• Type__PROP (Adjust value between OFF, PROP, ON/OFF or TIMED)
(only if set to Timed there are two new entries to make dosage cycles ON /
OFF selectable)
o Timed ON (Change the value from 5 to 3600 seconds)
o Timed OFF (Change the value from 5 to 3600 seconds)
§ Chlorine_Measure (only if enabled)
• Setpoint___1.2_ppm (Adjust value with enter and up or down key) It’s
possible to adjust from 0.0 to 5.0 ppm
• sp_type___low (Adjust value LOW or HIGH)
• ofa_time_000_min (Change the value from 1 to 240 minutes or Off)
• AlrBand__1.0ppm (Adjust value from 0.0 to 5.0 ppm)
• Type__PROP (Adjust value between OFF, PROP, ON/OFF or TIMED)
(only if set to Timed there are two new entries to make dosage cycles ON /
OFF selectable)
o Timed ON (Change the value from 5 to 3600 seconds)
o Timed OFF (Change the value from 5 to 3600 seconds)
§ Flow rate meas. (only if is present)
• sensor_K Factor (Select the sensor type with enter and up or down
key) It’s possible to select K Factor of W. Meter (Water Meter). Once the
type of sensor will be changed the system will ask for a reset of the
resettable totalizer and a new start date for the counter.
• K factor___1.00 / W.Meter__1I/ 1L (This screen depend from the
type of sensor selected in the menu item before) For K Factor sensor:
Adjust value from 0.01 to 99999,99. For W. Meter sensor the value is in
pulses/liter; adjust value between I=0÷999 L=0÷999. If the sensor is
calibrated in this menu (K Factor and Water Meter), the string “Cal” appear
for a couple of seconds in place of the actual number, indicating that the
instrument will use the parameter recalculated based on the calibration.
• Flow unit___L/s (Change the measure unit between: liters per second
(L/s), liters per minute (L/m), cubic meters per hour (m3/h) and gallons per
minute (GPM))
• Total unit___L (Change the measure unit between: liters (L), cubic
meters (m3) and gallons (GAL))
• Reset tr total (Reset the resettable totalizer) After a confirmation
message, “ENTER to confirm”, will be asked to set the new start date for the
counter (dd/mmm/yyyy). If there is not date set in the screen with the Tr
totalizer value will be displayed “install”.
§ INPUT Flow (Adjust value with enter and up or down key Enable or Disable)
• It’s possible to enable(ON) or disable (OFF) signal input
§ Cal (Calibration_probe) (Adjust value with enter and up or down key)
§ Full (pH 7 and 4, Redox 465 mV buffer solution)
§ Easy (pH 7, Redox 465 mV buffer solution)
§ Off (Disabled)
§ 3 PUMP*(Third external pump management) It’s possible to enable (ON) or
disable (OFF) the output for external pump
§ 3P-TIME ON (Adjust value from 00m01s to 59m59s, it’s
the time which the third external pump output is active)
§ 3P-TIME OFF (Adjust value from 00m01s to 59m59s, it’s
the time which the third external pump output is off)