UniPOS IFS7002 User manual

UniPOS
Interactive Fire Control Panel
IFS7002
Instruction Manual
Revision 2.05

UniPOS Interactive Fire Control Panel IFS7002
Instruction Manual Page 2
Revision 2.05 Of 107
Contents
1. Introduction...................................................................................................................................6
2. Terminology...................................................................................................................................6
3. Function.........................................................................................................................................8
4. Technical data ...............................................................................................................................8
4.1. Physical configuration.........................................................................................................................8
4.2. Fire alarm zones..................................................................................................................................8
4.3. Fire alarm loops...................................................................................................................................8
4.4. Power loop............................................................................................................................................8
4.5. Monitored outputs...............................................................................................................................9
4.6. Relay outputs for fire conditions........................................................................................................9
4.7. Relay output for fault conditions.......................................................................................................9
4.8. Performance.........................................................................................................................................9
4.9. Indications of registered events..........................................................................................................9
4.10. Power supply......................................................................................................................................9
4.10.1. Mains............................................................................................................................................................9
4.10.2. Back up batteries..........................................................................................................................................9
4.10.3. Consumption on back up batteries supply....................................................................................................9
4.10.4. Power supply to external devices ...............................................................................................................10
4.11. Dimensions.......................................................................................................................................10
4.12. Weight ..............................................................................................................................................10
5. Contents of delivery.....................................................................................................................10
6. General information....................................................................................................................10
6.1. Access levels.......................................................................................................................................10
6.1.1. Access Level 1 .............................................................................................................................................10
6.1.2. Access Level 2 .............................................................................................................................................10
6.1.3. Access Level 3 .............................................................................................................................................11
6.1.4. Access Level 4 .............................................................................................................................................11
6.2. Indications and buttons for control.................................................................................................11
6.3. Zone in Coincidence Mode ...............................................................................................................13
6.4. Operation of the fire control panel..................................................................................................13
7. Duty Mode....................................................................................................................................15
7.1. Description.........................................................................................................................................15
7.2. Indication ...........................................................................................................................................15
7.2.1. LED and sound indication............................................................................................................................15
7.2.2. Text message................................................................................................................................................16
7.3. Using the keypad ...............................................................................................................................16
8. Fire condition ..............................................................................................................................16
8.1. Description.........................................................................................................................................16
8.2. Indication ...........................................................................................................................................16
8.2.1. LED and sound indication............................................................................................................................16
8.2.2. Text messages ..............................................................................................................................................17
8.3. Using the keypad ...............................................................................................................................17

UniPOS Interactive Fire Control Panel IFS7002
Instruction Manual Page 3
Revision 2.05 Of 107
9. Fault Condition ...........................................................................................................................20
9.1. Description.........................................................................................................................................20
9.2. Indication ...........................................................................................................................................21
9.2.1. LED and sound indication............................................................................................................................21
9.2.2. Text messages ..............................................................................................................................................21
9.3. Using the keypad ...............................................................................................................................22
10. Disabled component ..................................................................................................................22
10.1. Description.......................................................................................................................................22
10.2. Indication .........................................................................................................................................22
10.2.1. LED and sound indication..........................................................................................................................22
10.2.2. Text messages ............................................................................................................................................23
10.3. Using the keypad .............................................................................................................................23
11. Test Mode...................................................................................................................................23
11.1. Description.......................................................................................................................................23
11.2. Indicators .........................................................................................................................................23
11.2.1. LEDs and sound indicators ........................................................................................................................23
11.2.2. Text messages ............................................................................................................................................23
11.3. Using the keypad .............................................................................................................................24
12. Information and Control Mode.................................................................................................24
12.1. Description.......................................................................................................................................24
12.2. Menu Lists........................................................................................................................................24
12.2.1. Menu Faults...............................................................................................................................................25
12.2.2. Menu Disables ...........................................................................................................................................26
12.2.3. Menu Zones in Test....................................................................................................................................28
12.2.4. Screen Panel configuration........................................................................................................................30
12.2.5. Menu Panel parameters.............................................................................................................................30
12.2.6. Menu Loops................................................................................................................................................30
12.2.7. Menu Zones................................................................................................................................................32
12.2.8. Menu Device Status....................................................................................................................................35
12.2.9. Menu Inputs ...............................................................................................................................................38
12.2.10. Menu Archive...........................................................................................................................................39
12.3. Menu System functions....................................................................................................................46
12.3.1. Menu Disables ...........................................................................................................................................47
12.3.2. Menu Zones in Test....................................................................................................................................50
12.3.3. Function Set Clock .....................................................................................................................................51
12.3.4. Function Set Mode......................................................................................................................................52
12.3.5. Function Check LEDs and Buzzer..............................................................................................................52
12.4. Menu Set Up.....................................................................................................................................53
13. Set Up Mode...............................................................................................................................53
13.1. Description.......................................................................................................................................53
13.2. Menu Panel configuration...............................................................................................................54
13.3. Menu Panel parameters...................................................................................................................55
13.4. Menu Loops......................................................................................................................................55
13.4.1. Menu Loop parameters..............................................................................................................................55
13.4.2. Menu Device parameters..........................................................................................................................56

UniPOS Interactive Fire Control Panel IFS7002
Instruction Manual Page 4
Revision 2.05 Of 107
13.5. Menu Zones......................................................................................................................................59
13.5.1. Menu Devices.............................................................................................................................................60
13.5.2. Menus Fire Phase 1 Outputs and Fire Phase 2 Outputs............................................................................65
13.5.3. Menu Zone parameters..............................................................................................................................68
13.5.4. Screen Text message ..................................................................................................................................69
13.6. Menu Inputs.....................................................................................................................................71
13.6.1. Screen List of addressable outputs.............................................................................................................72
13.6.2. Menu Remove addressable output .............................................................................................................72
13.6.3. Menu Add addressable output....................................................................................................................73
13.6.4. Menu Text message....................................................................................................................................74
13.7. Menu Initialization...........................................................................................................................76
13.7.1. Function Initialization................................................................................................................................77
13.7.2. Function Clean initialization......................................................................................................................78
13.7.3. Menu Readdressing....................................................................................................................................79
13.7.4. Menu Exclude devices................................................................................................................................80
13.7.5. Menu Check ...............................................................................................................................................81
13.8. Menu Checks....................................................................................................................................83
13.8.1. Menu Monitored outputs............................................................................................................................83
13.8.2. Menu Relay outputs....................................................................................................................................83
13.8.3. Menu Addressable outputs.........................................................................................................................84
13.8.4. Function Display........................................................................................................................................85
13.8.5. Menu Buttons.............................................................................................................................................85
13.9. Menu New passwords.......................................................................................................................87
13.9.1. Menu Level 2..............................................................................................................................................87
13.9.2. Function Level 3.........................................................................................................................................87
13.10. Function Default parameters.........................................................................................................88
13.11. Function Clear archive ..................................................................................................................89
14. Remote Control Mode................................................................................................................90
14.1. Description.......................................................................................................................................90
14.2. Indication .........................................................................................................................................90
14.2.1. LED and sound indication..........................................................................................................................90
14.2.2. Тext messages ............................................................................................................................................90
14.3. Keypad..............................................................................................................................................90
15. Saving the parameters...............................................................................................................91
16. Labour protection requirements ...............................................................................................91
17. Installation and arrangements..................................................................................................91
17.1. To mount the fire control panel .....................................................................................................91
17.2. Periphery devices assembly............................................................................................................91
17.2.1. Mounting periphery devices to monitored outputs.....................................................................................91
17.2.2. Mounting periphery devices to relay outputs .............................................................................................91
17.3. Connecting interface devices..........................................................................................................92
17.3.1. Global network...........................................................................................................................................92
17.3.2. Local network ............................................................................................................................................92
17.4. Connecting addressable fie detectors.............................................................................................92
17.5. Power supply connection ................................................................................................................93
18. Fire control panel start up ........................................................................................................93
19. Troubleshooting.........................................................................................................................93

UniPOS Interactive Fire Control Panel IFS7002
Instruction Manual Page 5
Revision 2.05 Of 107
20. Conditions of operation, storage and transportation...............................................................96
20.1. Operation and storage.....................................................................................................................96
20.1.1. Temperature ...............................................................................................................................................96
20.1.2. Relative humidity.......................................................................................................................................96
20.2. Transportation.................................................................................................................................96
21. Warranty....................................................................................................................................96
22. Appendixes.................................................................................................................................97

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 6
Revision 2.05 Of 107
1. Introduction
Interactive Fire Control Panel IFS 7002 is an up-to-date, high reliable, multifunctional and
versatile device, providing the user with unexpected potential in the design, installation and operation
of addressable fire alarm systems.
Some of its main features and possibilities are:
−Adjustment of operating modes and parameters of each fire alarm line via built in keypad;
−User oriented menu dialogue for easy and convenient operation;
−LCD for visualization of system checkup and setup modes;
−Touch-panel contributing to the creation of a dynamic keypad;
−LEDs indication for early warning of a break down or extreme conditions;
−Energy independent archive memory saving the event type, date and time, allowing for
detailed analysis of the actions of the authorized personnel and of possible problems in the
fire protection process of the area;
−User oriented test modes allowing for a total control of the site protected;
−Built-in serial interface for connection to other fire control panels of similar or higher level;
−Built-in serial interface for connection to second level control devices, ability for connection via
telephone line and a standard modem;
−System expansion and functional modification (our goal is to constantly improve the fire alarm
equipment features), no additional cabling necessary;
−Compatible to random installation design, within the range of the available fire control panels
resources.
All these are realizable via fire control panel’s keypad and after a detailed examination of the
instructions set herewith.
2. Terminology
ACCESS LEVEL – access level to various indications and control functions.
ADDRESSABLE DEVICE – a device included in one of the fire alarm loops that has its own
address for communication with the fire control panel. An addressable device can be a fire detector
(automatic or manual call point), a conventional line-monitoring module or an input/output module.
ADDRESSABLE OUTPUT – potential or relay output of an addressable executive device included
in fire alarm loops. The executive device can be power supplied from the fire alarm loop or from the
power supply loop.
ASSOCIATED OUTPUT – addressable monitored or relay output, user programmed to react
upon Fire condition (separately upon Fire condition I and Fire condition II) via selected fire alarm
zone.
COINCIDENCE MODE– mode of operation of the fire alarm zones, that requires activation of at
least two automatic fire detectors in a zone so the fire control panel is able to enter Fire condition,
phase Fire condition stage I, in this particular zone (see section 6.3).
DEVICE REMOVED – non-fatal fault condition due to removed device (addressable fire detector
of a specific zone and/or addressable executive device).
DISABLED ADDRESSABLE/MONITORED OUTPUT – the addressable/ monitored output is
switched off (the executive device can not be activated) and is not monitored for a fault condition. This
feature is user defined. The indication for a disabled addressable/monitored output is common light
indication and text messages on the LCD display.

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 7
Revision 2.05 Of 107
DISABLED DEVICE – the addressable device (a fire detector) is switched off and is not
monitored for a fault condition. This feature is user defined. The indication for a disabled device is
common light indication and text messages on the LCD display
DISABLED ZONE – a zone that is not controlled for activated fire detectors and fault condition.
This condition is user defined. The indication for a disabled zone is common light indication and text
messages on the LCD display.
FATAL FAULT CONDITION – fault condition that prevents the fire control panel from continuing
its operation. The indication is common light indication, local sound indication and text messages on
the LCD display.
FIRE ALARM LOOP (further on it will be referred as LOOP) – automatic fire detectors and
addressable manual call points and addressable executive devices, physically connected by the
means of two-wire connection. The basic configuration of IFS 7002 includes two fire alarm loops; a
maximum of 125 devices (addressable fire detectors and/or addressable executive devices) can be
integrated into each loop.
FIRE ALARM ZONE (further on it will be referred as ZONE) – logical unification of automatic fire
detectors and addressable manual call points, physically allocated in fire alarm loops on random
principle. Interactive Fire Control Panel IFS7002 allows for formation of a maximum of 250 zones. Up
to 60 fire detectors can be integrated in each zone.
FIRE CONDITION STAGE I – phase 1 of Fire condition; upon activation of automatic fire detector
the fire control panel enters Fire condition until the specified time expires. The common and local light
indicators, local sound signaling and a text message displayed on the LCD display indicate the phase.
FIRE CONDITION STAGE II – phase 2 of Fire condition; the fire control panel enters Fire
condition stage II when: a) the time for Fire condition stage I has expired or b) upon activation of a
manual call point. The common light indicators, local sound signaling and a text message displayed
on the LCD display indicate the phase.
GROUNDS – non-fatal fault condition, due to leakage to a grounded wire.
INSPECTION TIME – period of time added to the remaining time, before the system proceeds
from Fire condition stage I to Fire condition stage II, when button is pressed. Usually, this
period of time is long enough for the authorized personnel to check up the indicated premises. The
inspection time is user defined and is specified for each zone.
INTERRUPTED LOOP OR MONITORED OUTPUT – non-fatal fault condition due to current
value in a loop or in monitored output lower than the threshold value. The user shall define the
threshold value separately for each loop.
LOCAL SOUNDER – a sounder built-in the fire control panel.
LOW BATTERY – fatal fault condition due to full discharge of the backup batteries upon
interrupted power supply.
MONITORED OUTPUT – a potential output that monitors the serviceability of the connection
wires between the fire control panel and the executive device. Follow the special diagram for
connection.
NON-FATAL FAULT CONDITION – fault condition that allows the fire control panel to continue
operation. The indication is common light indication, local sound indication and text messages on the
LCD display.

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 8
Revision 2.05 Of 107
POWER LOOP – a two-wire connection supplying power to addressable executive devices in
case their consumption exceeds the load carrying capacity of the fire alarm loops, which they have
been integrated into. IFS7002 has 1 power loop, its load carrying capacity is 1000 mA.
PROCEEDING FROM FIRE CONDITION STAGE I TO FIRE CONDITION STAGE II – the time is
user defined for each zone separately. During the phase Fire condition stage I the remaining time for
the selected fire alarm line is indicated on the LCD display. During the remaining time actions can be
taken, for example press or .
RELAY OUTPUT – a relay, potential-free switching outputs provided for controlling external
executive devices.
SHORT CIRCUIT IN A LOOP – non-fatal fault condition, entered due to registered current value
in a loop, exceeding a threshold value. The threshold value for each loop shall be user defined.
SHORT CIRCUIT IN A MONITORED OUTPUT – non-fatal fault condition, entered due to
registered current value in a monitored output, exceeding a threshold value.
SYSTEM ERROR – fatal fault condition due to a fault in system’s basic component
SYSTEM OPERATION – the fire control panel executes internal operations to set its registers.
This is visualized on the LCD display with a text message for system operations, before the user is
allowed to proceed with his work with IFS7002.
ZONE IN TEST – a zone set in Test condition by the user. The zone is reset (the fire detectors in
fire condition receive a command to clear the condition) periodically every 60 s. The events registered
in a zone in Test condition are not saved in the archive and do not trigger the associated outputs or
the light and sound signalling. The indication for a zone in Test condition is common light indication.
3. Function
Interactive Fire Control Panel IFS7002 is designed to operate with addressable automatic fire
detectors and manual call points. It controls addressable executive devices integrated into fire alarm
loops. The addressable executive devices can be power supplied from the fire alarm loop or from a
power loop. The panel has outputs provided for integration of external executive devices.
4. Technical data
4.1. Physical configuration
−2 fire alarm loops
−1 power loop
−2 monitored outputs
−2 relay outputs for fire condition
−1 relay output for fault conditions
4.2. Fire alarm zones
−Maximum number of zones - 250
−Maximum number of fire detectors in a zone - 60
4.3. Fire alarm loops
−Maximum number of fire detectors in a loop - 125
−Connecting line - two-wire shielded
−Maximum resistance of a loop - 100Ω
−Output resistance of a loop - 20Ω
−Maximum consumption of a loop - 120mA
4.4. Power loop
−Connecting line - two-wire
−Maximum resistance of the loop - 10Ω
−Output resistance of the loop - 2Ω
−Maximum consumption of the loop - 1A

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 9
Revision 2.05 Of 107
4.5. Monitored outputs
−Type - potential
−Еlectrical characteristics - (24±5)V/100mA
4.6. Relay outputs for fire conditions
−Type - potential free, switching,
−Electrical characteristics - 3A/125VAC; 3A/30VDC
4.7. Relay output for fault conditions
−Type - potential free, switching
−Electrical characteristics - 3A/125VAC; 3A/30VDC
4.8. Performance
−Control over fire alarm loops and monitored outputs for fault conditions (short circuit
and interruption) and automatic reset
−Detection of removed devices in the loops and automatic reset
−Ability to set the zones in Coincidence Mode
−Two phases of Fire condition, programmable time for Fire condition stage I,
separately for each zone
−Option to prolong the time period for Fire condition stage I with programmable
inspection period, specified for each zone
−Built-in sounder for fire condition – one tonal, discontinuous, can be switched off
−Built-in sounder for fault condition – one tonal, discontinuous, can be switched off
−Built-in real time clock
−Set of test modes and options for adjustment:
♦Setting the clock;
♦Check ups on light and sound indications;
♦Test of fire alarm zones;
♦Adjustment of outputs and integrated external devices;
♦Programming of parameters and modes of operation;
♦Remote programming of the parameters from distant operator control point;
−Energy independent archive of registered events with the events type, date and hour
– up to 1023 events;
−Interfaces for communication with external devices - CAN 2.0B and RS-232
(directly or via modem).
4.9. Indications of registered events
−Light indication - LED
−Text messages - LCD display,
320 х240 points, backlit
−Sound signaling - built-in sounder
4.10. Power supply
4.10.1. Mains
−voltage - 220/230V
−frequency - 50Hz
4.10.2. Back up batteries
−battery type - lead, gel electrolyte
−number of batteries - 2 pcs
−connection - serial connection
−nominal voltage of the back up battery - 24V
−nominal capacity C20 - 18Ah
−extreme discharge voltage - 21V
−charge voltage - 28,2V
4.10.3. Consumption on back up batteries supply
−at 24V - < 250mA
−at 26V - < 240mA

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 10
Revision 2.05 Of 107
4.10.4. Power supply to external devices
−Voltage - (24±5)V
−Maximum current value (including current
of monitored outputs and power loop) - 1,5А
4.11. Dimensions
−Overall dimensions - 480x445x100mm
4.12. Weight
−Weight (batteries not included) - 7,1kg
5. Contents of delivery
−Fire control panel IFS7002 - 1 pc
−Resistors 5,6kΩ/ 0,25W - 2 pcs
−Jumper for the backup batteries - 1 pc
−Fuse 4A - 2 pcs
−Instruction manual - 1 pc
−Instructions for authorized staff - 1 pc
−Packing - 1 pc
6. General information
6.1. Access levels
4 levels of access to the variable indications and control functions of IFS7002 are available.
6.1.1. Access Level 1
All persons who would presumably find out and react to alarm upon fault condition or fire
condition have access to level 1.
The following actions are accessible:
−Displaying suppressed messages for Fire condition, Fault condition, Disabled
components and Zone in test (see sections 8, 12.2.1, 12.2.2 and 12.2.3);
−Entering inspection time period (see section 8.3.1);
−Forced proceeding from phase Fire condition stage I to phase Fire condition stage II (see
section 8);
−Suppressing the local sounder (see sections 8 and 9);
−Displaying program data for the fire control panel (see sections 12.2.4 to 12.2.7 and
12.2.9);
−Displaying the status of the addressable devices in the loops (see section 12.2.8);
−Displaying the archive (see section 12.2.10).
All light indicators are visible.
6.1.2. Access Level 2
The personnel in charge of the fire protection have access to level 2; they shall be authorized and
trained to operate the fire control panel in the following conditions:
−Duty Mode;
−Fire condition;
−Fault condition;
−Disabled component;
−Information and adjustment.
To enter Access level 2 use your password.
The following features of the fire control panel are accessible:
−All features accessible at Level 1;
−Switching off the outputs, activated upon fire condition (see section 8);
−Exit of Fire condition (see section 8);
−System functions of the fire control panel (see section 12.3).

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 11
Revision 2.05 Of 107
6.1.3. Access Level 3
Accessible for personnel trained and authorized for:
−Reconfiguration of specific data – of the protected site or of the fire control panel – saved
in the memory;
−Maintenance of the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password entered at Access level 2. At this sublevel
the functions for reconfiguration of specific data for the protected site or the fire control panel are
accessible (see section 13).
Level 3, sublevel 3B is accessed when the fire control panel is opened. The following features are
accessible:
−Replacing a burnt fuse;
−Connecting fire alarm loops and executive devices.
6.1.4. Access Level 4
Accessible for personnel trained and authorized by the Producer to repair the fire control panel
and to modify the software. Special means are required to enter this level.
6.2. Indications and buttons for control
Table 1 gives detail description of the indications for each status, Table 2 presents the basic
means for control. Appendix 1 shows the front panel of IFS7002.
Table 1
Conditions of the fire control panel Indication
All conditions -
The fire control panel is power supplied
Indicator Power supply –
continuous green light
Fire condition Common indicator Fire condition –
flashing red light
Fault condition -
All faults except for Battery Low
Common indicator Fault condition
– flashing yellow light
Fault condition – System error Indicator System error - continuous
yellow light
Fault condition -
Fault in mains supply
Indicator Fault in mains supply -
flashing yellow light
Disabled component -
Disabled zone, addressable device or monitored
output
Indicator Disabled component -
continuous yellow light
Test condition Indicator Test –
continuous yellow light
Fire condition Local sounder – discontinuous signal: 0.5 s
sound, followed by 0.5s break
Fault condition - All faults except for Battery Low Local sounder – discontinuous signal: 1 s
sound, followed by 1 s break
Fault condition -
Low battery
Local sounder – discontinuous signal: 1 s
sound, followed by 3 s break

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 12
Revision 2.05 Of 107
Table 2
Means of control Condition of the fire
control panel Access
level Operation
Button Reset Fire
Fire condition Level 2 To exit the Fire condition
Fire condition, phase
Fire condition stage I Level 1 To force transition from Fire condition stage
Ito Fire condition stage II
Fire condition, phase
Fire condition stage I Level 2
- upon activated outputs for fire condition –
to suppress the outputs;
- if no outputs for fire condition are
activated - to force transition to phase Fire
condition stage II
Button Outputs
(no suppressed
outputs) or
(suppressed
outputs) Fire condition, phase
Fire condition stage II Level 2
- upon activated outputs for fire condition –
to suppress the outputs
- if no outputs for fire condition are
activated – to activate all suppressed
outputs
Button Inspection
Fire condition, phase
Fire condition stage I
Levels
1 and 2 To add time period for inspection
Button Stop Alarm
Fire condition and
Fault condition (with
the exception of Fatal
Fault Condition)
Levels
1 and 2 To suppress the local sounder
Button Menu
Duty mode, Fire
condition, Fault
condition (with the
exception of Fatal
Fault Condition) Test
mode and Disabled
component
Level 1 To enter Information and Control mode
Information and
Control Mode Level 1 To enter a selected menu
Information and
Control Mode Level 2
Button Enter
SetUp Mode Level 3А
- To enter a selected menu;
- To execute a selected command;
- To save a modified parameter
Information and
Control Mode
Levels
1 and 2
Button Down
SetUp Mode Level 3А
To display the next element of the menu
Information and
Control Mode
Levels
1 and 2
Button Up
SetUp Mode Level 3А
To display the previous element of the
menu
Information and
Control Mode
Levels
1 and 2 To exit Information and Control Mode
Button Exit
SetUp Mode Level 3АTo exit SetUp Mode and reset the system

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 13
Revision 2.05 Of 107
Means of control Condition of the fire
control panel Access
level Operation
Information and
Control Mode
Levels
1 and 2
Button Cancel
SetUp Mode Level 3А
- To exit a function without saving changes
in the parameter; the command will not be
executed;
- To exit the current menu and to move to
an upper hierarchy menu
Information and
Control Mode
Levels
1 and 2
Button Change
SetUp Mode Level 3А
To change an element to its next
permissible
Fire condition and
Information and
Control Mode
Levels
1 and 2
Button Move down
SetUp Mode Level 3А
Next element (if any are available) from the
left window
Fire condition and
Information and
Control Mode
Levels
1 and 2
Button Move up
SetUp Mode Level 3А
Previous element (if any are available) from
the left window
Button Page down
Information and
Control Mode Level 1 Next page from the left window
Button Page up
Information and
Control Mode Level 1 Previous page from the left window
Information and
Control Mode
Levels
1 and 2
- To move the cursor one position to the
right;
- Next element (if any are available) from
the left window
Button To the right
SetUp Mode Level 3АTo move the cursor one position to the right
Information and
Control Mode
Levels
1 and 2
- To move the cursor one position to the
left;
- Next element (if any are available) from
the left window
Button To the left
SetUp Mode Level 3АTo move the cursor one position to the left
Information and
Control Mode
Levels
1 and 2
Button Clear
SetUp Mode Level 3А
To delete a character pointed by the cursor
(if no character is pointed, the first
character to the left of the cursor will be
deleted)
Information and
Control Mode
Levels
1 and 2
Buttons with digits,
characters and
symbols SetUp Mode Level 3А
To insert a character/symbol to the left of
the cursor
6.3. Zone in Coincidence Mode
Coincidence Mode allows for enhanced certainty that a zone has entered Fire condition, phase
Fire condition stage I. The mode requires that at least two fire detectors from this zone shall be
activated to trigger Fire condition, phase Fire condition stage I in the fire control panel.
С

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 14
Revision 2.05 Of 107
The Coincidence Mode is not applicable to manual call points. If a manual call point, included in a
zone set to Coincidence Mode, responds, the fire control panel enters Fire condition, phase Fire
condition stage II in this particular zone.
Upon activation of an automatic fire detector from a zone set to Coincidence Mode, but the fire
control panel has not entered Fire condition in this zone, then:
−If no other automatic fire detector is activated, the zone enters Pre-Fire condition;
−If another automatic fire detector is activated, i.e. the zone is in Pre-Fire condition, then the
fire control panel enters Fire condition, phase Fire condition stage I, in this particular zone.
Exit from Pre-Fire condition in a zone is done automatically only:
−Upon activation of a second automatic fire detector in the zone within 60 s from the Pre-Fire
condition (the fire control panel enters Fire condition, phase Fire condition stage I, in this
particular zone);
−Upon activation of a manual call point in the zone, within 60 s from the Pre-Fire condition (the
fire control panel enters Fire condition, phase Fire condition stage II, in this particular zone)
−Where the 60 s of Pre-Fire condition expire and neither of the above mentioned two conditions
is carried out (the first activated fire detector then receives a command to reset the fire
condition).
To set a zone in Coincidence Mode you need to appoint the parameter Coincidence Mode for this
zone (see section 13.5.3).
While using the Coincidence Mode in a zone, we recommend you to include just one group of
automatic fire detectors (minimum 2 fire detectors) in this zone, allocated in one and the same room,
so upon activation of any two fire detectors you obtain a firm indication for fire in the room.
6.4. Operation of the fire control panel
When IFS7002 is switched on, reset of the system devices and initialization of the addressable
devices integrated in the loops are being done – addressable devices parameters (address,
identification number, type and class) are being verified against these saved in the energy
independent memory of the fire control panel. A text message -System operations - is displayed on
the LCD.
Upon completion of the system operations the fire control panel enters operation mode – it
monitors the addressable devices (automatic fire detectors, manual call points and executive devices)
by consecutively scanning their condition. Simultaneously, a constant control over the loops, the
monitored outputs and the voltage for fault conditions is being carried out.
The fire control panel IFS7002 operates in eight basic modes: Duty Mode, Fire Condition, Fault
Condition, Disabled Component Mode, Test Mode, Information and Control Mode, SetUp Mode and
Remote Control Mode.
Duty Mode, SetUp Mode and Remote Control Mode can not be combined with another mode:
−the fire control panel enters Duty Mode after all other conditions are exited;
−when the fire control panel enters SetUp Mode or Remote Control Mode it exits all other
conditions.
When the fire control panel is in Fire condition or in Fault condition or in a combination of one of
these, the lighting of the display is constantly on, until you press button Stop alarm (with the
exception of these fault conditions – Battery low, discharged batteries due to interruption of mains
supply, and Fault in mains supply). Upon Battery low the lighting of the display is constantly off. In all
other cases the lighting is extinguished 3 min after the last pressing of any button on the display.
Up to 250 fire alarm zones can be formed in IFS7002. Except for these zones the fire control
panel supports two additional zones:
−Service zone (Zone 0) – here addressable devices which location in the loop can not be
detected synonymously are integrated;
−Zone 255 – here addressable devices not included or that can not be included in a fire alarm
zone (addressable output and input devices) are integrated.
When a removed addressable device is replaced in a loop, the fire control panel runs initialization
once again and verifies its parameters (previous address, identification number, type and class)
against these saved in the energy independent memory. While this operation is being executed, the
text message ReInitialization appears on the display.

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 15
Revision 2.05 Of 107
Depending on the result of the verification, the fire control panel would execute the following
operations:
a) if the fire control panel is able to synonymously detect the location of a device in a loop and to
verify its parameters against these saved in the energy independent memory:
♦the device is placed in service with its previous address in the loop;
♦the fault Removed device is cleared;
b) if the fire control panel is able to synonymously detect the location of a device in a loop, but
the device’s parameters do not conform with these saved in the energy independent memory:
♦the device is placed in service with an address, corresponding to device’s location in
the loop;
♦a fault condition due to incompliance with identification number, type or class is
added;
♦the device is included in the Service zone;
c) if the fire control panel is not able to synonymously detect the location of a device in a loop
(two or more serial devices forming an area are removed, but only some replaced):
♦the device is placed in service with the first available address from the corresponding
area in the loop;
♦a fault is added, Device not initialized;
♦the device is included in the Service zone.
When the last device for Removed devices area is placed, the fire control panel will
synonymously detect their location. For the last placed device the fire control panel will run operations
a) or b). For previously placed devices the fire control panel will run the following operations:
d) if the fire control panel detects compliance of parameters with these saved in the energy
independent memory:
♦the device is placed in service with its previous address in the loop;
♦the faults Removed device and Device not initialized are cleared;
♦the device is excluded from the Service zone;
e) if the fire control panel detects incompliance of parameters with these saved in the energy
independent memory:
♦the device is placed in service with an address, corresponding to device’s location in
the loop;
♦a fault condition due to incompliance with identification number, type or class is
added;
♦the device remains in the Service zone.
In cases b), c) and e) the following actions can be taken:
−if any devices seemed to be involuntarily exchanged, they shall be placed on the proper
locations;
−the device can be excluded from the Service zone by using the Menu Readdressing (see
section 13.7.3) and setting the proper address;
−to save the new loop configuration by using the Function Clean initialization (see
section 13.7.2).
When a new addressable device (exceeding the number of addressable devices in the loop), the
fire control panel sets a temporary address for this device (the text message Reinitialization appears
on the lower end of the display) but ignores the device during further operation. To include the device
in the loop configuration you need to start the Function Clean initialization (see section 13.7.2).
7. Duty Mode
7.1. Description
The fire control panel is in Duty Mode, when it is not in any other of the rest 7 possible conditions.
7.2. Indication
7.2.1. LED and sound indication
In Duty Mode the green LED indicator is activated (Power supply). The local sounder is off.

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 16
Revision 2.05 Of 107
7.2.2. Text message
The display shows the logo of
the company-producer, information
on the current local time and the
mode of operation of the fire control
panel (DAY or NIGHT):
7.3. Using the keypad
The only accessible button in Duty Mode is (Menu). Press it and the fire control panel
enters Information and Control Mode.
8. Fire condition
8.1. Description
The fire control panel enters Fire Condition after a fire detector has been activated in one of the
fire alarm zones. In Mode:DAY the condition has two phases – Fire condition stage I and Fire
condition stage II. The time period for Fire condition stage I is limited and is user programmable,
separately for each zone (up to 255 seconds). The period can be prolonged with the Inspection time
(see section 8.3.1). When Fire condition stage I in this particular zone expires, the fire control panel
enters Fire condition stage II in the same zone.
The fire control panel enters Fire condition stage I upon activation of an automatic fire detector
and Fire condition stage II - upon activation of a manual call point.
In Night Mode the phase Fire condition stage I is ignored. The fire control panel enters Fire
condition, phase Fire condition stage II upon activation of a manual call point or of an automatic fire
detector. The fire control panel can be in Fire Condition in one or more zones. In the second case,
when in Mode:DAY, the fire control panel can be in phase Fire condition stage I in part of the zones,
and in phase Fire condition stage II in the rest of the zones.
To exit this condition press button at Access level 2 (see section 8.3.4).
8.2. Indication
8.2.1. LED and sound indication
In this condition the common light indicator illuminates in red flashing light (Fire condition).
The local sounder produces discontinuous signal (0,5s sound, 0,5s break), if the device has not
been suppressed by button (Stop Alarm).
M
ode:DAY
FIRE CONTROL PANEL IFS7002
UniPOS Ltd
Thu 03 Feb 2005
9:42:23

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 17
Revision 2.05 Of 107
8.2.2. Text messages
Information on zones for which
the fire control panel has detected
Fire condition is displayed:
For this condition the display is
divided into three panels.
The first panel (the upper one)
displays information on zones in fire
condition. A flashing heading with the
text FIRE and the total number of
zones in fire condition appear. The
panel is subdivided into two text
fields, each providing two lines. The
first line displays information on the
first zone in fire condition, the second
line provides information on the last
zone in fire condition.
The first line of each field provides information on the type of the fire condition:
−the sequence number of the indicated fire condition;
−the phase of Fire condition detected by the fire control panel in this particular zone;
−the zone number;
−the remaining time in seconds before the fire control panel proceeds to phase Fire condition
stage II (indicated only in Fire condition stage I).
The second line of each field displays a text message for the corresponding zone. If the fire
control panel has entered Fire condition in more than two zones, the rest of the text messages for fire
condition are suppressed. They can be displayed in the upper field by pressing the buttons on the
right side (see section 8.3.5.1).
The second panel (the middle one) provides information on devices in fire condition. In the head
part is displayed the total number of devices in fire condition. The panel itself is subdivided into three
text fields, each providing two lines. The upper two-line field displays information on the first device
that has detected fire condition; the middle two-line field displays information on the second device in
fire condition, the bottom two-line field – information on the last device.
The first line of each field provides information on the device:
−the sequence number of the device in fire condition;
−the fire alarm loop where the device is integrated into;
−the zone number;
−the device address in the fire alarm loop.
The second line of each field displays text messages relevant to this particular device.
If more than three devices are activated due to fire condition, the rest of the messages are
suppressed. However, they can be displayed in the upper fields, by pressing the buttons on the right
side (see section 8.3.5.2).
The third panel (the bottom one) displays information on the numbers of faults and disables –
total number and for the outputs (monitored outputs and addressable output devices).
8.3. Using the keypad
8.3.1. Button (Inspection)
The button appears on the display when the fire control panel enters phase Fire condition stage I
in a new zone; it is extinguished if pressed or if all zones in Fire condition proceed to phase Fire
condition stage II.
When you press the Inspection button, the remaining time for the zones in Fire condition stage I
after which they proceed to Fire condition stage II, is prolonged with user programmed inspection time
for each particular zone. The operation can be performed only once for each zone in Fire condition
M
ode:DAY
1
1:11:08 Thu 03
F
eb 2005
FIRE CONDITION ZONES IN FIRE: 3
1 Phase 2 Zone 001
Zone 001
3 Phase 1 Zone 002
Zone 002
Time Fire Phase2: 120
Devices in Fire TOTAL NUMBER: 4
1 Loop 01 Zone 001 Addr 001
Point 1.001
2 Loop 02 Zone 003 Addr 001
Point 2.001
4 Loop 01 Zone 002 Addr 002
Point 1.002
Faults Total: 00000
Disables Total: 000
Failed Outputs: 00000
Disabled Outputs: 000

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 18
Revision 2.05 Of 107
stage I, i.e. it is executed for zones where the remaining time has not already been prolonged with
inspection time.
8.3.2. Button (Stop Alarm)
The button appears on the display when the fire control panel enters Fire condition in a new zone
or upon registration of a new fault condition; it is extinguished if pressed or if the local sound signaling
is suspended (fault conditions suspended and/or the fire control panel exits Fire condition).
Press it to turn off the local sounder.
Button’s operation does not effect and is not cancelled by the following events:
−When the fire control panel enters Fire condition in a new zone or proceeds from Fire
condition stage I to Fire condition stage II, the local sounder is activated for Fire condition
only.
−A new fault condition will trigger the local sounder for Fault condition only.
8.3.3. Button (Outputs)
The button is displayed when the fire control panel is in Fire condition.
Its operation depends on the current access level and on the status of the fire control panel:
−At Access Level 1 and in the presence of zones in Fire condition stage I, press the button to:
♦force transition to Fire condition stage II – where no outputs for fire condition responded;
♦Suppress activated outputs for fire condition – where outputs for fire condition responded.
−At Access Level 2 and in absence of zones in Fire condition stage I (i.e. the fire control panel
is in phase Fire condition stage II only), press the button to:
♦Suppress activated outputs for fire condition – where outputs for fire condition responded;
♦Activate suppressed outputs - where no outputs for fire condition responded.
If outputs for fire condition are suppressed, the button appears with the following graphics .
8.3.4. Button (Reset Fire)
The button appears on the display when the fire control panel is in Fire condition and is provided
to force the exit from Fire condition, at Access Level 2.
8.3.4.1. Access Level 1
Press the button at Access Level
1 to display a screen provided for
password entry:
To enter a password use the
buttons with digits – press a digit and
it appears on the place of the
cursor„_”, and the previous text and
the cursor itself move one position to
the right. Move the cursor to the left
or to the right, using buttons and
. Button will delete:
−Any digit under the cursor;
−Or, if there is no digit under
the cursor, then will be
deleted the first digit to the
left.
The length of the password can be 10 symbols maximum. If you press a digit button when the 10-
symbol password is entered, the digit will not be inserted.
С
M
ode:DAY
9
:
4
8:32 Mon
1
1
Ap
r 2005
FIRE CONDITION ZONES IN FIRE: 2
1 Phase 1 Zone 001
Zone 001
2 Phase 1 Zone 003
Zone 003
Time Fire Phase2: 068
Time Fire Pase2: 080
PASSWORD Reset Fire
Enter Password: _
0123456 7 8 9С

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 19
Revision 2.05 Of 107
The operation of button is:
−If a wrong password is entered – the entered digits will be deleted and the cursor will appear
over the password’s first position;
−If one of the 10 passwords for Access Level 2 or the password for Access Level 3 is entered:
♦The fire control panel will exit the Fire condition;
♦The fire control panel will exit Information and Control Mode if it was in a combination
of Fire condition and Information and Control Mode.
To exit the screen press buttons (Exit) or (Cancel). Then, if the fire control panel had
been in a combination of Fire condition and Information and Control Mode, it would exit Information
and Control Mode.
8.3.4.2. Access Level 2
At Access Level 2 press the button and the fire control panel will exit Fire condition and
Information and Control Mode.
8.3.5. Buttons (Move down) and (Move up)
8.3.5.1. Panel for zones in fire condition
Where suppressed messages for zones in fire condition are available they can be displayed in the
text fields of the first (upper) panel on the LCD display, by the means of buttons and situated
in the panel’s right section.
Button appears on the display where a message for a zone in Fire condition following the
message in the first text field is suppressed. Press the button to display it. When the last suppressed
text message for a zone in Fire condition is reached, the button disappears.
Button appears on the display where a message for a zone in Fire condition preceding the
message in the first text field is suppressed. Press the button to display it. When the first suppressed
text message for a zone in Fire condition is reached, the button disappears.
If a suppressed message for a zone in Fire condition is displayed, 20 s after the last button is
pressed, the message for the first zone in fire condition will be automatically restored.
8.3.5.2. Panel for devices in Fire condition
Where suppressed messages for devices in Fire condition are available, they are displayed in the
two text fields of the second (middle) panel, by the meansрof buttons and situated in the
right part of the panel.
Button is activated if the numbers of the messages in the second and the third field are not
consecutive. When you press the button you will display the consecutive messages for devices in
Fire condition, in the first and second text fields.
Button is activated if the number of the message in the first text field is higher than 1. When
you press the button you will display the previous messages for devices in Fire condition, in the
first and second text fields of the middle panel.
8.3.6. Button (Menu)
Press the button to enter Information and Control Mode; the mode uses the middle and the
bottom panel of the screen for Fire condition.

UniPOS Interactive Fire ControlPanel IFS7002
Instruction Manual Page 20
Revision 2.05 Of 107
8.3.7. Button (Exit)
When Fire condition is in combination with Information and Control Mode, press the button and
the fire control panel exits Information and Control Mode and on the display appear all three panels of
the screen for Fire condition.
9. Fault Condition
9.1. Description
The fire control panel enters Fault Condition when any of the events below have been registered:
−Fatal system error;
−Battery low – backup batteries discharged due to interruption of mains supply;
−Fault in a processor programme;
−Fault in a module;
−Fault in the real time clock;
−Fault in the external memory;
−Fault in a loop – a short circuit or a break;
−Loop not initialized;
−Higher number of devices in the fire alarm loop;
−Fault in a zone – upon detection of fault condition in a device, integrated in the zone;
−Removed device;
−Fault condition in a device;
−Activated isolator of a device;
−Activated isolator at the Power loop of a device;
−Contaminated fire detector (for optical detectors|;
−Communication error
−Device not initialized (detected new device in a loop);
−Exchanged devices;
−Different identification number of a device,
−Different device type;
−Different device class;
−Fault in a monitored output – short circuit or break;
−Fault in the mains supply;
−Fault in the backup batteries supply;
−Short circuited ground wire;
−Fault in the positive supply of the loops;
−Fault in the negative supply of the loops;
−Fault in external devices supply.
Where a fatal system error occurs, the main processor can not continue operation and the fire
control panel does not control loops, outputs and other periphery devices. To exit fatal system error
you have to cut off the mains supply and to repair the control panel.
Battery Low is a fatal non-system error; zones and outputs are not being services. The fire control
panel enters a special condition:
−A discontinuous sound signal is produced - 1s sound, 3s break for at least 1 hour;
−Only the green LED indicator is illuminated (Power supply).
−The lighting of the display is extinguished;
−Only the supply voltages are controlled.
The condition is exited automatically 20 s after the mains supply is restored.
All other fault conditions are not fatal and switch off some periphery devices. The condition is
exited automatically 20 s after the fault is suspended.
Upon fault condition Short circuit to ground wire where an element of a monitored output is short
circuited, fault condition in the monitored output (break) is also developed.
Fault condition is indicated by LEDs indicators and a text message on the LCD display.
Other manuals for IFS7002
3
Table of contents
Other UniPOS Control Panel manuals

UniPOS
UniPOS FS5100 User manual

UniPOS
UniPOS FS4000 User manual

UniPOS
UniPOS VIT 01 Operating instructions

UniPOS
UniPOS FS5200E User manual

UniPOS
UniPOS VIT 01 User manual

UniPOS
UniPOS IFS7002R Operating instructions

UniPOS
UniPOS IFS7002 Operating instructions

UniPOS
UniPOS FS5200 User manual

UniPOS
UniPOS IFS7002 Operating instructions

UniPOS
UniPOS FS5200E User manual
Popular Control Panel manuals by other brands

Carrier
Carrier Aritech Reliance XR Series Installation and programming guide

BFT
BFT ALCORA AC A installation manual

IGD
IGD TOCSIN 750 Series Operation and maintenance

Texecom
Texecom Veritas 8 user guide

BLAUBERG Ventilatoren
BLAUBERG Ventilatoren S14 user manual

NAPCO
NAPCO Gemini GEM-X255 Programming instructions