condition.
•Inhibit the resetting of the fire alarm
condition until the
alarm sounders have been silenced.
•Disable the internal panel buzzer.
•Select latching fault mode where all fault conditions latch
until the panel is manually reset.
•Restore factory default configuration.
Repeater panels
Support for up to 5 repeater panels via two-wire RS485 serial
communication. [Repeaters are not available for
the T1204
panels].
This manual suits for next models
4
Table of contents
Other Tyco Control Panel manuals

Tyco
Tyco PowerSeries Pro HS3032 User manual

Tyco
Tyco DSG Touch SCW9067 User manual

Tyco
Tyco MC-2 User manual

Tyco
Tyco T1200 Mounting instructions

Tyco
Tyco RAPID RESPONSE RCP-1 User manual

Tyco
Tyco Bentel Security ABSOLUTA Instruction manual

Tyco
Tyco RAPID RESPONSE RCP-1 User manual

Tyco
Tyco AutoPulse Z-10 User manual

Tyco
Tyco AutoPulse Z-20 User manual
Popular Control Panel manuals by other brands

Brightsky
Brightsky JB-QB-5Ei user manual

Limotec
Limotec MD300 user manual

Mitsubishi Electric
Mitsubishi Electric E1041 installation manual

Hvac
Hvac ZP4-ESP installation guide

WimTec
WimTec SanTec OCEAN T6 Installation and operating instructions

EWC Controls
EWC Controls ULTRA-ZONE ST2E Series Technical bulletin