Tyco DSC FSD-210 Series User manual

Read this instruction sheet thoroughly before installation and use of the
FSD-210 2-Wire Smoke Detector. This instruction sheet shall be used in conjunc-
tion with the Installation Manual of the alarm control panel. All the instructions
specified within that manual must be observed.
Introduction
The FSD-210 is a 2-wire photoelectric smoke detector with
internal piezoelectric alarm and optional fixed temperature
heat detector and/or auxiliary form C relay. Two versions are
available: US version (UL) and Canadian version (ULC). For
installations requiring tandem alarm operation, refer to the
PRM series modules and FSA series smoke detectors.
Operation
Approximately every 7 to 8 seconds the unit tests for a smoke
or heat alarm condition. During this sequence the unit also
performs self diagnostics, and checks for faults. During normal
operation the LED will flash every 50 seconds and the siren will
not sound.
Smoke Alarm
The smoke detector has a nominal fixed alarm sensitivity (refer
to the Specifications on the last page) and it will go into alarm
when the signal level exceeds the 'alarm' threshold and send
the alarm signal to the control panel. During an alarm the LED
will flash 1/second and the siren will sound the evacuation
temporal pattern (UL) or continuous beeps (ULC).
Smoke - Drift Compensation
The detector automatically compensates for long-term envi-
ronmentally induced changes to maintain a constant smoke
sensitivity. When the drift compensation has reached its high
or low limit of adjustment, the detector will go into the trou-
ble state.
Heat Alarm
The heat detector will go into alarm when the heat signal level
exceeds the heat alarm threshold (135ºF/57ºC); and send the
alarm signal to the control panel. During an alarm the LED will
flash 1/second and the siren will sound the evacuation tempo-
ral pattern (UL) or continuous beeps (ULC).
Installer Instructions
1. Smoke Detector Placement
On smooth ceilings, detectors
may be spaced 9.1M (30 feet)
apart as a guide. Other spacing
may be required depending on
ceiling height, air movement, the
presence of joists, uninsulated
ceilings, etc. Consult National Fire
Alarm Code NFPA 72, Chapter 11
CAN/ULC-S553-02 or other
appropriate national standards for
installation recommendations.
Do NOT locate smoke detectors at the top of peaked or
gabled ceilings; the dead air space in these locations may pre-
vent the unit from detecting smoke. Avoid areas with turbu-
lent air flow, (near doors, fans or windows. Rapid air
movement around the detector may prevent smoke from
entering the unit. Do NOT locate detectors in areas of high
humidity.
Do NOT locate detectors in areas where the temperature rises
above 38ºC (100ºF) or falls below 5ºC (41ºF).
Install Smoke detectors in accordance with NFPA 72,
Ch. 11: “Smoke detectors shall be installed outside of each
sleeping area in the immediate vicinity of the bedrooms and
on each additional story of the family living unit, including
basements and excluding crawl spaces and unfinished attics.
In new construction, a smoke detector also shall be installed in
each sleeping room.”
FSD-210 Series Smoke Detector
Installation and Operating Instructions
P
P
A
A
I
I
N
N
T
T
Piezo Siren
Alignment Marks
LED / Test Button
Place magnet here
DO
DO
N
N
O
O
T
T
'*
Alarm Indications
Condition LED Siren Relay Alarm
Current
Normal / Sensitivity
in Production Range Flash 1/50s OFF Deactivated No
Alarm Smoke/Heat Flash 1/1s Temporal or
Steady Activated Yes
Alarm Restore Flash 1/1s Temporal or
Steady Activated Yes
Low Power Trouble OFF OFF Deactivated No
Other
Fault / Trouble OFF CHIRP 1/50s Deactivated No
Test Switch - Failed OFF CHIRP 1/50s Deactivated No
Test Switch - Pass Flash 1/1s Temporal or
Steady Activated Yes
firealarmresources.com

2. Mount Smoke Detector Backplate
Mount backplate using screws pro-
vided and the appropriate holes on
the mounting plate.
NOTE: Install wiring in accordance
with the appropriate national and
local electrical codes. For UL/ULC
Installations, the power supply must
be supplied from a UL/ULC Listed
alarm control unit.
CAUTION: The dust cover protects
the unit when not in service. Remove dust cover before use.
3. Wiring
Refer to the wiring diagrams in this installation sheet and
those provided in the Installation Manual of the alarm control
panel being used with the unit. Before connecting the unit,
prepare the wires from the electrical box for connection; Do
not use frayed or bent wire.
CAUTION: Do NOT use looped wire under terminals. Break
the wire run, to provide supervision of connections.
When wiring is completed, inspect the wiring and correct any
errors before applying power to the unit. When the wiring has
been thoroughly reviewed, neatly insert the wires into the
electrical box and secure the unit to the mounting plate.
To connect this device use only wiring listed as fit for the pur-
pose.
4. Mounting
Detector Installation
Position the detector on to the base
plate using the detector and base plate
alignment marks. Press the detector
gently in place while rotating the detec-
tor clockwise until the detector snaps
into place. Remove the side tab from
the locking tab to lock in place (optional).
Removal: If the side tab is removed to lock the detector,
depress tab with a small flat blade screwdriver and rotate
detector counter-clockwise until the alignment marks line up.
Remove detector.
5. Test Unit
Initiate test by pressing the test button for greater than 5 sec-
onds.
Alarm activation is indicated by the LED, the siren, and the
alarm reporting to the Control Panel. The detector restores to
normal when the test button is released or when the magnet
is removed.
NOTES: Allow a minimum of 20 seconds between test activa-
tions.
If the detector is in one of the following states when a test is
initiated; it will not enter an alarm state.
1. Compensation trouble.
2. Failure of heat or smoke detector.
3. Other internal faults that could prevent a smoke or heat
alarm.
NOTE: Smoke sensitivity of installed detectors can be mea-
sured without removal or an alarm being generated using the
FSD-100 Smoke Detector Test Meter.
Test Unit with FSD-100 Smoke Detector Test Meter
To test the unit using the FSD-100, set the test meter up to
read devices as per the instructions supplied with the test
instrument. Depress the test button (or place the FSD-100 on
the outside edge of the plastics beside the test button to acti-
vate the reed switch on units without siren) on the smoke
detector for 1 second and release.
NOTES: If the test button is held for 5 seconds or longer, an
alarm will be generated. Move the test meter over the center
of the detector, wait until you hear the test meter beep,
remove the unit and the information can be immediately
reviewed. Please see the instructions supplied with the FSD-
100 Smoke Detector Test Meter for more information.
Perform the tests one at a time. Performing simultaneous tests
on multiple detectors may trigger an alarm at the control
panel.
6. Removing the Chamber for Cleaning
To clean or replace the smoke chamber the detector must be
opened.
1. Press the 3 tabs on the bottom of the detector outward to
release.
2. Remove the bottom portion which contains the PCB and
the chamber.
3. Place thumb and forefinger on the sides of the chamber in
the locations indicated by the arrows on top of the cham-
ber.
4. Squeeze gently inward and pull up and the chamber will
separate.
5. The removable portion can now be replaced or cleaned.
Cleaning can be done using compressed air. Do not use a
cloth as it may leave particles on the inner wall.
6. Replace the new or cleaned chamber by pressing it down
until it snaps into place. Locate and press the backplate
into the housing making sure the 3 locking tabs are
snapped into their locked position.
7. Compensation Reset
Cleaning, replacement of the smoke sensor, or other changes
may change the background signal/noise of the detector; this
requires the drift compensation be reset. Compensation trou-
ble is one of the faults indicated when the LED indicator is OFF
while the siren is chirping.
• Remove power from the unit, then press and hold the test
button for 30 seconds to power down unit.
• Power up unit while pressing the test button.The LED will
flash; when 5 seconds has elapsed. Release the test button
within 1 second after the fifth LED flash.
• The LED will flash every 8 seconds for 1 minute. When the
detector stops flashing test the detector to verify normal
operation.
Mountin
g
Holes
Locking
Ta b
V+
V
9.35-30VDC EOL Device
++
-
++
-
++
-
Relay
NO NC C
CLOSE
OPEN
Alignment
Marks
Backplate
Tabs
Mounting
Surface
Detector
firealarmresources.com

Owner’s Instructions
Fire Safety In The Home
Most fires occur in the home, and to minimize this danger, it is
recommended that a household fire safety audit be con-
ducted and a family escape plan be developed.
Household Fire Safety Audit
1. Are all electrical appliances and outlets in safe condition?
Check for frayed cords, overloaded lighting circuits, etc. If
you are uncertain about the condition of your electrical
appliances or household service, have a professional evalu-
ation.
2. Are all flammable liquids safely stored in closed containers,
and in a cool and well ventilated area? Avoid cleaning the
unit with flammable liquids.
3. Are hazardous materials such as matches out of the reach
of children?
4. Are furnaces and wood burning appliances properly
installed, clean, and in good working order? If in doubt,
have a professional evaluation.
Family Escape Planning
There is often very little time between the detection of a fire
and the time it becomes deadly. Because of this, it is very
important that a family escape plan be developed and
rehearsed.
• Include every family member when developing the escape
plan.
• Study the possible escape routes from each location within
the house. Since many fires occur at night, give special
attention to the escape routes from sleeping quarters.
• It is essential that escape from a bedroom be possible with-
out opening the interior door. Consider the following
when making your escape plans:
• Ensure that doors and windows that open to the outside
are easily opened. Ensure that they are not painted shut
and that the locking mechanisms operate smoothly.
• Develop plans for rescue, if opening the exit or using the
exit is too difficult for children, the elderly or handicapped.
This plan includes making sure that those who are to per-
form the rescue can promptly hear the fire warning signal.
• If the exit is above the ground level, provide an approved
fire ladder or rope, as well as training in its use.
• Keep exits on the ground level clear. Be sure to remove
snow from exterior patio doors in the winter and that out-
door furniture or equipment does not block exits.
• Have a predetermined assembly point where everyone can
be accounted for; for example, across the street or at a
neighbor’s house.
• Once everyone is out of the house, call the Fire Depart-
ment.
• A good plan emphasizes a quick escape. Do not investi-
gate first or attempt to fight the fire, and do not attempt
to rescue belongings or valuables as this takes up time.
Once outside, do not re-enter the house; wait for the Fire
Department.
• Write the plan down and rehearse it frequently so that
should an emergency ever arise, everyone will know what
to do. Revise the plan as conditions change; for example,
when there are more or fewer family members in the
home or if there are changes to the house.
• Make sure your fire warning system is operational by con-
ducting weekly tests. If you are unsure about system oper-
ation, contact your smoke detector installer or dealer.
• DSC recommends that you contact your local Fire Depart-
ment and request further information on home fire safety
and escape planning. If available, have your local fire pre-
vention officer conduct an in-house fire safety inspection.
Testing Your Smoke Detector
Follow the test procedure described here or contact your
smoke detector dealer or installer for testing instructions. DSC
recommends that you test the entire alarm system at least
once a week to verify the operation of all system functions.
Pushbutton switch
To test the smoke detector, press and hold the test button on
the front of the unit for 5 seconds minimum, the siren initiates
a clicking noise during this time. When the button is pressed,
the unit’s alarm will sound and an alarm will be sent to the
control panel. When the button is released, the alarm will
cease.
Upon completing the functional testing of the smoke detec-
tor, check the unit’s sensing chamber to ensure proper opera-
tion. To test the sensing chamber, wave a lit cotton wick or
punk stick around the outside of the unit until a generous
amount of smoke enters the sensing chamber or the unit
alarms. Alternatively, spray UL Listed canned smoke at the
chamber (following the instructions provided with the canned
smoke). If the smoke detector does not function properly, call
your smoke detector installer or dealer for service.
Maintenance
The smoke detector is designed to require minimum mainte-
nance. If the case becomes dusty, vacuum with a small brush
attachment. If the case is greasy, wipe the case gently with a
soft cloth slightly dampened with soapy water.
Never disassemble the smoke detector; there are no user
serviceable parts inside the unit. Never paint the unit. Paint
may prevent smoke from entering the unit. If you are plan-
ning renovations or repainting, contact your installer and
ask that the unit be temporarily removed until work is com-
plete.
If the unit is located in an area where it is exposed to high lev-
els of dust or insects and causes false alarms, it may require
service; contact your smoke detector installer or dealer. Testing
and maintenance procedures shall be in accordance with
CAN/ULC-S552.
firealarmresources.com

Smoke Detector Family
Specifications
NOTE: If this detector is used with compatible VISTA series
control panels:
• Set zone debounce time at the maximum of 1.2 seconds
• Consult the Control Unit Installation Manual for additional
compatibility information and limitations. All instructions
specified within that manual must be observed. The DSC
PRM-2W provides an interface for control panels that do
not have a compatible 2-wire smoke detector zone.
• The maximum number of DSC Model FSD-210B series of
detectors connected to the two wire smoke interface
should be limited to 5. If the installation requires the use of
more devices on the two wire loop and alarm interconnect
is not required, please use the DSC Model PRM-2W(C)
Reverse Polarity Module (please refer to the PRM-2W(C)
installation instructions for further information). If the instal-
lation requires more devices and alarm interconnect is
required, we recommend installing FSA-210 series detec-
tors.
FCC Compliance Statement
CAUTION: Changes or modifications not expressly approved by DSC could void your
authority to use this equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device, pur-
suant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harm-
ful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or televi-
sion reception, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
• Re-orient the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is con-
nected.
• Consult the dealer or an experienced radio/television technician for help.
The user may find the following booklet prepared by the FCC useful: “How to Identify and Resolve
Radio/Television Interference Problems”. This booklet is available from the U.S. Government Print-
ing Office, Washington D.C. 20402, Stock # 004-000-00345-4.
Industry Canada Compliance Statement
This Class B digital apparatus meets all requirements of the Canadian interference-causing equip-
ment regulations.
Cet appareil numérique de la Classe B respecte toutes les exigences de règlement sur le matériel
brouilleur du Canada.
IMPORTANT - READ CAREFULLY: DSC Software purchased with or without Products and Components is copyrighted and is purchased
under the following license terms:
• This End-User License Agreement (“EULA”) is a legal agreement between You (the company, individual or entity who acquired the Software and
any related Hardware) and Digital Security Controls, a division of Tyco Safety Products Canada Ltd. (“DSC”), the manufacturer of the integrated
security systems and the developer of the software and any related products or components (“HARDWARE”) which You acquired.
• If the DSC software product (“SOFTWARE PRODUCT” or “SOFTWARE”) is intended to be accompanied by HARDWARE, and is NOT accom-
panied by new HARDWARE, You may not use, copy or install the SOFTWARE PRODUCT. The SOFTWARE PRODUCT includes computer
software, and may include associated media, printed materials, and “online” or electronic documentation.
• Any software provided along with the SOFTWARE PRODUCT that is associated with a separate end-user license agreement is licensed to You
under the terms of that license agreement.
•
By installing, copying, downloading, storing, accessing or otherwise using the SOFTWARE PRODUCT, You agree unconditionally to be bound by the terms
of this EULA, even if this EULA is deemed to be a modification of any previous arrangement or contract. If You do not agree to the terms of this EULA,
DSC is unwilling to license the SOFTWARE PRODUCT to You, and You have no right to use it.
SOFTWARE PRODUCT LICENSE
The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties, as well as other intellectual property laws and treaties.
The SOFTWARE PRODUCT is licensed, not sold.
1. GRANT OF LICENSE This EULA grants You the following rights:
(a) Software Installation and Use - For each license You acquire, You may have only one copy of the SOFTWARE PRODUCT installed.
(b) Storage/Network Use - The SOFTWARE PRODUCT may not be installed, accessed, displayed, run, shared or used concurrently on or from differ-
ent computers, including a workstation, terminal or other digital electronic device (“Device”). In other words, if You have several workstations, You will
have to acquire a license for each workstation where the SOFTWARE will be used.
(c) Backup Copy - You may make back-up copies of the SOFTWARE PRODUCT, but You may only have one copy per license installed at any given
time. You may use the back-up copy solely for archival purposes. Except as expressly provided in this EULA, You may not otherwise make copies of
the SOFTWARE PRODUCT, including the printed materials accompanying the SOFTWARE.
2. DESCRIPTION OF OTHER RIGHTS AND LIMITATIONS
(a) Limitations on Reverse Engineering, Decompilation and Disassembly - You may not reverse engineer, decompile, or disassemble the SOFTWARE
PRODUCT, except and only to the extent that such activity is expressly permitted by applicable law notwithstanding this limitation. You may not make
any changes or modifications to the Software, without the written permission of an officer of DSC. You may not remove any proprietary notices, marks
or labels from the Software Product. You shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA.
(b) Separation of Components - The SOFTWARE PRODUCT is licensed as a single product. Its component parts may not be separated for use on
more than one HARDWARE unit.
(c) Single INTEGRATED PRODUCT - If You acquired this SOFTWARE with HARDWARE, then the SOFTWARE PRODUCT is licensed with
the HARDWARE as a single integrated product. In this case, the SOFTWARE PRODUCT may only be used with the HARDWARE as set forth in this
EULA..
(d) Rental - You may not rent, lease or lend the SOFTWARE PRODUCT. You may not make it available to others or post it on a server or web site.
(e) Software Product Transfer - You may transfer all of Your rights under this EULA only as part of a permanent sale or transfer of the HARDWARE,
provided You retain no copies, You transfer all of the SOFTWARE PRODUCT (including all component parts, the media and printed materials, any
upgrades and this EULA), and provided the recipient agrees to the terms of this EULA. If the SOFTWARE PRODUCT is an upgrade, any transfer must
also include all prior versions of the SOFTWARE PRODUCT.
(f) Termination - Without prejudice to any other rights, DSC may terminate this EULA if You fail to comply with the terms and conditions of this
EULA. In such event, You must destroy all copies of the SOFTWARE PRODUCT and all of its component parts.
(g) Trademarks - This EULA does not grant You any rights in connection with any trademarks or service marks of DSC or its suppliers.
3. COPYRIGHT - All title and intellectual property rights in and to the SOFTWARE PRODUCT (including but not limited to any images, photo-
graphs, and text incorporated into the SOFTWARE PRODUCT), the accompanying printed materials, and any copies of the SOFTWARE PRODUCT,
are owned by DSC or its suppliers. You may not copy the printed materials accompanying the SOFTWARE PRODUCT. All title and intellectual prop-
erty rights in and to the content which may be accessed through use of the SOFTWARE PRODUCT are the property of the respective content owner
and may be protected by applicable copyright or other intellectual property laws and treaties. This EULA grants You no rights to use such content. All
rights not expressly granted under this EULA are reserved by DSC and its suppliers.
4. EXPORT RESTRICTIONS - You agree that You will not export or re-export the SOFTWARE PRODUCT to any country, person, or entity sub-
ject to Canadian export restrictions.
5. CHOICE OF LAW - This Software License Agreement is governed by the laws of the Province of Ontario, Canada.
6. ARBITRATION - All disputes arising in connection with this Agreement shall be determined by final and binding arbitration in accordance with
the Arbitration Act, and the parties agree to be bound by the arbitrator’s decision. The place of arbitration shall be Toronto, Canada, and the language of
the arbitration shall be English.
7. LIMITED WARRANTY
(a) NO WARRANTY - DSC PROVIDES THE SOFTWARE “AS IS” WITHOUT WARRANTY. DSC DOES NOT WARRANT THAT THE SOFT-
WARE WILL MEET YOUR REQUIREMENTS OR THAT OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-
FREE.
(b) CHANGES IN OPERATING ENVIRONMENT - DSC shall not be responsible for problems caused by changes in the operating characteristics of
the HARDWARE, or for problems in the interaction of the SOFTWARE PRODUCT with non-DSC-SOFTWARE or HARDWARE PRODUCTS.
(c) LIMITATION OF LIABILITY; WARRANTY REFLECTS ALLOCATION OF RISK - IN ANY EVENT, IF ANY STATUTE IMPLIES WAR-
RANTIES OR CONDITIONS NOT STATED IN THIS LICENSE AGREEMENT, DSC’S ENTIRE LIABILITY UNDER ANY PROVISION OF
THIS LICENSE AGREEMENT SHALL BE LIMITED TO THE GREATER OF THE AMOUNT ACTUALLY PAID BY YOU TO LICENSE THE
SOFTWARE PRODUCT AND FIVE CANADIAN DOLLARS (CAD$5.00). BECAUSE SOME JURISDICTIONS DO NOT ALLOW THE
EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY
NOT APPLY TO YOU.
(d) DISCLAIMER OF WARRANTIES - THIS WARRANTY CONTAINS THE ENTIRE WARRANTY AND SHALL BE IN LIEU OF ANY AND
ALL OTHER WARRANTIES, WHETHER EXPRESSED OR IMPLIED (INCLUDING ALL IMPLIED WARRANTIES OF MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE) AND OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF DSC. DSC
MAKES NO OTHER WARRANTIES. DSC NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON PURPORTING TO ACT ON
ITS BEHALF TO MODIFY OR TO CHANGE THIS WARRANTY, NOR TO ASSUME FOR IT ANY OTHER WARRANTY OR LIABILITY
CONCERNING THIS SOFTWARE PRODUCT.
(e) EXCLUSIVE REMEDY AND LIMITATION OF WARRANTY - UNDER NO CIRCUMSTANCES SHALL DSC BE LIABLE FOR ANY
SPECIAL, INCIDENTAL, CONSEQUENTIAL OR INDIRECT DAMAGES BASED UPON BREACH OF WARRANTY, BREACH OF CON-
TRACT, NEGLIGENCE, STRICT LIABILITY, OR ANY OTHER LEGAL THEORY. SUCH DAMAGES INCLUDE, BUT ARE NOT LIMITED
TO, LOSS OF PROFITS, LOSS OF THE SOFTWARE PRODUCT OR ANY ASSOCIATED EQUIPMENT, COST OF CAPITAL, COST OF SUB-
STITUTE OR REPLACEMENT EQUIPMENT, FACILITIES OR SERVICES, DOWN TIME, PURCHASERS TIME, THE CLAIMS OF THIRD
PARTIES, INCLUDING CUSTOMERS, AND INJURY TO PROPERTY. WARNING:
DSC recommends that the entire system be completely tested on a regular basis. However, despite frequent testing, and due to, but not limited to, crim-
inal tampering or electrical disruption, it is possible for this SOFTWARE PRODUCT to fail to perform as expected.
Model Heat Siren Aux
Relay
LED
Output
Max.
Alarm
Current
Draw
FSD-210AS, FSD-210BS NO YES NO NO 60mA
FSD-210AST, FSD-210BST YES YES NO NO 60mA
FSD-210BRS NO YES YES NO 75mA
FSD-210BRST YES YES YES NO 75mA
Diameter (base) . . . . . . . . . . . . . . . . . . . . . . . . . . 5.8in (147mm)
Height (including base). . . . . . . . . . . . . . . . . . . . 2.077in (528mm)
Operating Temperature . . . . . . . . . . . . . . . .32º-100ºF (0º-37.8ºC)
Humidity . . . . . . . . . . . . . . . . . . . . 5%-93% RH, non-condensing
Maximum Operating Voltage Range. . . . . . . . . . . . . 9.35 - 30VDC
Maximum Standby Current . . . . . . . . . . . . . . 20A@12 or 24VDC
Maximum Alarm Current: . . . . . . . . . . . . . . . . . . . . . . .60-75 mA
Smoke Sensitivity ULC . . . . . . . . . . . . . . 2%±0.5%/ft obscuration
Smoke Sensitivity UL . . . . . . . . . . . . . . . 3%±0.8%/ft obscuration
Heat Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135ºF (57ºC)
Siren Alarm Pattern UL. . . . . . . . . . . .Evacuation Temporal Pattern
Siren Alarm Pattern ULC. . . . . . . . . . . . . . . . . . Continuous Beeps
Auxiliary Relay Rating (Form C Relay) . . . . . 2A @ 30VDC (Resistive)
FSD-210 series compatibility identifier: . . . . . . . . . . . . . . . .FS200
DSC Compatible Control Units:
DSC PC1864 with compatibility identifier: . . . . . . . . .PC18-1
DSC PC1832 with compatibility identifier: . . . . . . . . .PC18-1
DSC PC1616 with compatibility identifier: . . . . . . . . .PC18-1
DSC PC1555 with compatibility identifier: . . . . . . . . .PC15-1
DSC PC5010 with compatibility identifier: . . . . . . . . . .PC5-1
DSC PC5015 with compatibility identifier: . . . . . . . . .PC15-1
DSC PC5020 with compatibility identifier: . . . . . . . . . .PC5-2
DSC PC4020 with compatibility identifier: . . . . . . . . . . FM-2
DSC PRM-2W with compatibility identifier: . . . . . . . . PR200
R = Auxiliary For m C Relay
S = Sounder/Siren
T = FixedTemperature Heat Sensor
FSD-210 XYYY
A = ULC
B = UL
2-Wire Smoke Detector Family
© 2011 Tyco International Ltd. and itsRespective Companies. All RightsReserved.
Tech Support: 1-800-387-3630 (Canada& U.S.) or 905-760-3000
Printed in Czech 17 • www.dsc.com
firealarmresources.com
Other Tyco Smoke Alarm manuals

Tyco
Tyco Visonic SMD-426 PG2 User manual

Tyco
Tyco Visonic SMD-429 PG2 Series User manual

Tyco
Tyco SB User manual

Tyco
Tyco Fire Alarm User guide

Tyco
Tyco Xtralis VESDA VLC-800MX User guide

Tyco
Tyco MX4428 User manual

Tyco
Tyco 601PH User manual

Tyco
Tyco B-1 User manual

Tyco
Tyco FP1600 User manual

Tyco
Tyco MR601TEx User manual
Popular Smoke Alarm manuals by other brands

EDS
EDS RK100B user guide

SOMFY
SOMFY TaHoma 2401368 installation guide

CALECTRO
CALECTRO Uniguard Superflow UG-3-J Installation instruction

Ei Electronics
Ei Electronics Ei 100R Ionisation Technical specifications

AROHA
AROHA SM11 manual

System Sensor
System Sensor 7251 Installation and maintenance instructions