USFilter V-2000 User manual

SERIES V-2000
CHLORINATOR
3000 LB/24 HR
AUTOMATIC CONTROL
BOOK NO. IM 25.055AC UA ISSUE C

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
EQUIPMENT SERIAL NO. _________________
DATE OF START-UP _____________________
START-UP BY ___________________________
Prompt service available from nationwide authorized service contractors.
ORDERING INFORMATION
Inorderforustofillyourorderimmediatelyandcorrectly,pleaseordermaterialbydescriptionandpartnumber,asshowninthis
book. Also,please specify the serial numberof the equipment on whichthe parts will be installed.
WARRANTY
Sellerwarrants for a periodof one yearafter shipment that theequipment or material ofits manufacture is freefrom defects in
workmanshipandmaterials. Corrosion or other decompositionbychemical action is specifically excludedasa defect covered
hereunder,exceptthisexclusionshallnotapplytochlorinationequipment.Sellerdoes not warrant (a) damage caused by use of
the items for purposes other than those for which they were designed, (b) damage caused by unauthorized attachments or
modifications,(c)productssubject to any abuse, misuse, negligence oraccident, (d)products wherepartsnotmade,supplied,
orapproved by Sellerare used and inthe sole judgement ofthe Seller suchuse affectsthe products’ performance,stability or
reliability, and (e) productsthat have been altered or repairedin a manner in which, inthe sole judgement of Seller, affects the
products’performance,stabilityorreliability. SELLER MAKES NO OTHER WARRANTY OF ANY KIND, AND THE FOREGO-
ING WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF
MERCHANTABILITY OR OF FITNESS OF THE MATERIAL OR EQUIPMENT FOR ANY PARTICULAR PURPOSE EVEN
IF THAT PURPOSE IS KNOWN TO SELLER. If Buyer discovers a defect in material or workmanship, it must promptly notify
Sellerin writing; Seller reserves the right to require the return of such defectivepartstoSeller,transportationchargesprepaid,to
verifysuch defect before this warrantyisapplicable.Innoevent shall such notification bereceivedbySellerlaterthan 13 months
afterthedate of shipment. No actionforbreachof warranty shall be broughtmorethan 15 months after the dateofshipment of
theequipmentor material.
LIMITATION OF BUYER’S REMEDIES. The EXCLUSIVE REMEDY for any breach of warranty is the replacement f.o.b.
shippingpointofthedefective part or parts of the material or equipment. Any equipmentor materialrepaired orreplaced under
warrantyshallcarry the balance of the original warrantyperiod,ora minimum of three months. Seller shallnot beliablefor any
liquidated,special,incidentalorconsequential damages, including without limitation, loss of profits,loss ofsavings orrevenue,
lossof use of the materialor equipment or any associatedmaterial or equipment, the costof substitute material or equipment,
claimsofthirdparties,damagetoproperty,orgoodwill,whetherbaseduponbreachofwarranty, breach of contract, negligence,
stricttort, or any other legaltheory;provided, however,that such limitation shallnotapply to claims forpersonalinjury.
Statementsandinstructions set forth herein arebasedupon the best information andpracticesknown to U.S. Filter/Wallace&
Tiernan, Inc., but it should not be assumed that every acceptable safety procedure is contained herein. Of necessity this
companycannotguaranteethatactionsinaccordancewithsuchstatementsandinstructionswillresultinthecompleteelimina-
tionof hazards and itassumesno liability for accidentsthatmay occur.
1.010-42D
WALLACE & TIERNAN PRODUCTS
1901 West Garden Road, Vineland, NJ 08360

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
INTRODUCTION
This instruction book provides installation, operation, and maintenance
instructions for the USFilter's Wallace & Tiernan Products (USF/W&T)
Series V-2000 (Chlorine) Gas Feeder (control module and injector). Of
necessity,moreinformationisprovidedthanappliestoeachspecificinstal-
lation; disregard those details that do not apply to your installation.
Instructions for accessory equipment, where applicable, are provided in
separate books included with that equipment.
The complete gas feeder consists of a control module, an injector, and a
vacuumregulator.Thevacuumregulatoriscoveredbyaseparateinstruc-
tion book provided with that equipment.
WARNING:DONOTUSETHISEQUIPMENTFORSWIMMING
POOL, WATER PARK, OR SIMILAR RECREATIONAL APPLI-
CATIONS. IT IS NOT SOLD FOR SUCH USE.
The USF/W&T Gas Feeder is designed to meter and control the flow of
chlorinegas.Aninjectoracceptsthisflowofgas,mixesitwithwater,and
deliverstheresultantsolutiontothepointofapplication.Byusingaselec-
tion of rotameters and valve seats, the gas feeder may be adapted to meet
awiderangeofcapacityrequirements.Thus,asrequirementschangeover
aperiodoftime,thecapacityofthegasfeedermaybechangedaccordingly.
Alargeindicatorscaleontherotameterpermitsadirectreadingoftherate
of gas feed in pounds per 24 hours. Control of the feed rate is electric;
however, a simple release mechanism permits the operator to assume
manual control at any time. The gas feeder is normally equipped with a
two-inch variable throat injector.
WARNING: HAZARDOUS GAS IS PRESENT IN THIS EQUIP-
MENTDURINGNORMALOPERATION.TOAVOIDPOSSIBLE
SEVERE PERSONAL INJURY OR DAMAGE TO THE EQUIP-
MENT, READ THIS INSTRUCTION BOOK AND THE APPRO-
PRIATE GAS MANUAL BEFORE CONNECTING THIS EQUIP-
MENT TO A SUPPLY OF GAS. OPERATION AND MAINTE-
NANCE OF THIS EQUIPMENT MUST BE RESTRICTED TO
TRAINED,QUALIFIEDPERSONNELWHOARECOMPLETELY
FAMILIAR WITH THESE INSTRUCTIONS. CONSULT FAC-
TORY FOR APPLICATIONS AGAINST A NEGATIVE HEAD
(PARTIAL VACUUM) OR A POSITIVE BACKPRESSURE OF
LESSTHAN1.0PSI(28INCHESOFWATER)INTHESOLUTION
DISCHARGE LINE.
!
!
Introd.

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
NOTE: When ordering material always specify model and serial
number of apparatus.
Table Of Contents
Very Important Safety Precautions........................... 1.010-40,-41
PreventiveMaintenanceGeneralInformation........... 1.010-5
Maintenance Record Card ........................................ 1.010-13
RegionalOffices........................................................ 1.010-1
TechnicalData .......................................................... Section 1
Installation................................................................. Section 2
Operation .................................................................. Section 3
Service ...................................................................... Section 4
Illustrations ............................................................... Section 5
Preventive Maintenance Kits and Spare Parts List ... Section 6
Literature/Manuals.................................................... Section 7
ChlorineHandlingManual ..................................... IM 25.000AA
Introd. (Cont'd)

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
VERY IMPORTANT SAFETY PRECAUTIONS - CHLORINE
This and the following pages titled “Very Important Safety Precautions” provide, in brief, information of
urgent importance relative to safety in the installation, operation, and maintenance of this equipment.
WARNING
TO AVOID POSSIBLE SEVERE PERSONAL INJURY OR EQUIPMENT DAMAGE, OBSERVE
THE FOLLOWING:
THISEQUIPMENTSHOULD BE INSTALLED,OPERATED,ANDSERVICE ONLYBYTRAINED,
QUALIFIED PERSONNEL WHO ARE THOROUGHLY FAMILIAR WITH THE ENTIRE CON-
TENTS OF THIS INSTRUCTION BOOK AND THE CHLORINE GAS HANDLING MANUAL.
CHLORINE GAS IS A RESPIRATORY IRRITANT. EXPOSURE TO CHLORINE GAS IN SUFFI-
CIENT CONCENTRATION PRODUCES IRRITATION OF THE MUCOUS MEMBRANES, THE
RESPIRATORY SYSTEM, AND THE SKIN. IN EXTREME CASES, SUFFOCATION AND DEATH
CAN OCCUR.
WHEN CHANGING CHLORINE CYLINDERS, IT IS RECOMMENDED PRACTICE TO HAVE
AN APPROVED GAS MASK AVAILABLE THAT YOU HAVE BEEN TRAINED TO USE AND
YOU MUCH BE COMPLETELY FAMILIAR WITH YOUR LOCAL PLANT OPERATING AND
EMERGENCY PROCEDURES AND CHLORINE INSTITUTE RECOMMENDED EMERGENCY
PROCEDURES.
DO NOT TOLERATE ANY CHLORINE LEAKS. CHLORINE LEAKS NEVER GET BETTER.
CHLORINE LEAKS ALWAYS GET PROGRESSIVELY WORSE IF THEY ARE NOT PROMPTLY
CORRECTED.ITIS RECOMMENDED PRACTICE TOHAVEAN APPROVED GAS MASK AVAIL-
ABLE WHEN MAKING LEAK CHECKS.
AS SOON AS THERE IS ANY INDICATION OF CHLORINE IN THE AIR, TAKE IMMEDIATE
STEPS TO CORRECT THE CONDITION.
IMPORTANT INFORMATION RELATED TO SAFETY OF CHLORINATION EQUIPMENT IN-
STALLATION IS PROVIDED IN THE CHLORINE GAS HANDLING MANUAL. IN THE INTER-
EST OF SAFE OPERATION, THIS INFORMATION MUST BE READ, UNDERSTOOD, AND
PRACTICED BY EQUIPMENT OPERATORS AND THEIR SUPERVISORS.
AT TIME OF INITIAL INSTALLATION, WHEN CHLORINE SUPPLY LINES HAVE BEEN DIS-
CONNECTEDFORANYREASONANDONAROUTINEDAILY BASIS, THOROUGHLY CHECK
ALL JOINTS, CONNECTIONS, AND EQUIPMENT FOR POSSIBLE CHLORINE LEAKS AND
IMMEDIATELY CORRECT ANY THAT MAY BE FOUND.
1.010-40

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
VERY IMPORTANT SAFETY PRECAUTIONS - CHLORINE (CONT’D)
WHEN ANY CONNECTION IS BROKEN EVEN FOR A SHORT TIME, IMMEDIATELY PLUG
THE RESULTANT OPENINGS WITH A RUBBER STOPPER OR EQUIVALENT TO PREVENT
THE ENTRANCE OF MOISTURE. MOISTURE MUST BE EXCLUDED FROM ANY PART OF
THE EQUIPMENT THAT IS NORMALLY EXPOSED TO DRY CHLORINE ONLY. WHILE DRY
CHLORINE IS NON-CORROSIVE, MOIST CHLORINE IS EXTREMELY CORROSIVE TO COM-
MON METALS, SUCH AS BRASS OR STEEL.
THE TWO MOST COMMON CAUSES OF CHLORINE PIPING LEAKS ARE:
1. RE-USE OF GASKETS. THIS SHOULD NEVER BE DONE. ALWAYS HAVE AN AD-
EQUATE SUPPLY ONHANDAND ALWAYS USE NEWGASKETSOF THE CORRECT
MATERIAL AND SIZE AS IDENTIFIED ON THE EQUIPMENT PARTS DRAWING.
2. IMPROPERLY MADE-UP THREADED PIPE JOINTS. SEE CHLORINE GAS HAN-
DLING MANUAL FOR RECOMMENDED PROCEDURE.
EXCEPT IN CASES OF LEAK DETECTION OR CALIBRATION ADJUSTMENTS, THE CHLO-
RINEGASSUPPLY MUST BE SHUT OFF ATTHEGAS SUPPLYCONTAINERSANDTHE CHLO-
RINE GAS IN THE SYSTEM EXHAUSTED BEFORE SERVICING THE EQUIPMENT.
USE ONLY USF/W&T LISTED PARTS, EXCEPT FOR COMMERCIALLY AVAILABLE PARTS
ASIDENTIFIEDON THE PARTS LIST.THEUSE OF UNLISTED PARTS CAN RESULTINEQUIP-
MENT MALFUNCTIONS HAVE HAZARDOUS CONSEQUENCES.
DO NOT DISCARD THIS INSTRUCTION BOOK UPON COMPLETION OF INSTALLATION.
INFORMATION PROVIDED IS ESSENTIAL TO PROPER AND SAFE OPERATION AND MAIN-
TENANCE.
ADDITIONAL OR REPLACEMENT COPIES OF THIS BOOK ARE AVAILABLE FROM:
USFILTER'S WALLACE & TIERNAN PRODUCTS
1901 WEST GARDEN ROAD
VINELAND, NEW JERSEY 08360
PHONE: (856) 507-9000
FAX: (856) 507-4125
NOTE
Minor part number changes may be incorporated into USF/W&T products from time to time that are
not immediately reflected in the instruction book. If such a change has apparently been made in your
equipment and does not appear to be reflected in your instruction book, contact your local USF/W&T
sales representative for information.
Please include the equipment serial number in all correspondence. It is essential for effective communi-
cation and proper equipment identification.
1.010-41

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
PROTECT YOUR EQUIPMENT INVESTMENT
MINIMIZE DOWNTIME
ORDER A PREVENTIVE MAINTENANCE KIT NOW ... KEEP ONE ON HAND
Quality + Preventive = Dependable Operation
Equipment Maintenance Minimum Downtime
There’s no question about it.
Equipment that is properly maintained is dependable equipment.
It will give optimum performance with minimum unscheduled downtime.
USFilter’s Wallace & Tiernan Products manufactures quality equipment designed for perfor-
mance and reliability. Each product is carefully tested and inspected before shipment to ensure that it
meets our high standards.
Our equipment is engineered for easy maintenance. To ensure maximum service life and minimize
unscheduled repairs, we recommend a program of regular preventive maintenance, as described in the
Service section of this book. To support this program, we developed. standard parts kits. These kits can
also be used for minor emergency repairs to minimize downtime.
We recommend that these kits be available in your stock at all times. When the complete kit or any
of its parts are used, the kit should be replaced immediately.
Preventivemaintenance kitsmay be ordereddirectlyfromthecompany thatsuppliedyour equip-
ment, or they may be ordered directly from USFilter’s Wallace & Tiernan Products. For ordering
numbers, refer to the parts list at the rear of this book.
1.010-5E

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
PREVENTIVE MAINTENANCE SCHEDULE
AND RECORD OF PERFORMANCE
This equipment should receive preventive maintenance on a one (1) year cycle.* It is recommended
that the following table be used to plan, schedule, and record this important work.
*NOTE: This is the recommended cycle. Your local operating conditions may call
for more frequent preventive maintenance.
1.010-13B
noitallatsnIfoetaD
goLecnanetniaMevitneverP
etaDeludehcS demrofrePetaD
PROTECT YOUR EQUIPMENT INVESTMENT
MINIMIZE DOWNTIME
ORDER A PREVENTIVE MAINTENANCE KIT NOW ... KEEP ONE ON HAND

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
REGIONAL OFFICES
INSTALLATION, OPERATION, MAINTENANCE, AND SERVICE INFORMATION
Direct any questions concerning this equipment that are not answered in the instruction book to the
Resellerfrom whomtheequipmentwas purchased.Iftheequipment waspurchaseddirectly from USFilter's
Wallace & Tiernan Products (USF/W&T), contact the office indicated below.
UNITED STATES
1901 West Garden Road
Vineland, NJ 08360
TEL: (856) 507-9000
FAX: (856) 507-4125
CANADA
If the equipment was purchased directly from USF/W&T Canada, contact the nearest office indicated
below.
ONTARIO QUEBEC
250 Royal Crest Court 243 Blvd. Brien
Markham, Ontario Bureau 210
L3R3S1 Repentigny, Quebec
(905) 944-2800 (514) 582-4266
MEXICO
If the equipment was purchased directly from USF/W&T de Mexico, contact the office indicated below.
Via Jose Lopez Portillo 321
Col. Sta. Maria Cuautepec
Tultitlan, Edo. de Mexico
54900 Mexico
TEL: 525 879 0260
FAX: 525 875 2171
1.010-1D

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
1
SECTION 1 - TECHNICAL DATA
List Of Contents
PARA./DWG.NO.
TechnicalData .......................................................... 1.1
Illustrations
Performance
V-2000 Injector Inlet Pressure Limits................. 25.055.190.010
VacuumLineLengthLimits ............................... 25.052.190.030

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
2
1.1 Technical Data
ycaruccAwolfdetacidnifo%4
yticapaCenirolhcrh42/bl0003ot05
egnaRdeeFgulphctoN-Venoynarof1ot01
noitacilppAfotnioPtaerusserPelbixelfhtiw.xamisp57 .enilnoitulosehtrofenelyhteylop erusserphgihhtiw.xamisp061 noitulosehtrofepipdigirroesoh .enil
erusserPtelnIrotcejnImuminiMhcni-owtehtybderiuqersiisp02 ffo-tuhsgulpdetarepoerusserp dnahcni-4/3ehtosla;rotcejni nohpys-itnataorhtdexifhcni-eno .srotcejni
erusserPtelnIrotcejnImumixaM010.091.550.52.gwDeeS

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
3
V-2000 INJECTOR INLET PRESSURE LIMITS
- PERFORMANCE
25.055.190.010
ISSUE 1 5-97

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
4
VACUUM LINE LENGTH LIMITS - PERFORMANCE
Used In Remote Vacuum Gas Feeders
25.052.190.030
ISSUE 2 10-84

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
5
SECTION 2 - INSTALLATION
List Of Contents
PARA./DWG.NO.
Location of Components........................................... 2.1
Gas Supply ................................................................ 2.2
Unpacking ................................................................. 2.3
PressureReliefValve ................................................ 2.4
Rotameter ................................................................. 2.5
Vent ......................................................................... 2.6
ElectricalConnections .............................................. 2.7
Installation of Throat and Tailway ............................ 2.8
Injector Suction Connection ..................................... 2.9
Injector Water Supply............................................... 2.10
Drain ......................................................................... 2.11
InjectorDischarge..................................................... 2.12
Point of Application .................................................. 2.13
MainConnection.................................................... 2.13.1
OpenWell .............................................................. 2.13.2
Vacuum Regulator .................................................... 2.14
Leak Check ............................................................... 2.15
Injector Arrangements for Intermittent Start-Stop
Operation ............................................................... 2.16
Illustrations
TypicalInstallation
Series V-2000 Gas Feeder .................................. 25.055.110.035
Series V-2000 Gas Feeder - With 2" Injector..... 25.055.110.070
2" Injector With 3/4" Ball Valve......................... 25.055.110.075
InstallationPiping
2" Injector - Connections for Prime and Flush
Operations........................................................ 25.100.006.122
2" Injector - Connections for Manual Suction
Shut-OffUnit ................................................... 25.100.06.131
2" Injector - Connections for Intermittent
Start-Stop Operation........................................ 25.100.006.142
2" Injector - Connections for Intermittent
Start-Stop Operation With Injector Suction
Shut-OffUnit ................................................... 25.100.006.152
PVC Pipe - Installation .......................................... 50.830.110.011

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
6
WARNING: THIS CONTROL MODULE IS DESIGNED TO OP-
ERATE UNDER VACUUM ONLY. TO AVOID POSSIBLE SE-
VEREPERSONALINJURYOREQUIPMENTDAMAGE,DONOT
CONNECT TO A SOURCE OF GAS UNDER PRESSURE.
2.1 Location of Components
The general physical requirements of the installation are shown on the
Typical Installation drawings. Locate the control module so that the nec-
essary gas and power supplies may be connected. Ready access to the
equipment for operation, routine maintenance, and service is required.
Locate the injector so that the water supply, solution line to the point of
application, and suction lines are connected with access for service con-
venientlyprovided.
2.2 Gas Supply
For gas supply installation details, refer to the separate instruction book
providedwiththevacuumregulator(whichregulatesthegassupplytothe
control module).
2.3 Unpacking
When the equipment and accessory items are unpacked, check all items
against the packing list to be sure that no parts are discarded with the
packingmaterial.Wheneverpossible,unpacktheequipmentattheinstal-
lation site. Set aside items not required at the time of installation, such as
spare parts, where they will be available when needed.
WARNING:TOAVOIDPOSSIBLESEVEREPERSONALINJURY
OR EQUIPMENT DAMAGE, DO NOT DISCARD OR REMOVE
THIS INSTRUCTION BOOK WHEN THE INSTALLATION IS
COMPLETED. THE OPERATOR WILL NEED IT.
CAUTION: To prevent damage to the module, replace the shim
washersunderneath the module after theplywood feet are removed.
2.4 Pressure Relief Valve
WARNING:TOAVOIDPOSSIBLESEVEREPERSONALINJURY
OR EQUIPMENT DAMAGE, A PRESSURE RELIEF VALVE
MUST BE INSTALLED THE SYSTEM.
NOTE: See appropriate Typical Installation drawings.
!
!
!
!

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
7
2.5 Rotameter
For protection in shipment, the rotameter and associated parts are re-
moved after the gas feeder is factory tested. These parts are separately
packaged; assemble and install as indicated on Dwg. 25.055.151.010.
2.6 Vent
Asshownonthetypicalinstallationdrawings,aventlineisrequiredfrom
thepressurereliefporttoapointoutsidethebuildingwherethegascannot
causeinjurytopersonnelordamagetoequipment.Theproperinstallation
ofthislineisimportant.Forgasesotherthanammonia,thegradientofthe
line must be continuous (down, if possible), without traps, and the atmo-
spheric end should point down and be screened against the entrance of
foreignmaterials.Forammonia,thegradientofthelinemustbecontinuous
(up, if possible), without traps, and the atmospheric end should point up
and be provided with a suitable raincap to prevent the entrance of water
andforeign materials. Allow for freedischarge of vapor. Where traps are
unavoidable,provisionsforcondensateremovalmustbeinstalledatalllow
points.Suitablesupportfortheventisrequiredthroughoutitsentirelength.
The vent lines from the vacuum regulator-check units are covered in a
separate book.
NOTE: See appropriate Typical Installation drawings at the end of
this section.
WARNING:THEPRESSURERELIEFVALVEMUSTBEVENTED
TO AN AREA WHERE GAS FUMES CANNOT CAUSE INJURY
TOPERSONNELORDAMAGETOEQUIPMENT.DONOTTER-
MINATETHEVENTLINEATALOCATIONROUTINELYUSED
BY PERSONNEL, SUCH AS WORK AREAS OR PATHWAYS,
NORNEARWINDOWSORVENTILATIONSYSTEMINTAKES.
2.7 Electrical Connections
If the control module is furnished with built-in accessories requiring a
power supply or wiring to other equipment, appropriate wiring diagrams
will be found in the instructions for the accessory items.
NOTE: Field wiring must conform to local electrical codes.
2.8 Installation of Throat and Tailway
Thethroatandtailwayof3/4-inchandone-inchfixedthroatinjectorsmust
be assembled as shown on the parts drawings. If faulty injector action is
!

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
8
suspected,inspecttheO-ringsandreplacethemifthereisanydoubtabout
theircondition.
2.9 Injector Suction Connection
Except in those instances where the injector is installed in the control
module, a line must be provided to carry the gas from the module to the
injector. The piping must be sized as required to obtain six inches of
mercury minimum vacuum at the module.
2.10 Injector Water Supply
Theinjectorrequiresasupplyofreasonablyclean water. Equip the water
supplyuptoandincludingtwo-inchsizeswithastrainer,asindicatedinthe
Typical Installation drawing in this section. The pressure and quantity of
water required varies from one installation to another.
2.11 Drain
Two-inch bellofram type injectors used for start-stop operation require a
1/4-inchIDdrainhosetodisposeofashortspurtofwaterwhentheinjector
is operated. Run the drain hose to a suitable floor drain or waste pipe.
Forone-inchand3/4-inchfixedthroatinjectors,nofloordrainisrequired;
however, a drain is always desirable to facilitate injector service.
2.12 Injector Discharge
For3/4-inch fixed throat injector,the tailway (beige color) is designed to
accept3/4-inchpolyethylenetubingor3/4-inchthreadedpipeconnection.
NOTE: For pipe thread connection, do not cut off the serrated sec-
tion.
For one-inch fixed throat injectors, a rigid PVC pipe or USF/W&T solu-
tionhoseisrequiredbetweentheinjectordischargeandthepointofappli-
cation.Thepipe size depends on the size ofthethroat and tailway used in
the injector, the operating water pressure, and length of the solution line.
Solution hose may be connected directly to the injector tailway. If rigid
PVCpipe is used,apieceofstraight pipe atleasteightinches long should
be coupled to the end of the injector tailway before any elbows, tees, or
Saunders valves are used. This is to prevent any flow disturbances that
could affect the hydraulic performance of the tailway connections (see
Dwg. 25.200.003.010).

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
9
For the two-inch variable throat injectors, two-inch polyethylene pipe or
two-inchrigidPVCpipeisnormallyused.Solutionhosemaybeconnected
directlytotheinjectortailway.IfrigidPVCpipeisused,apieceofstraight
pipe at least 12 inches long should be coupled to the end of the injector
tailway before any elbows, tees, or Saunders valves are used. This is to
preventanyflowdisturbancesthatcouldaffectthehydraulicperformance
of the tailway. Discharge in an upward direction.
2.13 Point of Application
2.13.1 Main Connection
If the solution is to be applied in a main, a suitable pipe tap is required in
the main to accommodate the solution tube or diffuser.
2.13.2 Open Well
Ifthesolution is tobeappliedin a basin,flume,channel,etc., where there
isnopressure,thelinefromtheinjectormustbesupportedsothattheopen
endis submerged to the bottom of the chamber, or a minimum of sixfeet,
if possible, and is located in a nonstagnant area.
2.14 Vacuum Regulator
A vacuum regulator (or vacuum regulator-check unit), which is a gas
pressure reducing valve (and check), is connected to the control module
inlet. Refer to the separate instruction book supplied with the unit for
installation instructions for the unit.
2.15 Leak Check
After the vacuum regulator(s) (or vacuum regulator-check unit) are in
place,andbeforethegastubingorpipingthatwillconnectittothecontrol
moduleisinstalled,checkforgasleaksasdirectedintheseparateinstruc-
tion book provided with the vacuum regulator.
WARNING:TOAVOIDPOSSIBLESEVEREPERSONALINJURY
OR EQUIPMENT DAMAGE, DO NOT TOLERATE ANY CHLO-
RINELEAKS.LEAKSALWAYSGETPROGRESSIVELYWORSE
AND MUST BE CORRECTED PROMPTLY.
NOTE: The vacuum line extending from the control module to the
vacuumregulatormustnotexceedthedistanceasdeterminedthrough
the use of the graph shown on Dwg. 25.052.190.030 for the standard
tubing and pipe sizes given. If necessary, any tubing or pipe can be
!

IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
10
installedthat willnot givemore thanfive inchesof water differential
between the module and vacuum regulator at the maximum chlori-
natorfeedrate.Notethattheequivalentlengthofthefittingsmustbe
added to the tubing length to obtain the total equivalent length as
shown on the graph.
2.16 Injector Arrangements for Intermittent Start-Stop Operation
Ifthegasfeederistobeoperatedintermittentlyinconjunctionwithapump
orotherequipment, this is usually accomplished by oneof the following:
• Two-inch injectors with three-way shut-off valves may be fitted with
solenoid valves as shown in Dwgs. 25.100.006.122, 25.100.006.142,
and/or 25.100.006.152 in this section. Material for this purpose is
furnished only when specifically listed in the order.
• Other injectors may be shut off by means of an electrically operated
valve in the water supply line to the injector. In this case, flexible
polyethylene or rigid PVC pipe is recommended for a minimum of
three feet immediately upstream of the injector. This should reduce
corrosionofmetalpipe and components (valves, pump impellers, etc.)
caused by diffusion of chlorine solution during shut-down periods.
Other manuals for V-2000
1
Table of contents
Other USFilter Water Filtration System manuals
Popular Water Filtration System manuals by other brands

HEISSNER
HEISSNER Smartline HLF4000-00 Instructions for use

Arkal
Arkal 2" Sand Separator Operation, Service & Maintenance Manual

Oneida Air Systems
Oneida Air Systems Dust Deputy Plus AXD050004 instructions

jbc
jbc FAE2-100 manual

Klimawent
Klimawent STRONG-2000-N Use and maintenance manual

GE
GE Culligan FXRT12 quick start guide

Kessel
Kessel EasyClean Installation and operating instructions

Angelo Decor
Angelo Decor 1500 quick start guide

Promolife
Promolife Hydrogen Water Tumbler quick start guide

Clean Water Systems
Clean Water Systems 7500-REV2.5 installation guide

A.O. Smith
A.O. Smith Pro AOW-4000 owner's manual

Vision Aqua
Vision Aqua VA-Basic instructions