UniPOS FS5200E User manual

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 1
Revision 7/06.12 of 63
Fire Extinguishing Control Panel
FS5200Е
INSTRUCTION MANUAL
Revision 7/06.12

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 2
Revision 7/06.12 of 63
Table of contents
1.
2.
3.
4.
4.1.
4.2.
4.2.1.
4.2.2.
4.2.3.
4.2.4.
4.2.5.
4.2.6.
4.2.7.
4.2.8.
4.2.9.
4.2.10.
4.2.11.
4.2.12.
4.2.13
4.3.
5.
5.1.
5.2.
5.3.
6.
6.1.
6.2.
6.3.
7.
7.1.
7.2.
7.3.
8.
8.1.
8.2.
8.3.
8.4.
9.
9.1.
9.2.
9.3.
10.
10.1.
10.2.
10.3.
11.
11.1.
11.2.
11.3.
12.
12.1.
12.2.
12.3.
12.4.
12.4.1.
Terminology ...............................................................................................................
Technical Data...........................................................................................................
Contents of Delivery...................................................................................................
Installation and Arrangements....................................................................................
To Mount the Control Panel........................................................................................
Description of Inputs and Outputs. Periphery Devices Assembly .............................
Description and Mounting of Devices to L1, L2 and L3 Inputs...................................
Description and Mounting of Devices to Manual Release Input ................................
Description and Mounting of Devices Mode Select Input ..........................................
Description and Mounting of Devices Hold Input .......................................................
Description and Mounting of Devices On/Off Exting Input .........................................
Description and Mounting of Devices Low Press Input ..............................................
Description and Mounting of Devices Exting Output ..................................................
Description and Mounting of Devices Sounder S1 and Sounder S2 Outputs ............
Description and Mounting of Devices to Outputs OK1, OK andи OK3 Open
Collector Type.............................................................................................................
Description and Mounting of Devices to Rel Fire Output............................................
Description and Mounting of Devices Rel 1ST and Rel 2ST Outputs .........................
Description and Mounting of Devices to Rel Fault Output .........................................
Description and Mounting of Devices to RS485 Interface Terminals.........................
Power Supply Connection ..........................................................................................
General Information ..................................................................................................
Access Levels ............................................................................................................
Indications and Buttons for Control.............................................................................
Conditions of the Fire Extinguishing Control Panel.....................................................
Duty Mode ..................................................................................................................
Description..................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Fire Condition Stage I.................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Fire Condition Stage II ...............................................................................................
Description.................................................................................................................
Indication ....................................................................................................................
Using the keypad........................................................................................................
Using the Switch for Mode Selection (Automatic/Manual/Disabled)……...................
Fault Condition............................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Disabled Component ..................................................................................................
Description .................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Test Mode ..................................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Information and Control Mode ....................................................................................
Description .................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Using the Menus ........................................................................................................
Menu View Faults .......................................................................................................
4
6
8
8
8
8
11
12
12
13
13
14
14
15
15
15
16
16
16
16
17
17
18
20
21
21
21
21
21
21
22
22
23
23
23
25
26
26
26
27
28
29
29
29
30
30
30
30
30
31
31
31
31
32
32

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 3
Revision 7/06.12 of 63
12.4.2.
12.4.3.
12.4.4.
12.4.5.
13.
13.1.
13.2.
13.3.
13.4.
13.4.1.
13.4.2.
13.4.3.
13.4.4.
13.4.5.
13.4.6.
13.4.7.
13.4.8.
14.
15.
16.
17.
18.
19.
Menu View Disables...................................................................................................
Menu View Test .........................................................................................................
Menu Statuses ...........................................................................................................
Menu System Functions .............................................................................................
Setup Mode ................................................................................................................
Description..................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Using the Menus ........................................................................................................
Menu Fire Extinguishing Control Panel.......................................................................
Menu „CAN Parameters”.............................................................................................
Menu Inputs/Outputs ..................................................................................................
Menu Time Extinguishing............................................................................................
Menu Time Evacuation...............................................................................................
Menu Factory Settings................................................................................................
Menu Clear archive.....................................................................................................
Menu new Password...................................................................................................
Extinguishing Control Algorithm..................................................................................
Labour Protection Requirements ...............................................................................
Fire Extinguishing Control Panel Start Up .................................................................
Operation, Storage and Transportation .....................................................................
Warranty .....................................................................................................................
Appendixes ...............................................................................................................
33
34
35
36
44
44
45
45
46
46
48
54
56
56
57
57
57
57
59
59
59
59
60

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 4
Revision 7/06.12 of 63
Introduction
The fire extinguishing control panel FS5200Е is designated for fire protection, monitoring and
control of systems for active extinguishing.
After processing the signals from the automatic fire detectors and/or manual call points the control
panel it sends commands to the executive devices for extinguishing, sound-light signalers, air
conditioning and ventilation devices, it sends information to a repeater, PC or another intelligent
devices.
FS5200Еcould be used in – gas, powder, aerosol, water and other types of systems for active
extinguishing.
The fire extinguishing control panel is designed for extinguishing in one zone. It is possible up to
15 zones to be protected when the fire extinguishing control panel is connected in a network via
interface RS485 and a repeater FS5200R.
The fire extinguishing control panel could be connected and become a part of the Interactive Fire
Control System IFS7002 /UniPOS production/.
The fire extinguishing control panel FS5200Е is designed and produced in compliance with
standards EN 54-2:1997/ А1:2006/AC: 2009, EN 54-4:1997/A2: 2006/AC: 2009, EN 12094-1: 2003.
Some of its main features and possibilities are:
adjustment of operating modes and parameters of each fire alarm line, output and input via
built in keypad;
user oriented menu dialogue for easy and convenient operation;
LCD for visualization of system checkup and set up modes;
LEDs indication for early warning of a break down or extreme conditions;
energy independent archive memory saving the event type, date and time, allowing for
detailed analysis of the actions of the authorized personnel and of possible problems in the
fire protection process of the area;
user oriented test modes allowing for a total control of the site protected;
built-in serial interface RS485 and CAN for connection to other fire control panels;
compatible to random installation design, within the range of the available fire extinguishing
control panels resources.
All these are realizable via fire extinguishing control panel’s keypad and after a detailed
examination of the instructions set herewith.
1. Terminology
OUTPUT –monitored or relay output, programmed by the user to be activated during the different
stages of the extinguishing.
EVACUATION TIME –the time from occurring the situation for extinguishing to the moment of
switching on the extinguishing automatics. This time should be enough for the evacuation of the staff
from the premises. The evacuation time is user defined for the specific site. The evacuation time is
shown on the LCD display and it counts down the remaining time until the release of the extinguishing
automatics.
DISABLED LINE –the fire detecting line is switched off (not power supplied) and it is not
monitored for turned out fire detector and a fault condition. This feature is user defined. The indication
for a disabled line is common light indication and text messages on the LCD display.
DISABLED OUTPUT –the output is switched off (the executive device can not be activated) and
is not monitored for a fault condition in the monitored outputs. This feature is user defined. The
indication for a disabled monitored output is common light indication and text messages on the LCD
display.
DISABLE EXTINGUISHING –condition of the fire extinguishing control panel when regardless
the input actions the executive extinguishing device cannot be activated. Disable extinguishing is

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 5
Revision 7/06.12 of 63
defined by “on” status of the monitored input “On/Off Exting” (See section 4.2.) or by the secret switch
on the front panel. The indication for disable extinguishing is an individual light indication.
HOLD EXTINGUISHING –condition of the fire extinguishing control panel when the release
signal to the executive extinguishing device is delayed. Hold extinguishing is defined by “on” status of
the monitored input „Hold”. Hold extinguishing could be controlled by a manual button if extra
evacuation time is needed and monitoring if the doors of the protected premise are tightly closed.
After the hold signal is cancelled the timer for the evacuation time is started automatically. After the
evacuation time expires the extinguishing executive device is switched on. The indication for hold
extinguishing is an individual light indication.
GROUNDS –non-system non-fatal fault condition, due to leakage to a grounded wire.
MONITORED INPUT –input that monitors the serviceability of the connection wires between the
fire extinguishing control panel and the executive devices. Follow the special diagram for connection.
(See section 5.2.).
MONITORED OUTPUT –a potential output that monitors the serviceability of the connection
wires between the fire extinguishing control panel and the executive device. Follow the special
diagram for connection. (See section 5.2.).
SHORT CIRCUIT IN A LINE, MONITORED OUTPUT OR MONITORED INPUT –non-system,
non-fatal fault condition, entered due to registered current value, exceeding a threshold value.
LINE IN TEST –a line, set in Test condition by the user. The line is switched on (supplied) and
reset (the power supply is switched off for 3 s) periodically every 60 s. The events registered in a line
in Test condition are not saved in the archive and do not trigger the outputs or the light and sound
signaling. The indication for a line in Test condition is a text message in the display field for the
respective line.
LOCAL SOUNDER –a sounder built-in the fire extinguishing control panel.
NON-FATAL FAULT CONDITION –fault condition that allows the fire extinguishing control panel
to continue operation. The non-fatal fault condition is not usually a system fault condition. The
indication is common light indication, local sound indication and text messages on the LCD display.
ACCESS LEVEL –access level to various indications and control functions (See section 5.1).
LOW BATTERY –non-system fatal fault condition due to full discharge of the backup batteries
upon interrupted power supply.
SUPPRESSED OUTPUT –a monitored or relay output, which should be activated (for the
respective Extinguishing stage) but it is switched off manually by the user.
FIRE DETECTING LINE (further in the text only LINE) –a combination of fire detectors,
physically connected by two-wire connection. Maximum 32 fire detectors could be connected in each
line.
FIRE CONDITION STAGE I –phase of Fire condition; upon activation of automatic fire detector
only in one line the fire extinguishing control panel enters Fire condition. It continues until the line is
manually reset by Reset Alarm. The indication for Fire condition stage 1 is common light indication.
Local sound signaling and text messages on the LCD display.
FIRE CONDITION STAGE II –phase of Fire condition when active extinguishing procedure is
started. The fire extinguishing control panel enters this stage in the event of:
а) Fire condition along both fire detecting lines;

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 6
Revision 7/06.12 of 63
b) Manual button release for forced extinguishing.
The indication for Fire condition stage 1 is common light indication. Local sound signaling and
text messages on the LCD display.
INTERRUPTED LINE, MONITORED OUTPUT OR MONITORED INPUT –non-system non-fatal
fault condition entered when parameters lower than the threshold value are registered.
RELAY OUTPUT –a relay, potential-free switching outputs provided for controlling external
executive devices.
MANUAL RELEASE –condition entered by the fire extinguishing control panel in the event of
Fire condition stage II, regardless the status of the Fire detecting lines. The manual release is defined
by “on” status of the monitored input „Manual Release”.
MANUAL MODE –condition when the fire extinguishing control panel could release the
extinguishing devices only by manual release command. The manual mode is defined by “on” status
of the monitored input „Mode Select”. The mode indication is an individual light indication.
SYSTEM FAULT CONDITION –fault condition due to a fault in the fire extinguishing control
panel (system’s) component panel. The system fault condition could be fatal or non-fatal. The
indication is common light indication, local sound indication and text messages on the LCD display.
REMOVED FIRE DETECTOR /FD/ –non-system non-fatal fault condition entered when a
removed fire detector in a line is registered. In order this function to be utilized follow the special
diagram for connection (See section 5.2.).
LINE STATUS, MONITORED OUTPUT OR MONITORED INPUT–the current status of a line,
monitored output or input: duty mode; fire condition (only for the fire detecting lines); fault condition
(specifying the type of the fault condition).
FATAL FAULT CONDITION –fault condition that prevents the fire extinguishing control panel, or
the part of it related to the communication with the user, from continuing its operation. The fatal fault
condition is usually a system one, except Law Battery fault condition. The indication is common light
indication, local sound indication and text messages on the LCD display.
2. Technical data
Fire detecting lines
For extinguishing control - 2
Without extinguishing control - 1
Maximum number of fire detectors in a line - 32
Type of the connecting line - two-wire
Maximum resistance of a loop - 100
Output resistance of the line - 164
2.1. Current thresholds in a line per default parameters for:
0÷3mA* - interruption
3÷12mA* - duty mode
12÷60mA* - fire condition
>80mA - short circuit
* It is possible the current in the lines for interruption, duty mode and fire condition to be
adjusted (13.4.2.1.).
2.2. Monitored outputs for control the fire extinguishing control panel performance:

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 7
Revision 7/06.12 of 63
Type - balanced
2.3. Monitored outputs for the sound-light indication
Type - potential relay
Electrical characteristics - (24±3)V/0.5 A
2.4. Monitored output for the extinguishing devices
Type - potential relay
Electrical characteristics - (24±3)V/1.5A
2.5. Relay outputs for common purpose
Type - potential free, switching
Electrical characteristics - 3A/125VAC; 3A/30VDC
2.6. Relay output for fault condition
Type - potential free, switching
Electrical characteristics - 3A/125VAC; 3A/30VDC
2.7. Relay output for fire alarm
Type - potential free, switching
Electrical characteristics - 3A/125VAC; 3A/30VDC
2.8. Performance characteristics
Control over the lines, the monitored inputs and outputs for fault condition (short circuit
and interruption) and automatic reset
Control over the lines for removed fire detector and automatic reset
Ability to set the evacuation time
Ability to set the time when the extinguishing executive device is switched on
Built-in sounder for fire alarm first stage –one tonal, discontinuous, can be switched off
Built-in sounder for fire alarm second stage –one tonal, continuous, can be switched off
Built-in sounder for fault condition –one tonal, discontinuous, can be switched off
Built-in real time clock
Set of test modes and options for adjustment:
Setting the clock;
Check ups on light and sound indications;
Test of the fire detecting lines;
Adjustment of outputs and integrated external devices;
Current measurement in the fire detecting lines;
Programming of parameters and modes of operation;
Remote programming of the parameters from distant operator control point;
Energy independent archive of registered events by the fire extinguishing control panel
with the events type, date and hour –up to 100 events;
Interfaces for communication with external devices - RS-485 and CAN 2.0
2.9. Indications of registered events
Light indication - LED
Text message - LED display -
4 lines 20 characters per line,
Cyrillic, backlit
Sound signaling - built-in sounder
2.10. Power supply
2.10.1. Mains
voltage - 220/230V
frequency - 50/60Hz
2.10.2. Back up batteries
battery type - led, gel electrolyte
number of batteries - 2 pcs
connection - serial connection

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 8
Revision 7/06.12 of 63
nominal voltage of the back up battery - 2x12V
nominal capacity C20 - (7-12)Ah
extreme discharge voltage - 21V
charge voltage - 28,2V
2.10.3. Consumption on back up batteries supply
At 24V - < 120mA
2.10.4. Power supply to external devices
Voltage - (24±3)V
Maximum current value (including current
of monitored outputs ) - 2,5А
2.11. Dimensions
Overall dimensions - 450х355х115mm
2.12. Weight
weight (batteries not included), maximum - 6,6kg
3. Contents of delivery
3.1. Fire extinguishing control panel
Fire detecting control panel FS5200Е- 1 pc.
Resistors 3,0k/ 0,25W - 11 pcs.
Resistors 1,5k/ 0,25W - 5 pcs.
Diode 1N4004 - 1 pc.
Jumper for the back up batteries - 1 pc.
Fuse 4A - 2 pcs.
CD (Instruction manual,Operator’s manual) - 1 pc.
Packing - 1 pc.
4. Installation and arrangements
When fire detectors and periphery devices are integrated in the fire extinguishing control panel,
avoid arranging wires in closed loops; it will reduce the control panel’s resistance to electro magnetic
interferences.
4.1. To mount the control panel
unpack the control panel;
put the dowels on the determined places for fixing the control panel;
fasten the control panel to the dowels through the three holes provided on the chassis.
4.2. Description of inputs and outputs. Periphery devices assembly to the control panel.
All connections are to be made by means of terminals, mounted on the printed circuit board. Be
advised, that the total consumption of the voltage powering the external devices (terminal “+ 28V”)
plus the consumption of the monitored outputs shall not exceed 2.5A in heavy duty mode.
“L1”, “L2” –Inputs for switching automatic Fire detectors. In Fire condition an
extinguishing procedure starts along both lines according to set up algorithm.
“L3” –Fire detecting line input.
“Manual Release” –Input with line status monitoring. The input sends a signal to the
control panel from a manual button to start the extinguishing procedure.
“Mode Select” - Input with line status monitoring. The input sends a signal to the control
panel from a switch for the operating mode. The modes are Manual-Automatic and Manual.
“Hold” - Input with line status monitoring. The input sends a signal to the control panel

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 9
Revision 7/06.12 of 63
from a manual button or controlled contact for holding (delaying) the extinguishing
procedure.
“On/Off Exting” - Input with line status monitoring. The input sends a signal to the control
panel from a switch for disabling the extinguishing procedure.
“Low Press” - Input with line status monitoring. The input sends a signal to the control
panel from pressostat contact, balance or other device to show the extinguishing agents
draining.
“GND” –Terminal for sending GND potential to the periphery devices.
“Еxting” –Active level output with line status monitoring. The output switches the
extinguishing automation valves on.
“S2 Sounder” –Active level output with line status monitoring. The output switches the
sound-light indication on in Fire condition stage II.
“S1 Sounder”–Active level output with line status monitoring. The output switches the
sound-light indication on in Fire condition stage I.
“Rele Fire” –Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fire condition of the control panel, registered by the fire detecting
lines.
“Rel Fault” –Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fault condition of the control panel.
“+28V” –Three terminals for supplying 28V voltage to the periphery devices as well as the
positive potential of the open collectors OK1, OK2 and OK3.
“OK1” –Output open collector /in active status it supplies GND potential, in non-active
status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and
other devices, with total consumption not exceeding 100mA. The output is active when the
control panel has registered extinguishing reagent leakage.
“OK2” –Output open collector /in active status it supplies GND potential, in non-active
status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and
other devices, with total consumption not exceeding 100mA. The output is active when the
control panel is in Disable Extinguishing Mode.
“OK3” –Output open collector /in active status it supplies GND potential, in non-active
status it has potential +28V via resistor 1k/0.125W/. The output controls relays, LEDs and
other devices, with total consumption not exceeding 100mA. The output is active when the
control panel is in manual Mode.
“Rel 2ST” –Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fire condition stage II of the control panel.
“Rel 1ST” –Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fire condition stage I of the control panel.
“CAN” –Terminals to connect the two-wire line of CAN interface. The connection with the
Interactive system IFS7002 /production of UniPOS LTD/ is executed via this interface. A
jumper is provided that shunts the line by 120 ohms. It is needed if the fire extinguishing
control panel is the final point in the interface line. The interface requires resistors 120
ohms to be mounted in both ends of the line.
“RS 485” –Terminals to connect the two-wire line of RS 485 interface. The connection
with a repeater, PC and other devices realized by exchange protocol - UniProtocol
/FS5200E interface/ is executed via this interface. As the case with CAN interface, a
jumper is provided here too with the same functions.
“┴” –Terminal to connect a third wire /screen/ of the interfaces cable.

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page10
Revision 7/06.12 of 63
GND NO NC C
REL Fault Rele
Fire + S1 -
Sounder + S2 -
Sounder + -
Exting Low
Press. On/Off
Exting Hold Mode
Select Manual
Release + L1 - + L2 - + L3 -
CAN term
RS485 term
NC NO NC NO
NC NO
A RS485 B
H CAN L
Rel
1ST
Rel
2ST
OK1
+28V
OK2
+28V
OK3
+28V
Jump (RS485)
Jump (CAN)
Jump Rel 1ST
Jump Rel 2ST
Jump relay Fire
Interface RS 485 (repeater, PC and other devices)
Interface CAN (join to system IFS7002)
Relay output in condition Fire Alarm Phase 1
Relay output in condition Fire Alarm Phase 2
Output Open Collector –Active in case of extinguisher leakage (+28V)
Output Open Collector –Active in case of extinguishind disable (+28V)
Output Open Collector –Active in manual mode (+28V)
Relay output in Fault Alarm condition
Relay output in Fire condition
3k 3k
Sounder Fire Alarm Phase 1
(28V/0,5A)
1N4004 Device Extinguishing
(28V/1,5A)
3k
1,5 k
3k
1,5k
3k
1,5k
3k
1,5k
Switch for monitoring
extinguisher leakage
Switch for extinguishing disable
Button for extinguishing delay
Switch mode manual/manual-automatic
3k
1,5k
1,5k
Buttons manual
extinguishing activation
3k
FD
FD
FD
3k
FD
FD
FD
3k
FD
FD
FD
Fire Alarm Line 1
FS5200E
Sounder Fire Alarm Phase 2
(28V/0,5A)
Fire Alarm Line 2
Fire Alarm Line 3
Drawing1

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page11
Revision 7/06.12 of 63
4.2.1. Description and mounting of devices to L1, L2 and L3 inputs
Connect a two-wire line at L1, L2 and L3 inputs for connection with the Fire detectors. The line
total resistance shall not exceed 100. The recommended wire section depending on the lines length
is:
To 500 m -cable 2 х 0.5 mm2
To 1000 m -cable 2 х 1.0 mm2
To 1500 m -cable 2 х.1.5 mm2
It is recommended to make a check with a multicet before connecting the fire detecting line to the
fire extinguishing control panel. If the line is installed correctly (with mounted final resistor 3kΩ /
0.25W) between the plus and minus of the cable entering the fire extinguishing control panel the
measured resistance should be 3kΩ (+/-10%). Also when measuring both wires to ground the
multicet should show no connection or leakage.
Make the connection to the terminals –“+ Lx -” (where “x” is the line number). Observe the shown
polarity (Drawing 2).
+OUT +IN
-IN/OUT RI/KL-
- Lx +
FS5200E 1N5819*
FD80xx
First
detector
5 4
2 1
1N5819*
FD30xx 3k/0.25W
Last
detector
* Diode 1N5819 or similar
Drawing 2
Use automatic fire detectors FD3000 or FD8000 series or other compatible automatic fire
detectors. Mount resistor 3 kΩ/ 0.25W on the last fire detector in the line.
Mount diodes, for example 1N5819 or similar in the shown direction if you are to use the fire
extinguishing control panel function to register Fault condition –removed fire detector.
Maximum 32 fire detectors could be mounted to one line regardless of their type.
When mounting the fire detectors take into consideration the specific technical characteristics of
the fire detector with the fire extinguishing control panel parameters for the current threshold in the
different conditions. Change the current threshold from Set up menu.
Current thresholds in a line with default parameters for the conditions:
0÷3mA* - interruption
3÷12mA* - duty mode
12÷80mA* - fire condition
>80mA - short circuit
Mount fire detectors on Lines 1 and 2 in the premise where the extinguishing will be performed.
The first and the second line are in a logical dependence „I”; the fire extinguishing control panel enters
Fire condition stage II if only both lines are activated and the extinguishing algorithm is possible to be
executed.
Line 3 is only Fire detecting and it serves for fire protection of the adjoining premises to the
extinguished zone. When this line is activated it switches on the outputs for Fire condition stage I as
well as the common output for Fire condition. This line is not included in the extinguishing algorithm
logic. Line 3 can be assumed as a standard line of a Fire control panel.

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page12
Revision 7/06.12 of 63
4.2.2. Description and mounting of devices to Manual Release input
Connect a two-wire line to the Manual Release input for connection with the manual release
buttons for extinguishing activation. It is possible to mount maximum three buttons. The line is
balanced and it is monitored for interruption and short circuit. Install resistors to the button terminals
as shown in the connecting diagrams to monitor the condition. Install resistor 3k to the last button if 2
or 3 buttons are mounted (Drawing 3).
Connecting diagram with 1 button
Release
FS5200E
Button for manual
activation of the extinguishing
3k/
Manual
0.25W 1.5k/
0.25W
Connecting diagram with 2 buttons
Release
FS5200E Button 1
Manual
1.5k/
0.25W
Button 2
3k/
0.25W 1.5k/
0.25W
Connecting diagram with 3 buttons
Release
FS5200E Button2
Manual
1.5k/
0.25W
Button 3
3k/
0.25W 1.5k/
0.25W
Button 1
1.5k/
0.25W
Drawing 3
When the contact is closed the fire extinguishing control panel accepts the button to be active.
4.2.3. Description and mounting of devices to Mode Select input
Connect a two-wire line to the Mode Select input for connection with a switch to select the fire
extinguishing control panel mode –Manual-Automatic or Manual. The line is balanced and it is
monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in
the connecting diagram to monitor the condition.
When the contact is closed the fire extinguishing control panel accepts Manual Mode; when it is
opened –Manual-Automatic Mode. Output Open collector type is activated in Manual Mode. That
output could be used as switch indication, if this option is provided.

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page13
Revision 7/06.12 of 63
Select
FS5200E
Switch modes
Manual/Manual-automatic
Mode
1.5k/
0.25W
4.2.4. Description and mounting of devices to Hold input
Connect a two-wire line to the Hold input for connection with a switch to activate hold
extinguishing function. The line is balanced and it is monitored for interruption and short circuit. Install
the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition
(Drawing 4).
Hold
FS5200E
Switch
Extinguishingdelay
3k/
0.25W 1.5k/
0.25W
Drawing 4
Set up the input active status: OPEN or CLOSED contact from menu System functions > Set up
> Input/Outputs > Hold input.
Attention! The active status of the default parameters is OPEN contact of the switch in order the
fire extinguishing control panel to accept Hold Extinguishing function.
4.2.5. Description and mounting of devices to On/Off Exting input
Connect a two-wire line to the On/Off Exting input for connection with a switch to disable
extinguishing. The line is balanced and it is monitored for interruption and short circuit. Install the two
resistors to the switch terminals as shown in the connecting diagram to monitor the condition
(Drawing 5).
Exting
FS5200E
Switch
Extinguishingdisable
3k/
On/Off
0.25W 1.5k/
0.25W
Drawing 5
When the contact is closed the fire extinguishing control panel accepts Disable Extinguishing.
Output Open collector type is activated in Disable Extinguishing. That output could be used as switch
indication, if this option is provided.

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page14
Revision 7/06.12 of 63
4.2.6. Description and mounting of devices to Low Press input
Connect a two-wire line to the Low Press. input for connection with a pressostat contact, balance
or other devices registering a Fault condition in the extinguishing installation. The line is balanced and
it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as
shown in the connecting diagram to monitor the condition (Drawing 6).
Low
FS5200E
Pressure
3k/
0.25W 1.5k/
0.25W
Press.
Drawing 6
Set up the input active status: OPEN or CLOSED contact from menu System functions > Set
up > Input/Outputs > Low Press input.
Attention! The active status of the default parameters is OPEN contact of the switch in order the
fire extinguishing control panel to accept the function Leaked extinguishing agent or Fault condition.
4.2.7. Description and mounting of devices to “Exting” output
Connect a two-wire line to the Exting output for connection with a magnetic valve or other device
to activate the extinguishing automation. The line is balanced and it is monitored for interruption and
short circuit. Install a diode 1N4004 or similar to the executive device terminals in the direction as
shown in the connecting diagram as the valve winding resistance shall be in the range: 30Ω ÷ 3kΩ.
(Drawing 7).
Install a parallel resistor 3kΩ / 0.25W and a serial diode 1N5401 on the line if the winding
resistance is less than 30Ω(Drawing 8).
Connecting diagram if the winding valve active resistance is from 30 Ω to 3к Ω
+ -
FS5200E valve
1N4004
Exting
Electromagnetic
V
Rv - 30 Ohms up to 3 k
Drawing 7
Connecting diagram if the winding valve active resistance is less than 30 Ω

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page15
Revision 7/06.12 of 63
+ -
FS5200E
1N5401
Exting
V
Rv - < 30 Ohms
3k/
0.25W
1N4004
valve
Electromagnetic
Drawing 8
Upon the output activation the supplied voltage (24±3)V is with load-carrying capacity of 1.5А.
The time for output activation could be set from 2 to 255 seconds from menu System functions >
Set up > Extinguishing time and it depends on the type of the used executive device. The default
setting is 10 seconds.
4.2.8. Description and mounting of devices to Sounder S1 and Sounder S2 outputs
Connect a two-wire line to the Sounder output for connection with sound and light signaling
devices. The line is balanced and it is monitored for interruption and short circuit. Install a resistor
3kΩ/0.25W to the signaling device terminals to monitor the condition (Drawing 9).
- Sx +
FS5200E
Sounder
3k/
0.25W
Drawing 9
Upon the outputs activation the supplied voltage (24±3)V is with load-carrying capacity of 0.5А.
The outputs are activated for Fire condition stage I and Fire condition stage II, respectively.
The fire extinguishing control panel provides the option for Sounder S1 output disable from menu
System functions > Disables > Disable S1 output .
4.2.9. Description and mounting of devices to outputs OK1, OK2 and OK3 open
collector type
OKx outputs send a signal to relays, LEDs and other devices to follow and monitor the fire
extinguishing control panel condition. The outputs are not monitored for the line status.
47k
GND
28V
OKx
+28V
Drawing 10
Upon activation of the outputs GND potential is supplied with load-carrying capacity of 0.1А.
The internal diagram of output Open collector type is presented on the drawing (Drawing 10).
4.2.10. Description and mounting of devices to Rel Fire output
Rel Fire is a potential free, relay output. The logic of the contact - Normally Open or Normally
Closed could be adjusted by means of a jumper. The output is not monitored. The output is activated
in Fire condition along one or both fire detecting lines.

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page16
Revision 7/06.12 of 63
4.2.11. Description and mounting of devices to Rel 1ST and Rel 2ND outputs
Rel 1ST and Rel 2ND are potential free, relay outputs. The logic of the contact - Normally Open or
Normally Closed could be adjusted by means of a jumper. The outputs are not monitored. The
outputs are activated in Fire condition stage I and Fire condition stage II, respectively. The fire
extinguishing control panel provides the option to disable the activation of Rel 1ST and Rel 2ND outputs
from menu System functions > Disables > Disable Rel 1ST / Disable Rel 2ND.
4.2.12. Description and mounting of devices to Rel Fault output
Rel Fault is a potential free, relay output, as both relay contacts are possible Normally Open or
Normally Closed. The output is not monitored.
4.2.13. Description and mounting of devices to RS485 interface terminals
RS485 interface is designed to transmit information and to receive commands from FS5200R
repeater. The following connection configurations are possible:
One fire extinguishing control panel and one repeater
One fire extinguishing control panel and up to 6 repeaters
Up to 15 fire extinguishing control panels and 1 repeater
Up to 6 repeaters and up to 10 fire extinguishing control panels (If less than 6 repeaters
are installed they could be substituted by fire extinguishing control panels, i.e.
configuration of 3 repeaters and 13 fire extinguishing control panels, etc.)
FS5200R repeater receives information from all fire extinguishing control panels as it indicates
the occurred events by sound signaling, light indication and text messages. It is also possible a
remote fire extinguishing control panel to be reset.
RS485 interface could be used also for communication with other intelligent devices and PCs.
The connection between the devices along RS485 is parallel connection. Observe the
requirement potential A and B not to be crossed. The maximum distance between the end devices is
1000 meters. Jumper to shunt the line by 120 ohms has to be installed on the first and the last device
regardless the line length. On all other devices the jumper has to be removed (Drawing 11).
А В
120
Enddevice
RS485
JА В
120
Enddevice
RS485
FS5200x
J
А В
120
RS485
FS5200x
А В
120
RS485
FS5200x
А В
120
RS485
FS5200x
FS5200x
Drawing 11
4.3. Power supply connection
Connect a feeding cable to the terminal with mains fuse, observing the following positions
(Appendix 3):
P –power wire “Phase”;

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page17
Revision 7/06.12 of 63
N –power wire “Null”;
Ground - safety ground wire.
The cable shall be double insulated and of 0,5mm2section for the power supply wires, and of
1,5mm2section for the safety ground wire.
The other end of the feeding cable is connected to the mains power supply by means of junction
box.
The mains power supply of the fire control panel shall be in a separate loop.
5. General information
5.1. Access levels
4 levels of access to the variable indications and control functions of FS5200Е are available.
5.1.1. Access level 1
All persons who would presumably find out and react to alarm upon fire condition or fault
condition have access to level 1.
The following actions are accessible:
Displaying suppressed messages for Fire condition stage I, Fire Condition stage II, Fault
condition, Disabled components;
Forced proceeding from phase Fire condition stage I to phase Fire condition stage II ;
Suppressing the local sounder;
Displaying the status of the lines and the monitored outputs (see section 12.5);
All light indicators are visible.
5.1.2. Access level 2
The personnel in charge of the fire protection have access to level 2; they shall be trained and
authorized to operate the fire control panel in the following conditions:
Duty Mode;
Fire condition stage I;
Fire condition stage II;
Fault condition;
Disabled component;
Information and adjustment.
To enter Access level 2, turn the key on the front panel of the fire extinguishing control panel into
position .
The following features of the fire extinguishing control panel are accessible:
All features accessible at Level 1;
Switching off the outputs, activated upon fire condition;
Exit of Fire condition;
System functions of the fire extinguishing control panel except entering Set up Mode
(see section Error! Reference source not found.).
5.1.3. Access level 3
Accessible for personnel trained and authorized for:
Reconfiguration of specific data –of the protected site or of the fire extinguishing control
panel –saved in the memory;
Maintenance of the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password entered at Access level 2. At this
sublevel the functions for reconfiguration of specific data for the protected site or the fire extinguishing
control panel are accessible.
Level 3, sublevel 3B is accessed when the fire extinguishing control panel is opened. The
following features are accessible:
Replacing a burnt fuse;
Adding, removing or replacing a module;
Connecting fire detecting lines and executive devices.

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page18
Revision 7/06.12 of 63
5.1.4. Access Level 4
Accessible for personnel trained and authorized by the Producer to repair the fire extinguishing
control panel and to modify the software.
Special means are required to enter this level.
5.2. Indications and buttons for control
Table 1 gives detail description of the indications for each status, Table 2 presents the basic
function of the control buttons. Appendix 1 shows the front panel of FS5200 with the indications and
buttons for control.
Table 1
Conditions of the fire extinguishing control panel
Indication
All conditions -
The fire extinguishing control panel is power
supplied
Indicator Power Supply –
continuous green light
Fire condition –Fire condition Stage I and Stage II
Individual indicators for
Fire condition in the fire detecting
lines
Fire condition –Fire condition Stage I
Common indicator Fire condition
Stage I –
continuous red light
Fire condition –Fire condition Stage II
Common indicator Fire condition
Stage II –
flashing red light during the
evacuation time and continuous
red light after the automated
extinguishing is switched on
Manual Mode –a signal for manual mode of
extinguishing control is given
Indicator Manual Mode -
continuous yellow light
Manual Mode –a signal for manual mode of
extinguishing control is given
Indicator Manual-Automatic Mode -
continuous yellow light
Disabled extinguishing –a signal disabling the
extinguishing is given
Indicator Disabled Extinguishing -
continuous yellow light
Extinguishing held –a signal holding the
extinguishing is given
Indicator Extinguishing Held - -
continuous yellow light
Fire Condition and Fault Condition –the sound
indication is suppressed
Indicator Stop Alarm - continuous
red light
Fire condition Stage I -
The fire condition stage I outputs are suppressed
Indicator Suppressed Outputs -
continuous red light
Fault condition - All faults except for Battery Low
Common indicator Fault Condition
- continuous yellow light
Fault condition –System Error and new
Configuration
Indicator System Error -
continuous yellow light
Fault condition –Fault in mains supply or backup
battery
Indicator mains Supply Fault -
continuous yellow light
Fault condition –fault condition in monitored line
Indicator Monitored Line Fault -
continuous yellow light
Fault condition –fault condition Low pressure in the
extinguishing installation
Indicator Low Pressure Fault -
continuous yellow light
Disabled component -
Disabled line or monitored output
Indicator Disabled Component –
continuous yellow light
Fire condition Stage I
Local sounder –discontinuous signal: 4
sound impulses for 1 s, followed by 1 s
break
Fire condition Stage II
Local sounder –continuous signal

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page19
Revision 7/06.12 of 63
Conditions of the fire extinguishing control panel
Indication
Fault condition - All faults except for Battery Low
Local sounder –discontinuous signal: 1 s
sound, followed by 1 s break
Fault condition -
Low battery
Local sounder –discontinuous signal: 1 s
sound, followed by 3 s break

UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page20
Revision 7/06.12 of 63
Table 2
Means of control
Condition of the fire
extinguishing
control panel
Access
level
operation
Access level 2 key
Level 1
Status
Level 2
Status
Button Line Reset
Fire condition
Level 2
Output from Fire Condition stage I or Fire
condition stage II initiated on the display
Button
Outputs
Fire condition, phase
Fire condition Stage I
Level 2
- if outcomes for Fire condition Stage I are
activated –to suppress them;
- if outcomes for Fire condition Stage I are
suppressed –to activate them
Fire condition, phase
Fire condition Stage II
Level 2
- If the common output for fire condition is
activated –to suppress it;
- if there is no activated common output for
fire condition –to activate it
Button Alarm
Fire condition Stage I
or Stage II and Fault
condition*
Level 1
To suppress/activate the local sounder
Button Menu
Duty Mode, Fire
condition, Fault
condition*, Test and
Disabled component
Levels 1
and 2
To enter Information and Control Mode
Information and
Control Mode
Levels 1
and 2
- To enter the selected menu;
- To execute the selected command;
- To save the modified parameter
Set up Mode
Level
3А
Button Down
Fire condition
Levels 1 and 2
To show on the display the next message for fire condition
Information and
Control Mode
Levels 1
and 2
- To show on the display the next element
from the menu;
- To move the cursor;
- To modify the selected parameter
Set up Mode
Level
3А
Button Up
Fire Condition
Levels 1
and 2
To show on the display the previous
message for fire condition
Information and
Control Mode
Levels 1
and 2
- To show on the display the previous
element from the menu;
- To modify the selected parameter
Set up Mode
Level
3А
Button Cancel
Information and
Control Mode
Levels 1
and 2
- To exit a function without saving changes
in the parameter; the command will not be
executed;
- To exit the current menu and to move to
an upper hierarchy menu
Set up Mode
Level
3А
*Not operating in Fault condition (fatal fault condition except New Configuration).
5.3. Conditions of the Fire Extinguishing Control Panel
The fire extinguishing control panel FS5200Еmonitors the fire detecting lines and the monitored
outputs as it scans consecutively their status. Depending on the current the fire extinguishing control
panel could be in Duty Mode, in Fire condition or Fault condition (short circuit or interruption).
Depending on the measured parameters the inputs could be in Fault condition (short circuit or
Other manuals for FS5200E
1
Table of contents
Other UniPOS Control Panel manuals

UniPOS
UniPOS FS5200 User manual

UniPOS
UniPOS IFS7002 User manual

UniPOS
UniPOS IFS7002 Operating instructions

UniPOS
UniPOS FS5100 User manual

UniPOS
UniPOS IFS7002R Operating instructions

UniPOS
UniPOS IFS7002 Operating instructions

UniPOS
UniPOS FS5200E User manual

UniPOS
UniPOS FS4000 User manual

UniPOS
UniPOS VIT 01 User manual

UniPOS
UniPOS VIT 01 Operating instructions