Unipower SAGEON Site Monitor Installation and operating instructions

Sageon Site Monitor (SSM) Application Note
AN103-4012-00, Issue 3 i
RECEIVING INSTRUCTIONS
&
GENERAL EQUIPMENT INFORMATION
Please Note: For your protection, the following information and the product manual should be read
and thoroughly understood before unpacking, installing, or using the equipment.
UNIPOWER, LLC presents all equipment to the delivering carrier securely packed and in perfect
condition. Upon acceptance of the package from us, the delivering carrier assumed responsibility for
its safe arrival to you. Once you receive the equipment, it is your responsibility to document any
damage the carrier may have inflicted, and to file your claim promptly and accurately.
1. PACKAGE INSPECTION
1.1 Examine the shipping crate or carton for any visible damage: punctures, dents, and any other signs of
possible internal damage.
1.2 Describe any damage or shortage on the receiving documents, and have the carrier sign their full name.
1.3 If your receiving freight bill notes that a Tip-N-Tell is attached to your freight, locate it. If the Tip-N-
Tell arrow has turned even partially blue, this means the freight has been tipped in transport. Make
sure the carrier notes this on your receipt before you sign for the freight.
2. EQUIPMENT INSPECTION
2.1 Within fifteen days, open the crate and inspect the contents for damages. While unpacking, be careful
not to discard any equipment, parts, or manuals. If any damage is detected, call the delivering carrier
to determine appropriate action. They may require an inspection.
*SAVE ALL SHIPPING MATERIAL FOR THE INSPECTOR TO SEE!
2.2 After the inspection has been made, call UNIPOWER. We will determine if the equipment should be
returned to our plant for repair, or if some other method would be more expeditious. If it is determined
that the equipment should be returned to UNIPOWER, ask the delivering carrier to send the packages
back to UNIPOWER at the delivering carrier's expense.
2.3 If repair is necessary, we will invoice you for the repair so that you may submit the bill to the
delivering carrier with your claim form.
2.4 It is your responsibility to file a claim with the delivering carrier. Failure to properly file a claim for
shipping damages may void warranty service for any physical damages later reported for repair.
3. HANDLING
Equipment can be universally heavy or top-heavy. Use adequate humanpower or equipment for
handling. Until the equipment is securely mounted, be careful to prevent the equipment from being
accidentally tipped over.
4. NAMEPLATE
Each piece of UNIPOWER equipment is identified by a part number on the nameplate. Please refer to
this number in all correspondence with UNIPOWER.
5. INITIAL SETTINGS
All equipment is shipped from our production area fully checked and adjusted. Do not make any
adjustments until you have referred to the technical reference or product manual.

Sageon Site Monitor (SSM) Application Note
AN103-4012-00, Issue 3 ii
6. SPARE PARTS
To minimize downtime during installation or operation, we suggest you purchase spare fuses, circuit
boards and other recommended components as listed on the Recommended Spare Parts List in the back
of the product manual. If nothing else, we strongly recommend stocking spare fuses for all systems.
Issue
Page(s)
Altered
Description Issued by / Date
3 All
Updated UNIPOWER logo & contact information. See
PCO# 44448.
WD
6/26/17
PROPRIETARY AND CONFIDENTIAL
The information contained in this product manual is the sole property of UNIPOWER, LLC. Reproduction of
the manual or any portion of the manual without the written permission of UNIPOWER, LLC is prohibited.
© Copyright UNIPOWER, LLC 2015
DISCLAIMER
Data, descriptions, and specifications presented herein are subject to revision by UNIPOWER, LLC without
notice. While such information is believed to be accurate as indicated herein, UNIPOWER, LLC makes no
warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its
control, UNIPOWER, LLC hereby disclaims and excludes all warranties, express, implied, or statutory,
including any warranty of merchantability, any warranty of fitness for a particular purpose, and any implied
warranties otherwise arising from course of dealing or usage of trade. The user is solely responsible for
determining the suitability of the product(s) featured herein for user’s intended purpose and in user’s specific
application.
Throughout the remainder of this manual, “UNIPOWER” will mean “UNIPOWER, LLC.”
PERSONNEL REQUIREMENTS
Installation, setup, operation, and servicing of this equipment should be performed by qualified persons
thoroughly familiar with this Product Manual and Applicable Local and National Codes. A copy of this manual
is included with the equipment shipment.
Table of Contents
1.0 Introduction ...............................................................................................................................................1
2.0 Applications...............................................................................................................................................1
3.0 Example Installation..................................................................................................................................1
4.0 System Configuration................................................................................................................................2
5.0 Electrical Specification..............................................................................................................................2
6.0 Physical Specification ...............................................................................................................................3

Sageon Site Monitor (SSM) Application Note
AN103-4012-00, Issue 3 1
1.0 INTRODUCTION
The Sageon Site Monitor (SSM) is an auxiliary module for the SageonDC Power Plant. The SSM provides
additional I/O for the power plant enabling users to monitor the status of additional equipment through the
Sageon system. The SSM includes twelve digital inputs and eight analog inputs for monitoring devices such as
site security (door and window magnetic switches), AC Inverter status and alarms, Generator status (fuel level,
oil pressure), and HVAC status and alarms. Also included are four voltage free (dry), Form C control output
relays. The control relays can be automatically activated in response to an event on any of the SSM digital or
analog input (configurable by the user), or operated manually from a PC running SageView.
2.0 APPLICATIONS
The SSM provides a simple, integrated solution to many common application challenges eliminating the need to
purchase separate monitoring equipment. Using the remote communication capabilities and SageView software,
the Sageon system can be remotely monitored, allowing the appropriate response to site events.
Typical applications include:
•Integration of site alarms
•Integration of Inverter status
•Individual load monitoring
•Integration of auxiliary equipment status
3.0 EXAMPLE INSTALLATION
In this example the auxiliary site equipment is integrated into the site monitor. The I/O for this application
include:
Analog Inputs
•Generator fuel level
•Generator output voltage, current, and frequency
•Inverter output voltage, current, and frequency
Digital Inputs
•Window and door opening sensors
•HVAC alarms
Digital Outputs
•NOC alarm generation
•Local alarms
•Strobe lights
4 C/O RELAY
CONTACT
OUTPUTS
HVAC
INVERTERS
GENERATOR
SEN
SEN
SEN
V
I
f
V I f
FUEL
LEVEL
FUEL
POWER PLANT
DIESEL
SSM
12 DIGITAL
INPUTS
8 ANALOG
INPUTS
Expansion module
cable to SCU
4 C/O RELAY
CONTACT
OUTPUTS
4 C/O RELAY
CONTACT
OUTPUTS
HVAC
INVERTERS
GENERATOR
SEN
SEN
SEN
V
I
f
V I f
FUEL
LEVEL
FUEL
POWER PLANT
DIESEL
SSM
12 DIGITAL
INPUTS
8 ANALOG
INPUTS
Expansion module
cable to SCU

Sageon Site Monitor (SSM) Application Note
AN103-4012-00, Issue 3 2
4.0 SYSTEM CONFIGURATION
The SSM is easily configured using the SageView program included with each SageonDC Power Plant. The
Site Monitor configuration screen is pictured below and provides a simple, intuitive user interface.
Each input has a user-defined label field (up to 8 characters) to describe its function. If a label field is left blank,
the corresponding input is treated as not used. Analog input fields also include a two-character field for the
description of the units of measure as well as high and low alarm thresholds. Scaling factor for analog inputs
are set-up for 0 volts (0% F.S.) to 4 volts (100% F.S.). The type of digital input source (normally open or
normally closed) is user definable by selecting the appropriate check box. Each discrete output can be
automatically generated based on any combination of discrete and analog inputs.
5.0 ELECTRICAL SPECIFICATION
Analog inputs
Number of inputs: 8
Input Range: 0 to +4Vdc Full Scale,
Over-voltage and reverse polarity protected.
Configuration: Scaling factor, low and high alarm levels are user programmable.
Electrical Isolation: Non-isolated. Each analog input source must be isolated.
Digital inputs
Number of inputs: 12
Source type: Voltage free (dry) contact closure
Active state: User defined (active open or active closed)
Electrical Isolation: Non-isolated. Each digital input source must be isolated.
Digital outputs
Number of outputs: 4
Output type: Voltage free (dry) 1 Form C relay contacts
Output rating: 1A@30VDC
General Power Source: Self powered from the Sageon Interface Board
Plant Connection:16 conductor cable to the Sageon Interface Board
Maximum Distance: 30 feet (9.14 meters)

Sageon Site Monitor (SSM) Application Note
AN103-4012-00, Issue 3 3
6.0 PHYSICAL SPECIFICATION
Module Dimensions (approx): 5.11” x 9.37” x 3.14” (130 x 238 x 80) (DxWxH)
Table of contents
Other Unipower Control Unit manuals
Popular Control Unit manuals by other brands

Genebre
Genebre 1054 08 manual

Emerson
Emerson Kunkle Series Operating and safety instructions

Durafly
Durafly 9164000024-0 manual

National Instruments
National Instruments FBUS-HSE/H1 LD installation guide

M-system
M-system R30YV4 instruction manual

American Standard
American Standard Ultima Selectronic 6064.013 installation instructions

Voltek
Voltek 1809 installation guide

Marshall Excelsior
Marshall Excelsior ME980-8 installation instructions

gofanco
gofanco Prophecy PRO-HDExtIP-CTRL user guide

Val-Matic
Val-Matic SWCV-OM2-5 Operation, maintenance and installation manual

Thermo Scientific
Thermo Scientific Nicolet iS50 GC-IR user guide

Burkert
Burkert 2000 INOX quick start