VAMP VAMP 220 User manual

VAMP 220 / 220R
Arc protection system
User manual

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
2 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 3
Table of Content
Preface .........................................................................................5
1. Introduction ............................................................................6
2. System description.................................................................8
2.1. Master unit VAMP 220/220R...............................................8
2.1.1.General .........................................................................8
2.1.2.Functional description.................................................9
2.2. Slave unit VAM 12 CD...................................................... 11
2.3. Arc sensor VA 1 DA.......................................................... 12
2.4. Portable sensor VA 1 DP.................................................. 13
2.5. Trip multiplier relay VAR 4 CE.......................................... 14
2.6. Systems with multiple master units................................. 15
2.7. Selective arc protection ................................................. 15
3. Technical data .....................................................................17
3.1. Master unit VAMP 220/220R............................................ 17
3.2. Slave unit VAM 12 CD...................................................... 19
3.3. Arc sensor VA 1 DA.......................................................... 20
3.4. Portable sensor VA 1 DP.................................................. 20
3.5. Trip multiplier relay VAR 4 CE.......................................... 20
4. Product handling..................................................................21
4.1. Receiving goods .............................................................. 21
4.1.1.Unpacking and transportation............................... 21
4.1.2.Checking the consignment .................................... 21
4.1.3.Complaints................................................................. 21
4.2. Warranty............................................................................ 21
5. System installation................................................................23
5.1. Safety notes....................................................................... 23
5.2. Preparing for installation ................................................. 23
5.3. Installing master unit VAMP 220/220R........................... 24
5.3.1.Mounting master unit VAMP 220/220R.................. 24
5.3.2.Wiring the master unit, overview............................ 24
5.3.3.Wiring secondary circuits of current transformers 25
5.3.4.Wiring trip circuits of circuit breakers..................... 26
5.3.5.Wiring alarm circuits ................................................. 27
5.3.6.Protective earthing................................................... 27
5.3.7.Wiring auxiliary supply .............................................. 27
5.4. Installing slave units.......................................................... 29
5.4.1.Mounting slave unit VAM 12 CD............................. 29
5.4.2.Wiring between master and slave......................... 29
5.4.3.Wiring separate power supply to VAM 12 CD...... 30
5.5. Installing sensors................................................................ 31
5.5.1.Mounting arc sensor VA 1 DA................................. 31
5.5.2.Connecting sensors to slave units.......................... 32
5.5.3.Connecting portable sensor................................... 33
5.5.4.Arc sensor wiring over long distances ................... 33
5.6. Installing trip multiplier VAR 4 CE.................................... 33

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
4 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
5.7. Wiring multiple master systems....................................... 35
5.8. Wiring systems with selective arc protection............... 36
5.9. Checking wirings.............................................................. 36
5.9.1.Visual inspection ....................................................... 36
5.9.2.Control by measuring............................................... 37
6. Commissioning.....................................................................38
6.1. Using master unit control panel ..................................... 38
6.1.1.General ...................................................................... 38
6.1.2.Control modes........................................................... 39
6.1.3.Fast guide of the function menu............................ 40
6.1.4.Push-button functions............................................... 41
6.2. Using slave unit panel...................................................... 41
6.3. Setting addresses of slave units...................................... 42
6.4. System configuration....................................................... 43
6.5. Setting overcurrent values.............................................. 45
6.6. Relay output settings ....................................................... 47
6.7. Testing the arc sensors..................................................... 54
7. Operational measures.........................................................55
7.1. Arc faults............................................................................ 55
7.1.1.Arc fault tripping alarm............................................ 55
7.1.2.Reading arc fault information ................................ 55
7.2. Supervision of phase currents......................................... 56
7.2.1.Overcurrent warning................................................ 56
7.2.2.Reading current values............................................ 56
7.3. Handling self-supervision faults....................................... 57
7.3.1.Error indications......................................................... 57
7.3.2.Reading and erasing error messages.................... 58
7.3.3.Fault codes ................................................................ 59
7.3.4.VAM 12 CD TEST/ERROR indication........................ 60
7.4. Checking system configuration..................................... 61
8. Application examples.........................................................62
8.1. System with two master units.......................................... 62
9. Product information .............................................................63
9.1. Dimensional drawing....................................................... 63
9.2. Panel mounting................................................................ 64
9.3. Semi-flush mounting......................................................... 64
Ordering code VAMP220/220R................................................65
11.Reference information.........................................................67

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 5
Preface
This user’s manual provides information for handling,
mounting, wiring, commissioning and operating the VAMP 220
arc protection system. It also includes a system description,
technical data and some application examples.
The first chapter introduces the VAMP arc protection system
and its modules. Chapter 2, SYSTEM DESCRIPTION,
describes the system modules and their functions. Chapter 3
provides technical data in table format, and chapter 4 gives
general product handling information for new owners.
Chapter 5, SYSTEM INSTALLATION, gives instructions for
mounting and wiring the VAMP 220 modules, while chapter 6,
COMMISSIONING, describes how to do the address setting,
system configuration and parameter setting necessary for
making the system work in the desired way. In chapter 6 you
will also find instructions for using the control panel of the
master unit.
Chapter 7, OPERATIONAL MEASURES, deals with measures
that can be taken during operation. It shows how to handle
alarm signals, how to read measured values, and how to
interpret internal fault signals.
In chapter 8 some application examples with illustrative
pictures are given, and in chapter 9 ordering information and
contact information.
In this manual, we use the following styles of presentation to
notify the reader of important, critical or risky factors and
situations:
NOTE!
Note text is used to stress and draw attention to facts and cir-
cumstances that should be specially noted.
CAUTION!
Caution text is used to draw attention to factors that may
cause damage on the equipment.
WARNING!
Warning text is used to draw attention to situations and
circumstances that may cause personal injury. When a warning
appears, follow the instructions in the text thoroughly.

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
6 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
1. Introduction
VAMP 220 is a state-of-the-art arc protection system for
electrical power distribution systems. By using VAMP 220 in
switchgears considerable safety improvements are obtained in
the form of minimized injury and damage in case of an arc
fault.
VAMP 220 uses modern microprocessor technology and
provides numerous new features previously not found in
similar devices.
Key features of VAMP 220:
a total operating time of 7 milliseconds
exact location of the activating arc sensor
self-supervision of the entire system
system wiring using standard copper cables
self configuration.
In addition to the high-level requirements set for protective
relays, VAMP 220 meets the most recent EMC-standards.
Figure 1-1 VAMP 220 arc protection system.
VAMP 220 is a modular system composed of a master unit,
slave units, arc sensors, temperature sensors, and possible trip
multiplying units and interface units.
The master unit VAMP 220 includes all the main functions of
the arc protection system, such as overcurrent, arc and
temperature supervision. Up to 10 slave units can be connected
to a master unit.
The slave unit VAM 12 CD serve as a link between the sensors
and the master unit. Each slave unit can be connected to ten
fixed arc sensors, one temperature sensor and one portable arc
sensor.

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 7
The arc sensor VA 1 DA is activated by strong light which it
transforms to a current signal. The signal is tranferred via the
slave to the master unit.
The portable sensor VA 1 DP is an arc sensor that can be
temporarily connected to a slave. Attached to persons it
improves the personal safety during work in live switchgears.
The master unit provides up to four trip output channels for
tripping circuit-breakers. By connecting the trip multiplying
relay VAR 4 CE to the outputs, up to 16 trip outputs can be
obtained.
The standard sensor cable length is 6m. Arc sensors can be con-
nected over longer distances, up to 20 m, using a sensor with a
shielded cable.
Thanks to the modularity, the system can be flexibly adapted to
a variety of arc protection applications, ranging from simple
systems with one master unit and one slave unit to complex
solutions comprising multiple master units, for instance, in
applications with selective arc protection.
VAMP220 suits both low voltage and medium voltage
switchgears. It can be installed in new as well as existing
switchgears.

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
8 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
2. System description
2.1. Master unit VAMP 220/220R
2.1.1. General
The master unit, which can be mounted into the infeeder
cubicle of the switchgear or in any other suitable space,
includes all the main functions of the arc protection system. It
comprises the following integrated subunits:
•a 3-phase overcurrent unit
•an arc protection unit
•a circuit-breaker failure protection unit
•a temperature supervision unit
•input and output elements
•arc and overcurrent BI/O unit
•a self-supervision un it.
VY 056 A
VY036A
VAMP
220 R
S
E
TRIP 1
TRIP 3
TRIP 5
TRIP 2
TRIP 4
TRIP 6
POWER
ERROR
COM
INSTALL
CURRENT
RUN
TEMP
INFO
ERROR
TEMP SET
Latch
I
I
I
>1A
>5A
Figure 2.1.1-1 Master unit VAMP 220/220R.
When the conditions for an arc short circuit occur
(simultaneous overcurrent and arc signal), the master unit
trips the circuit-breaker(s) of the incoming feeder(s). A master
unit can trip up to four circuit breakers. If more than four
parallel trip outputs are required, the trip multiplier relay VAR
4 CE can be used.

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 9
The tripping of the arc protection system can be backed up by
employing the built-in circuit breaker failure protection
subunit. This unit trips another breaker, for instance, the
upstream circuit breaker, in case the main circuit breaker
should fail to operate. Thus, it gives the system redundancy
and increased security.
The master unit includes a unidirectional arc input, a
unidirectional current dependent arc output, and a bi-
directional arc in/output. Furthermore, the master unit is
equipped with a unidirectional overcurrent output and a bi-
directional overcurrent in/output. With these properties a
selective arc protection can be built even in complex
distribution systems.
Any voltage within the range 40 - 265 V ac or dc (or optionally
18 - 36 V dc) can be used as auxiliary supply voltage for the
master unit. All internal supply voltages required by the
system are derived from the auxiliary supply voltage of the
master unit.
NOTE!
It is recommended that the auxiliary voltage is fed from a
secured source, which is unaffected by a possible arc fault.
2.1.2. Functional description
The current inputs of the three-phase overcurrent subunit
(220) or two-phase overcurrent and E/F subunits (220R) are
connected in series with any other possible protective devices of
the switchgear. The start value of the overcurrent (220) /
overcurrent + E/F (220R) subunits are set according to the
preconditions determined by the arc short circuit and/or E/F
current (220R) , independently of the settings of any other
protection systems within the switchgear. The start value is set
with a potentiometer knob on the control panel of the master
unit (220). VAMP 220R has a separate E/F setting.
The arc protection unit obtains its measuring signals from the
slave units, to which the arc sensors of the system are
connected. The unit starts when one or more of the system's
arc sensors are activated.
At a simultaneous activation of the overcurrent unit (220) /
overcurrent or/and E/F unit (220R) and the arc protection unit,
the arc protection system operates and the output elements trip
the circuit-breakers.
NOTE!
No operation takes place if only one unit (either the
overcurrent or arc protection unit) is activated.

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
10 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
NOTE!
The arc, overcurrent and E/F (220R) stages can also be
activated from external BI/O signals.
The circuit breaker failure protection subunit (CBFP) starts if
the preconditions for the operation of the arc protection unit
have not disappeared when a set operate time (80, 100 or 150
ms) has elapsed since the arc fault trip. The CBFP, which is
optional, trips its own circuit breaker. When not used, its trip
contacts are left unwired.
If not used for circuit breaker failure protection, the CBFP
output contact (TRIP3) can be set to operate in parallel with
the actual trip circuit (TRIP1), if two circuit breakers are to be
tripped simultaneously.
The desired function for the third trip circuit (TRIP3) is to be
specified when ordering the master unit.
By default, TRIP3 is programmed for CBFP function with a
time delay of 80 ms.
Figure 2.1.2-1 shows the TRIP signalling block diagram of
VAMP 220.

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 11
L>
I>
L>
I>
L>
L>
I>
I
>
L>
TR1
TR1
TR1
L>
I>
VAMP 220 R T
r
i
p
Si
gna
lli
ng
Bl
oc
k Di
agram
SW2
SW5
BIO option PCB
Power/Trafo/Trip PCB
from ARC sensor
from Slave
3 x
t
La >
80ms
100ms
150ms
Lb>
Ia>
&
Ib>
I>
L>
Tem p A la r m
L>
I>
LOC
LOC
La >
Lc>
L4>
TR4
TR4
I>
T5
T6
T6
T5
T5
T6
TR2
I>
LOC
L>
LOC
TRIP 2
TRIP 3
TempAl/TRIP4
TRIP 1
>1
L>
I>
>1
>1
T1
T2
T3
L
SW3
T3
LL
SW2
T2
L
SW1
T1
>1
SW7
SW8
int.sw.
&
&
&
+48V (BIO)
+5V (GND)
TRIP 6
TRIP 5
1
1
TR loc
TR loc
I>
L>
L
L
L
>
>1
1
2
3
4
5
6
7
8
9
10
11,12,13
14
15
16
17
18
L4>
0ms
>1
SW6
int.sw.
SW4
L
Figure 2.1.2-1 Trip signalling block diagram of VAMP 220.
2.2. Slave unit VAM 12 CD
The slave units, which can be mounted into suitable places in
the switchgear compartments, serve as links between the
sensors and the master unit. Each slave unit can be connected
to ten arc sensors and one portable arc sensor. Up to 10 slave
units can be connected to one master unit. The master unit and
the slave units are interconnected by means of modular cables.
The slave units contain, for instance, the self-supervision of the
connected arc sensors.

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
12 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
VAM
12 CD
POWER
COM
TEST/ERROR
SENSOR ADDR. COM1 COM2
VY005A
ARC SENSORS 1 ... 10 24 V
1 2 3 4 5 6 7 8 9 10
Made in Finland
T
E
M
P
S
S
I++
Figure 2.2-1 Slave unit VAM 12 CD.
When the system operates due to an arc fault, information of
the sensor that caused the operation is forwarded by the slave
unit to the master unit. The slave number and sensor number
is then displayed by the master unit.
The slave unit supervises all its sensors continuously. In an
internal fault situation the fault information is transferred to
the master unit and the fault can be viewed on the display of
the master unit.
A fault alarm is also given if an arc sensor connected to the
slave unit remains in active state for more than 7 s. This can
happen, for instance, if the arc sensor is exposed to direct sun
light. At the same time the corresponding slave unit is
disconnected from the master unit in order to prevent false
circuit-breaker trippings. When the interference light
disappears, the function of the slave unit is restored.
2.3. Arc sensor VA 1 DA
The arc sensor is a light sensitive element, which is activated
by strong light. Arc sensors should be mounted in the
switchgear cubicles in such a way that they cover the space to
be protected as completely as possible.

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 13
Figure 2.3-1 Arc sensor VA 1 DA.
A sudden increase of the light intensity is interpreted as an arc
fault. The electronic circuits of the sensor transforms the light
message into a current message and transmits it to the slave
unit, which forwards it to the master unit.
The sensitivity of the sensor is nearly equal over the front side.
At the rear side the sensitivity decreases remarkably. See
Figure 2.3-2. In a switchgear, however, the light caused by an
arc is reflected from the walls. Therefore, the mounting position
of the sensor is not critical.
The standard sensor cable length is 6 m. As an option, a
shielded cable can be used for distances up to 20 m.
40 30 20 10 0
50
60
70
80
90
100
120
130
140
100%
80
60
40
20
Figure 2.3-2 The sensitivity of the arc sensor to light from different
directions.
2.4. Portable sensor VA 1 DP
This module is a portable sensor element which can be
temporarily connected to the slave units. It is used to improve
personal safety during work, for instance during maintenance
work, in a live switchgear. The sensor should be located close to
the place where work is done. It can, for instance, be attached
to the breast pocket of the service man's shirt or boiler suit.
The function of the portable arc sensor equals that of the fix-
mounted arc sensors. The difference is that the portable arc
sensor can be moved around within the reach of the connection
cable.

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
14 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
Figure 2.4-1 Portable sensor VA 1 DP in use.
The connector of the portable arc sensor can be plugged into the
SENSOR connector of any slave unit of the arc protection
system. The portable sensor should be attached in such a way
that the sight is clear towards the working place.
NOTE!
To avoid false activations, the portable arc sensor must be dis-
connected from the slave unit immediately after use.
2.5. Trip multiplier relay VAR 4 CE
With the VAR 4 CE multiplying relay the TRIP signals can be
multiplied. Each multiplying relay has four ultra fast trip
outputs, each of which can trip its own circuit breaker. Any
combination of NO and NC contacts is available (to be specified
in the order, see Figure 5.6-1 and table 9.3-1).
Figure 2.5-1 Trip multiplier relay VAR 4 CE.

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 15
Up to four trip functions are available by connecting TRIP1
and/or TRIP2 output to the control inputs of the trip multiplier
relay. Auxiliary supply voltage is available from the 24 V OUT
terminals of the master unit.
2.6. Systems with multiple master units
Especially in medium-voltage switchgears the power may be
fed from two or more infeeders. At an arc fault situation, each
infeeder that can supply short circuit power must be tripped. In
these applications, the arc protection system may include
several master units, that is, one master unit per infeeder.
In applications with multiple master units, the master units
are interconnected via the BI/O connectors. When an arc sensor
in the system is activated, information is transferred over the
BI/O lines to all master units in the system. As a consequense,
all master units with the overcurrent subunit activated will
trip their respective circuit breakers.
If a master unit connected to the BI/O lines is tripping, and the
arc or overcurrent activation comes from a BI/O connection, the
identifier of the activated BI/O line will be shown on the
display.
2.7. Selective arc protection
The master unit facilitates a selective arc protection even in
more complex electricity distribution systems. As mentioned
earlier, it includes the following input/output modules:
•unidirectional arc input
•unidirectional arc output (current dependent)
•bidirectional arc in/output
•unidirectional overcurrent output
•bidirectional overcurrent in/output.
By utilizing these features, complex busbar systems can be
divided into separate zones. Each zone includes the parts of the
distribution system that are limited by two or more circuit-
breakers. See the example in Figure 2.7-1. Selective arc
protection means that all zones are protected independently of
each other.
In the example in Figure 2.7-1, VAMP 220 master units are
used for tripping the circuit-breakers K4, K5, K6 and K7 as
well as the actual infeeding circuit-breakers K1, K2 and K3.

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
16 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
Suppose that an arc fault occurs in switchgear B in Figure 2.7-
1, in a situation where circuit-breaker K3 is closed and the
other two infeeding circuit-breakers are open. The arc fault
power is fed via K3 to switchgear C and further to switchgear B
by bus ducts E, A and D. The master unit of the bus duct D
(which trips the circuit-breaker K6) obtains the unidirectional
arc information from the B I/ O bus of the master unit in
switchgear B. In other words, when an arc occurs in switchgear
B, the arc information is forwarded to all master units that
limits that particular zone, independently on their physical
location. In the described infeeding arrangements the pre-
conditions for an arc fault (arc signal and overcurrent) are
fulfilled only in the master unit tripping the circuit-breaker K6.
Therefore, K6 is the only circuit breaker that is tripped.
In this example, the overcurrent BI/O lines are not used.
Figure 2.7-1 Selective arc protection using VAMP 220 master unit
(example).

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 17
3. Technical data
3.1. Master unit VAMP 220/220R
Power supply Us 40…265V ac/dc
(option): 18…36V dc)
Rated current In
Rated frequency fn
1A / 5A
45…65Hz
Power consumption ≤0.3VA
Three phase overcurrent
stages (220)
Two phase overcurrent and
E/F stage (220R)
Thermal withstand capability
- continuous
- for 1s
4 x In
100 x In
IL>
Inaccuracy
0.9…6.0 x In
±10%
Io>
Inaccuracy
0.01…0.1 x In
±10% or 5mA
Reset ratio 0.95
Operating settings, phase
overcurrent stage
t>
t> CBFP
7ms
7, 80, 100, 150ms
TRIP contacts Normally open
4 pcs (standard) + 2 pcs (option)
Rated voltage ≤250V ac/dc
Continuous carry 5A
Make and carry for 0.5s 30A
Make and carry for 3s 15A
Breaking capacity DC, when
time constant L/R=40ms
50W
Contact material AgCdO2
Tripping contacts
Operating time
- TRIP1, 2, 3, 4, 5, 6
- CBFP (TRIP3)
7ms
7, 80, 100, 150ms
SF (error) alarm Change-over contact
Trip alarm Normally open
Rated voltage ≤250V ac/dc
Continuous carry 5A
Make and carry for 0.5s 10A
Make and carry for 3s 8A
Breaking capacity DC, when
time constant L/R=40ms for
- 48 Vdc
- 110 Vdc
- 220Vdc
1A
0.25A
0.05A
Signal / alarm contacts
Contact material AgCdO2

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
18 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
Rated voltage
Rated current
+48Vdc
20mA
L> BIO line (IN/OUT)
L> UIO line (dependent OUT)
L> UIO line (IN)
1 pcs (La>)
1 pcs (Lb>)
1 pcs (Lc>)
I> UIO line (OUT)
I> BIO line (IN/OUT)
1 pcs (Ia>)
1 pcs (Ib>)
BIO inputs / Outputs
Optional:
L> UIO (IN)
L> UIO (OUT)
I> UIO (IN)
I> UIO (OUT)
5 pcs
2 pcs
3 pcs
1 pcs
Slave units 10 pcs / 100 sensorsARC inputs
BIO Input/Output channels ARC information (+48Vdc) 3
channels + 7 channels (option)
Slave port
Transfer protocol
Electrical connection
Transfer rate
Multi drop (to slave units)
I2C
RS485 (15kV)
20 kbit/s
Communication
Programming port baud rate 9600 b/s
EMC tests CE approved and tested
according to EN 20081-2,
EN 50082-2
Voltage tests Insulation test voltage acc. to
IEC 255-5
Impulse test voltage acc. to
IEC 255-5
2kV, 50Hz, 1min
5kV, 1.2/50 µs, 0.5J
Emission tests Radiated and conducted
emission according to EN55011
class A
High-frequency (1MHz)
disturbance test according to
IEC 255-22-1, class III
- common mode
- differential mode
2.5kV
1.0kV
Fast transient according to IEC
255-22-4, class III and IEC 801-
4, level 4
- power supply input
- other inputs
4kV, 5/50ns
2kV, 5/50ns
Immunity tests
Electronic discharge test acc. to
IEC 255-22-2 and IEC 801-2,
class III
- air discharge
- contact discharge
8kV
6kV

VAMP Ltd Arc protection system
User manual VAMP 220 / 220R
VM220.EN004 Vamp 24h support phone : +358 (0)40 573 6316 19
RF electromagnetic field test
acc. to IEC 1000-4-3 and ENV
50140
f = 90…1000MHz
10V / m
Conducted RF disturbance test
acc. to ENV 50141 and IEC
1000-4-6
f = 150kHz…80MHz
10V / m
Vibration test 2…13.2Hz, ±1.0mm
13.2…100Hz, ±0.7g
Mechanical tests
Shock/bimp test acc. to IEC 255-
21-2
20g, 1000 bumps/dir.
Specified ambient temperature
range
0…+55 °C
Environmental conditions
Transport and storage
temperature range
-40…+70 °C
Protection by enclosure IP20
Weight About 4 kg
Dimensions (HxWxD) 155 x 208 x 223 mm
Housing
Panel cut-out (H x W) 139 x 193 mm
3.2. Slave unit VAM 12 CD
Power supply Voltage from the master unit
(via modular cable VX010 or
separate cable)
24 Vdc
Sensor connections Number, total:
- arc sensors
- portable sensors
11
10
1
Indications LEDs:
- green
- yellow
- red
Power
Communication
Test/Error
Transfer protocol I2C
Electrical connection RS485
Serial bus
Transfer rate 20 kbit/s
Operating temperature -10…+55 °C
Storage temperature -40…+70 °C
Relative humidity < 95%, 40 °C, 56 days
Vibration IEC 60721-3-3
Environmental conditions
Shock IEC 60068-2-27
Protection by enclosure IP21
Weight About 0.4 kg
Housing
Dimensions (H x W x D) 90 x 140 x 60 mm

VAMP 220 / 220R Arc protection system
User manual VAMP Ltd
20 Vamp 24h support phone : +358 (0)40 573 6316 VM220.EN004
3.3. Arc sensor VA 1 DA
Voltage from slave unit 12 VdcSupply voltage
Power consumption ≤2.5 mA
Operating temperature -10…+55 °C
Storing temperature -40…+70 °C
Relative humidity < 95%, 40 °C, 56 days
Vibration IEC 60721-3-3
Environmental conditions
Shock IEC 60068-2-27
Protection by enclosure IP21Enclosure
Weight About 0.01 kg
Connection cable Between master – slave
- VX010
Between slave – slave
- VX001
6 m (standard cable)
20m (shielded cable)
6 m (standard cable)
20m (shielded cable)
3.4. Portable sensor VA 1 DP
See table in section 3.3.
3.5. Trip multiplier relay VAR 4 CE
Power supply Voltage from the master unit
(via separate cable)
24 Vdc
Inputs TRIP signals from the master
unit
1 NO contact
Number 4 NO contacts
Rated voltage ≤250V ac/dc
Rated current 5A
Make and carry for 0.3s ≤30A
TRIP signals
Breaking capacity DC, when
time constant L/R=40ms for
- 48 Vdc
- 110 Vdc
- 220 Vdc
5A
3A
1A
Operation temperature -10…+55 °C
Protection by enclosure IP21
Environmental conditions
Dimensions (H x W x D) 90 x 140 x 60 mm
This manual suits for next models
1
Table of contents
Other VAMP Protection Device manuals