Vapac VapaNet User manual

These instructions contain operating information and should be left with the unit.
Electro Boiler
Units
Alpha-Numeric Display Module
Operation Manual
Edition 3.1
(For use with Software version 7.4 & subsequent issues)
Installation in countries covered by EC Directives:
This product will meet the requirements of the Low Voltage Safety Directive 73 / 23 EEC and the
EMC Directive 89 / 336 EEC when installed in accordance with the instructions contained in this
manual. Failure to comply with these instructions may invalidate the manufacturer's warranty or
any certificate/declaration of conformance requested to be supplied with the unit.

2
Contents
Introduction 3
Alpha-Numeric Display 3
Non Password Protected Menu Options 4
User Level Password “4602” 8
Service Engineer Level Password “5699” 12

3
Fig. 1
Fig. 1A
Introduction
Alpha-Numeric Display
F1 Accept
Line 2 option
F2 Accept
Line 3 option
F3 Accept
Line 4 option
Escape Key
Left/Up/Down/Right
Arrow Keys
Figure 1 above shows the Alphanumeric keypad
and display. This gives four lines of information,
with each line having a maximum of twenty
characters. The Arrow keys are used to navigate
through the menus and the round buttons, on
the right hand side, are used to action the
associated options :
In the menu tree the up/down arrow keys are
used to navigate through the menu’s one option
at a time (NB pressing the down arrow in the
example above will take you to the “Status” line
& the up arrow to the “Setup” line. Pressing F1
or F3 will move up or down three lines at a time
[page up or page down]. F2 will take you to the
“Logon” screen. Pressing the “Escape” key at
any time will move you bake one level in the
menu, repeated presses will take you back to
the default screen shown in Fig. 1.
Fig 1A shows the “unit status” menu tree screen.
From here it is possible to view the status of the
unit parameters.
If you report a fault to Vapac Humidity Control
Ltd, you may be asked to provide this
information to enable the problem to be
diagnosed.

4
Non Password Protected Menu Options
1-1 Languages Used to select the displayed language:
Languages available:
Software – M1 GB; CZ; NL; F; D; GR; I; PL; P; E.
Software – M2 GB; DK; F; D; IS; N; FIN; S.
1-2 Attach to unit Used to link the display to the motherboard, Select this option, then confirm
by pressing “ok”, then press the “network pin” on the motherboard. This is
already done if the display is factory fitted, but will need to be done if either
PCB is changed, or if the display is “field fitted”.
1-3 Factory Setup This option should only be used by Engineers from Vapac Humidity Control
Ltd. It is password protected and used to set the number of electrodes and
number of times the electrode cable passes through the toroid
1-4 Setup unit This option is used to set the site controlled parameters:
Control type: (0-5V; 0-10V; 2-10V; 1-18V; 0-20V; 4-20mA; Pot; Full output;
Network; or Sensing Head [0-5V; 0-10V; 0-20V; 4-20mA or pot].
Voltage: (115; 200; 230; 380; 400; 415; 440; 460; 480; 600V)
1-5 Network Setup Used to set-up master/slave systems: Password protected (Password
1111). Select this option (from the master unit), confirm by pressing “ok”
then press the service pin (this is referred to as the network button in the
operating manual) on the motherboard that is fitted to the first slave unit
(please ensure that this is the next largest unit). What while the slave unit is
“configured” then press “ok” to finish the network set-up or proceed to the
next slave unit and press its service pin. Once all the units are configured
press “ok” to confirm that the set-up is complete.
1-6 Not available at this level This item will not be displayed the next available menu item being displayed
will be 1.7
1-7 Reset display Used to re-synchronize the information between the motherboard and
display
2 Logon Used to gain access to protected menu trees. Passwords are entered via
the arrow keys. Digits are incremented or decremented using the up/down
arrows and digit being entered changed using the left/right arrows. Once
the correct password is displayed it must be entered by pressing “ok”.
These levels are described later in the manual.
LE 7.4 1
Lo
g
on
Setup
LE 7.3 2
Setup
Status
Logon

5
3-1 Master Vapac Used to select the “master” Vapac status parameters to be displayed
3-1-1 Unit Used to select “unit” parameters.
3-1-2 Cylinder 1 Used to select “cylinder 1” parameters.
3-1-3 Cylinder 2 (if fitted) Used to select “cylinder 2” parameters (this option will only be displayed if
the “master unit has two cylinders).
3-2 Slave Vapac 1 (if fitted) Used to select the first slave Vapac (this will only be displayed if there is a
slave unit on the system) in which case 3-2-1 will again be “unit” properties
and 3-2-2 “cylinder 1 “ properties etc…. NB if additional slaves are fitted 3-3
(slave 2) and 3-4 (slave 3) etc will be displayed if necessary.
3-1-1-1 State Displays the operational state of the unit either “Shutdown” (“switched off”;
“EPO/security circuit” open circuit or no 24 Vac supply to PCB); “Stand by”
(unit awaiting control signal demand) or “On” (unit operating – if the unit is
on it will also display the percentage demand i.e On/50% means the unit
has a demand level of 50%.
3-1-1-2 Demand Displays the unit demand level as a percentage.
3-1-1-3 Temperature This displays the space temperature (it will only be displayed if a thermistor
is connected to control terminals 1 & 2.
3-1-1-4 Rel Humidity This displays the space RH as a percentage it will only be displayed if a
sensing head is used to control the unit.
3-1-1-5 System Power Input This will display the actual power being supplied to the unit (kW/h)
3-1-1-6 Power Used Displays the total power used by the unit (kW.h)
3-1-1-7 Steam Output Displays the actual steam output.
3-1-1-8 Sys Steam Output Displays the total steam output of the system – only visible on Master/Slave
systems
3-1-1-9 Hours Run This will display the total number of hours the unit has been operating for.
3-1-1-10 Analogue Inputs This displays each of the four analogue inputs (Ai1 – AI4) as a 4 digit
number
3-1-1-11 Resistive Inputs This displays each of the 4 resistive inputs (AI5 – AI8) as a 4 digit number
3-1-1-12 Digital I/O This will display each of the 9 Digital Inputs (DI1-9) and the 24 V input as a
row of 10 binary digits (0 or 1) above another similar row representing the
10 Digital Outputs (DO1-10). This can be used to ascertain if any input or
output is made, and is useful in diagnosing any problem
3-1-1-13 Device Info This displays current and historic information relating to the health of the
controller hardware. This information can be used in diagnosing any
problem
3-1-1-14 Network Status This displays information on the errors and good messages seen by the
controller and the display. This information can be used to check the health
of the network
LE 7.4 3
Logon
Inf
o
Status

6
4-1 Master Vapac Used to select the “master” Vapac status parameters to be displayed
4-1-1 Unit Used to select “unit” parameters.
4-1-2 Cylinder 1 Used to select “cylinder 1” parameters.
4-1-3 Cylinder 2 (if fitted) Used to select “cylinder 2” parameters (this option will only be displayed if
the “master unit has two cylinders).
4-2 Slave Vapac 1 (if fitted) Used to select the first slave Vapac (this will only be displayed if there is a
slave unit on the system) in which case 3-2-1 will again be “unit” properties
and 3-2-2 “cylinder 1 “ properties etc…. NB if additional slaves are fitted 3-3
(slave 2) and 3-4 (slave 3) etc will be displayed if necessary.
4-1-1-1 Unit capacity Displays the maximum steam output of the unit, in addition to if the unit is
derated either via UCP1 or `Rated Output’
3-1-1-15 Master/Slave This displays information on the operation of master/slave systems. It can
be used to verify and/or diagnose master/slave operation
3-1-2-1 Mode Displays the cylinder mode (Shutdown/Standby/Online/Manual drain in
progress/complete)
3-1-2-2 Demand Displays the cylinder demand (for single cylinder units this will equal unit
demand
3-1-2-3 Not available at this level This option will not be displayed the next available menu item being
displayed will be 3-1-2-4)
3-1-2-4 Hours run Displays the total number of hour that the cylinder has been on line. (this
can be reset at Service engineer’s level)
3-1-2-5 Steam output Displays the actual steam output of the cylinder
3-1-2-6 Current Displays the unit demand level as a percentage.
3-1-2-7 Max current Displays the normal maximum current that will flow in the cylinder at full
output.
3-1-2-8 Actual Voltage Displays the actual voltage being applied to the electrodes control the unit.
3-1-2-9 Power Input Displays the actual input power to the cylinder
3-1-2-10 Consumption Displays the average power consumed by the cylinder
3-1-2-11 Total Power Used Displays the total power consumed by the cylinder
3-1-2-12 Fault Totals Displays the total number of faults that have occurred on the cylinder
3-1-2-13 Demand Runhours
(Version 7.4.2 controller) Displays the run hours for 4 bands of cylinder demand
3-1-3-1 to 3-1-3-15 Cylinder status repeated for cylinder 2 if applicable
3-2-1 to 3-10-3-13 Unit & cylinder status repeated for slave units 1 to 9 (depending on the
network configuration
LE 7.4 4
Status
Info

7
4-1-1-2 Not available at this
level This item will not be displayed the next available menu item being displayed
will be 4-1-1-3
4-1-1-3 Rated Output Displays the maximum operating capacity of the unit (which may be less
than the unit capacity up to 50% by fitting an alternative value UCP1)
4-1-1-4 Unit Type Displays the unit type i.e. “LE” or “LEP”
4-1-1-5 SW Version Displays the software version fitted in the control PCB
4-1-1-6 Nominal Voltage Displays the nominal supply voltage – as set during the initial unit “setup “.
4-1-1-7 Num Electrodes Displays the number of electrodes fitted to each cylinder.
4-1-1-8 Num of turns Displays the number of times the electrode cable passes through the
current sensing transformer or “toroid “
4-1-1-9 Steam Units Displays whether the steam output is measured in kg/h or lbs/h
4-1-1-10 Control Input Displays the selected control signal – set during initial unit “setup”
4-1-1-11 Slaves Attached Displays the number of slave units attached to the network
4-1-1-12 Num Cylinders Displays the total number of cylinders attached to the system or network
4-1-1-13 VOS Algorithm Displays the selected algorithm which is used by Vapac Operating System
either “VOS 4” or “VOS 6” the standard setting is “VOS 6”
4-1-1-14 Water Economy Displays whether water economy is “enabled” or “disabled”
4-1-2-1 Cyl Capacity Displays the maximum amount of steam that the cylinder is designed to
produce
4-1-2-2 Cylinder Type Displays whether the cylinder is “LE” or “LEP”. i.e. if the cylinder power is
modulated by SSR’s (close control) or not (comfort control)
4-1-2-3 Period drain int Displays the time interval between periodic drains – “0” indicates that
periodic drains have not been selected. Periodic drains can be set to
completely drain the cylinder at timed intervals which can assist unit
operation under certain conditions
4-1-2-4 Drain options Displays whether the unit is set to stop or resume automatic operation once
the periodic drain cycle is complete
4-1-2-5 Period flush int Displays the time interval between periodic flushes – “0” again indicates
that periodic flushes have not been selected. Periodic flushes can be set to
completely drain the cylinder then re-fill with fresh water and finally drain the
cylinder again to flush the cylinder at timed intervals. This can again assist
unit operation under certain conditions
4-1-2-6 Flush options Displays whether the unit is set to stop or resume automatic operation once
the periodic flush cycle is complete
4-1-3-1 to 4-1-3-6 The cylinder information options are repeated for cylinder 2 (if fitted)
4-2 to 4-9-3-6 The unit and cylinder information options are repeated for slave units 1 to 9
if fitted to the system. NB the maximum number of cylinders on any system
is 10

8
Password Protected Menu Options
User Level Password “4602”
2 Logon Used to gain access to protected menu trees. Passwords are entered via
the arrow keys. Digits are incremented or decremented using the up/down
arrows and digit being entered changed using the left/right arrows. Once
the correct password is displayed it must be entered by pressing “ok”.
These levels are described later in the manual.
1-1 Languages Used to select the displayed language:
Languages available:
Software – M1 GB; CZ; NL; F; D; GR; I; PL; P; E.
Software – M2 GB; DK; F; D; IS; N; FIN; S.
1-2 Attach to unit Used to link the display to the motherboard, Select this option, then confirm
by pressing “ok”, then press the “network pin” on the motherboard. This is
already done if the display is factory fitted, but will need to be done if either
PCB is changed, or if the display is “field fitted”.
1-3 Factory Setup This option should only be used by Engineers from Vapac Humidity Control
Ltd. It is password protected and used to set the number of electrodes and
number of times the electrode cable passes through the toroid
1-4 Setup unit This option is used to set the site controlled parameters:
Control type: (0-5V; 0-10V; 2-10V; 1-18V; 0-20V; 4-20mA; Pot; Full output;
Network; or Sensing Head [0-5V; 0-10V; 0-20V; 4-20mA or pot].
Voltage: (115; 200; 230; 380; 400; 415; 440; 460; 480; 600V)
1-5 Network Setup Used to set-up master/slave systems: Password protected (Password
1111). Select this option (from the master unit), confirm by pressing “ok”
then press the service pin (this is referred to as the network button in the
operating manual) on the motherboard that is fitted to the first slave unit
(please ensure that this is the next largest unit). What while the slave unit is
“configured” then press “ok” to finish the network set-up or proceed to the
next slave unit and press its service pin. Once all the units are configured
press “ok” to confirm that the set-up is complete.
1-6 Not available at this level This item will not be displayed the next available menu item being displayed
will be 1.7
1-7 Reset display Used to re-synchronize the information between the motherboard and
display
LE 7.4 1
Lo
g
on
Setup
LE 7.3 2
Setup
Status
Logon

9
3-1 Master Vapac Used to select the “master” Vapac status parameters to be displayed
3-1-1 Unit Used to select “unit” parameters.
3-1-2 Cylinder 1 Used to select “cylinder 1” parameters.
3-1-3 Cylinder 2 (if fitted) Used to select “cylinder 2” parameters (this option will only be displayed if
the “master unit has two cylinders).
3-2 Slave Vapac 1 (if fitted) Used to select the first slave Vapac (this will only be displayed if there is a
slave unit on the system) in which case 3-2-1 will again be “unit” properties
and 3-2-2 “cylinder 1 “ properties etc…. NB if additional slaves are fitted 3-3
(slave 2) and 3-4 (slave 3) etc will be displayed if necessary.
3-1-1-1 State Displays the operational state of the unit either “Shutdown” (“switched off”;
“EPO/security circuit” open circuit or no 24 Vac supply to PCB); “Stand by”
(unit awaiting control signal demand) or “On” (unit operating – if the unit is
on it will also display the percentage demand i.e On/50% means the unit
has a demand level of 50%.
3-1-1-2 Demand Displays the unit demand level as a percentage.
3-1-1-3 Temperature This displays the space temperature (it will only be displayed if a thermistor
is connected to control terminals 1 & 2.
3-1-1-4 Rel Humidity This displays the space RH as a percentage it will only be displayed if a
sensing head is used to control the unit.
3-1-1-5 System Power Input This will display the actual power being supplied to the unit (kW/h)
3-1-1-6 Power Used Displays the total power used by the unit (kW.h)
3-1-1-7 Steam Output Displays the actual steam output.
3-1-1-8 Sys Steam Output Displays the total steam output of the system – only visible on Master/Slave
systems
3-1-1-9 Hours Run This will display the total number of hours the unit has been operating for.
3-1-1-10 Analogue Inputs This displays each of the four analogue inputs (Ai1 – AI4) as a 4 digit
number
3-1-1-11 Resistive Inputs This displays each of the 4 resistive inputs (AI5 – AI8) as a 4 digit number
3-1-1-12 Digital I/O This will display each of the 9 Digital Inputs (DI1-9) and the 24 V input as a
row of 10 binary digits (0 or 1) above another similar row representing the
10 Digital Outputs (DO1-10). This can be used to ascertain if any input or
output is made, and is useful in diagnosing any problem
3-1-1-13 Device Info This displays current and historic information relating to the health of the
controller hardware. This information can be used in diagnosing any
problem
3-1-1-14 Network Status This displays information on the errors and good messages seen by the
controller and the display. This information can be used to check the health
of the network
LE 7.4 3
Logon
Inf
o
Status

10
3-1-1-15 Master/Slave This displays information on the operation of master/slave systems. It can
be used to verify and/or diagnose master/slave operation
3-1-2-1 Mode Displays the cylinder mode (Shutdown/Standby/Online/Manual drain in
progress/complete)
3-1-2-2 Demand Displays the cylinder demand (for single cylinder units this will equal unit
demand
3-1-2-3 Not available at this level This option will not be displayed the next available menu item being
displayed will be 3-1-2-4)
3-1-2-4 Hours run Displays the total number of hour that the cylinder has been on line. (this
can be reset at Service engineer’s level)
3-1-2-5 Steam output Displays the actual steam output of the cylinder
3-1-2-6 Current Displays the unit demand level as a percentage.
3-1-2-7 Max current Displays the normal maximum current that will flow in the cylinder at full
output.
3-1-2-8 Actual Voltage Displays the actual voltage being applied to the electrodes control the unit.
3-1-2-9 Power Input Displays the actual input power to the cylinder
3-1-2-10 Consumption Displays the average power consumed by the cylinder
3-1-2-11 Total Power Used Displays the total power consumed by the cylinder
3-1-2-12 Fault Totals Displays the total number of faults that have occurred on the cylinder
3-1-2-13 Demand Runhours
(Version 7.4.2 controller) Displays the run hours for 4 bands of cylinder demand
3-1-3-1 to 3-1-3-15 Cylinder status repeated for cylinder 2 if applicable
3-2-1 to 3-10-3-13 Unit & cylinder status repeated for slave units 1 to 9 (depending on the
network configuration
4-1 Master Vapac Used to select the “master” Vapac status parameters to be displayed
4-1-1 Unit Used to select “unit” parameters.
4-1-2 Cylinder 1 Used to select “cylinder 1” parameters.
4-1-3 Cylinder 2 (if fitted) Used to select “cylinder 2” parameters (this option will only be displayed if
the “master unit has two cylinders).
4-2 Slave Vapac 1 (if fitted) Used to select the first slave Vapac (this will only be displayed if there is a
slave unit on the system) in which case 3-2-1 will again be “unit” properties
and 3-2-2 “cylinder 1 “ properties etc…. NB if additional slaves are fitted 3-3
(slave 2) and 3-4 (slave 3) etc will be displayed if necessary.
LE 7.4 4
Status
Info

11
4-1-1-1 Unit capacity Displays the maximum steam output of the unit, in addition to if the unit is
derated either via UCP1 or `Rated Output’
4-1-1-2 Not available at this
level This item will not be displayed the next available menu item being displayed
will be 4-1-1-3
4-1-1-3 Rated Output Displays the maximum operating capacity of the unit (which may be less
than the unit capacity up to 50% by fitting an alternative value UCP1)
4-1-1-4 Unit Type Displays the unit type i.e. “LE” or “LEP”
4-1-1-5 SW Version Displays the software version fitted in the control PCB
4-1-1-6 Nominal Voltage Displays the nominal supply voltage – as set during the initial unit “setup “.
4-1-1-7 Num Electrodes Displays the number of electrodes fitted to each cylinder.
4-1-1-8 Num of turns Displays the number of times the electrode cable passes through the
current sensing transformer or “toroid “
4-1-1-9 Steam Units Displays whether the steam output is measured in kg/h or lbs/h
4-1-1-10 Control Input Displays the selected control signal – set during initial unit “setup”
4-1-1-11 Slaves Attached Displays the number of slave units attached to the network
4-1-1-12 Num Cylinders Displays the total number of cylinders attached to the system or network
4-1-1-13 VOS Algorithm Displays the selected algorithm which is used by Vapac Operating System
either “VOS 4” or “VOS 6” the standard setting is “VOS 6”
4-1-1-14 Water Economy Displays whether water economy is “enabled” or “disabled”
4-1-2-1 Cyl Capacity Displays the maximum amount of steam that the cylinder is designed to
produce
4-1-2-2 Cylinder Type Displays whether the cylinder is “LE” or “LEP”. i.e. if the cylinder power is
modulated by SSR’s (close control) or not (comfort control)
4-1-2-3 Period drain int Displays the time interval between periodic drains – “0” indicates that
periodic drains have not been selected. Periodic drains can be set to
completely drain the cylinder at timed intervals which can assist unit
operation under certain conditions
4-1-2-4 Drain options Displays whether the unit is set to stop or resume automatic operation once
the periodic drain cycle is complete
4-1-2-5 Period flush int Displays the time interval between periodic flushes – “0” again indicates
that periodic flushes have not been selected. Periodic flushes can be set to
completely drain the cylinder then re-fill with fresh water and finally drain the
cylinder again to flush the cylinder at timed intervals. This can again assist
unit operation under certain conditions
4-1-2-6 Flush options Displays whether the unit is set to stop or resume automatic operation once
the periodic flush cycle is complete
4-1-3-1 to 4-1-3-6 The cylinder information options are repeated for cylinder 2 (if fitted)
4-2 to 4-9-3-6 The unit and cylinder information options are repeated for slave units 1 to 9
if fitted to the system. NB the maximum number of cylinders on any system
is 10

12
Password Protected Menu Options
Service Engineer Level Password “5699”
1-1 Languages Used to select the displayed language:
Languages available:
Software – M1 GB; CZ; NL; F; D; GR; I; PL; P; E.
Software – M2 GB; DK; F; D; IS; N; FIN; S.
1-2 Attach to unit Used to link the display to the motherboard, Select this option, then confirm
by pressing “ok”, then press the “network pin” on the motherboard. This is
already done if the display is factory fitted, but will need to be done if either
PCB is changed, or if the display is “field fitted”.
1-3 Factory Setup This option should only be used by Engineers from Vapac Humidity Control
Ltd. It is password protected and used to set the number of electrodes and
number of times the electrode cable passes through the toroid
1-4 Setup unit This option is used to set the site controlled parameters:
Control type: (0-5V; 0-10V; 2-10V; 1-18V; 0-20V; 4-20mA; Pot; Full output;
Network; or Sensing Head [0-5V; 0-10V; 0-20V; 4-20mA or pot].
Voltage: (115; 200; 230; 380; 400; 415; 440; 460; 480; 600V)
1-5 Network Setup Used to set-up master/slave systems: Password protected (Password
1111). Select this option (from the master unit), confirm by pressing “ok”
then press the service pin (this is referred to as the network button in the
operating manual) on the motherboard that is fitted to the first slave unit
(please ensure that this is the next largest unit). What while the slave unit is
“configured” then press “ok” to finish the network set-up or proceed to the
next slave unit and press its service pin. Once all the units are configured
press “ok” to confirm that the set-up is complete.
1-6 Not available at this level This item will not be displayed the next available menu item being displayed
will be 1.7
1-7 Reset display Used to re-synchronize the information between the motherboard and
display
2 Logon Used to gain access to protected menu trees. Passwords are entered via
the arrow keys. Digits are incremented or decremented using the up/down
arrows and digit being entered changed using the left/right arrows. Once
the correct password is displayed it must be entered by pressing “ok”.
These levels are described later in the manual.
LE 7.4 1
Lo
g
on
Setup
LE 7.3 2
Setup
Status
Logon

13
3-1 Master Vapac Used to select the “master” Vapac status parameters to be displayed
3-1-1 Unit Used to select “unit” parameters.
3-1-2 Cylinder 1 Used to select “cylinder 1” parameters.
3-1-3 Cylinder 2 (if fitted) Used to select “cylinder 2” parameters (this option will only be displayed if
the “master unit has two cylinders).
3-2 Slave Vapac 1 (if fitted) Used to select the first slave Vapac (this will only be displayed if there is a
slave unit on the system) in which case 3-2-1 will again be “unit” properties
and 3-2-2 “cylinder 1 “ properties etc…. NB if additional slaves are fitted 3-3
(slave 2) and 3-4 (slave 3) etc will be displayed if necessary.
3-1-1-1 State Displays the operational state of the unit either “Shutdown” (“switched off”;
“EPO/security circuit” open circuit or no 24 Vac supply to PCB); “Stand by”
(unit awaiting control signal demand) or “On” (unit operating – if the unit is
on it will also display the percentage demand i.e On/50% means the unit
has a demand level of 50%.
3-1-1-2 Demand Displays the unit demand level as a percentage.
3-1-1-3 Temperature This displays the space temperature (it will only be displayed if a thermistor
is connected to control terminals 1 & 2.
3-1-1-4 Rel Humidity This displays the space RH as a percentage it will only be displayed if a
sensing head is used to control the unit.
3-1-1-5 System Power Input This will display the actual power being supplied to the unit (kW/h)
3-1-1-6 Power Used Displays the total power used by the unit (kW.h)
3-1-1-7 Steam Output Displays the actual steam output.
3-1-1-8 Sys Steam Output Displays the total steam output of the system – only visible on Master/Slave
systems
3-1-1-9 Hours Run This will display the total number of hours the unit has been operating for.
3-1-1-10 Analogue Inputs This displays each of the four analogue inputs (Ai1 – AI4) as a 4 digit
number
3-1-1-11 Resistive Inputs This displays each of the 4 resistive inputs (AI5 – AI8) as a 4 digit number
3-1-1-12 Digital I/O This will display each of the 9 Digital Inputs (DI1-9) and the 24 V input as a
row of 10 binary digits (0 or 1) above another similar row representing the
10 Digital Outputs (DO1-10). This can be used to ascertain if any input or
output is made, and is useful in diagnosing any problem
3-1-1-13 Device Info This displays current and historic information relating to the health of the
controller hardware. This information can be used in diagnosing any
problem
3-1-1-14 Network Status This displays information on the errors and good messages seen by the
controller and the display. This information can be used to check the health
of the network
LE 7.4 3
Logon
Info
Status

14
3-1-1-15 Master/Slave This displays information on the operation of master/slave systems. It can
be used to verify and/or diagnose master/slave operation
3-1-2-1 Mode Displays the cylinder mode (Shutdown/Standby/Online/Manual drain in
progress/complete)
3-1-2-2 Demand Displays the cylinder demand (for single cylinder units this will equal unit
demand
3-1-2-3 Cylinder Data Displays cylinder data i.e.
Top Line: D=Demand%; F=Feed to current%;
Mid Line: A=Actual current%; B=Boil to current%;
Additional information may be requested by VHCL to assist in fault
diagnosis.
3-1-2-4 Hours run Displays the total number of hour that the cylinder has been on line. (this
can be reset at Service engineer’s level)
3-1-2-5 Steam output Displays the actual steam output of the cylinder
3-1-2-6 Current Displays the unit demand level as a percentage.
3-1-2-7 Max current Displays the normal maximum current that will flow in the cylinder at full
output.
3-1-2-8 Actual Voltage Displays the actual voltage being applied to the electrodes control the unit.
3-1-2-9 Power Input Displays the actual input power to the cylinder
3-1-2-10 Consumption Displays the average power consumed by the cylinder
3-1-2-11 Total Power Used Displays the total power consumed by the cylinder
3-1-2-12 Fault Totals Displays the total number of faults that have occurred on the cylinder
3-1-2-13 Demand Runhours
(Version 7.4.2 controller) Displays the run hours for 4 bands of cylinder demand
3-1-3-1 to 3-1-3-15 Cylinder status repeated for cylinder 2 if applicable
3-2-1 to 3-10-3-13 Unit & cylinder status repeated for slave units 1 to 9 (depending on the
network configuration
4-1 Master Vapac Used to select the “master” Vapac status parameters to be displayed
4-1-1 Unit Used to select “unit” parameters.
4-1-2 Cylinder 1 Used to select “cylinder 1” parameters.
4-1-3 Cylinder 2 (if fitted) Used to select “cylinder 2” parameters (this option will only be displayed if
the “master unit has two cylinders).
4-2 Slave Vapac 1 (if fitted) Used to select the first slave Vapac (this will only be displayed if there is a
slave unit on the system) in which case 3-2-1 will again be “unit” properties
and 3-2-2 “cylinder 1 “ properties etc…. NB if additional slaves are fitted 3-3
(slave 2) and 3-4 (slave 3) etc will be displayed if necessary.
LE 7.4 4
Status
Info

15
4-1-1-1 Unit capacity Displays the maximum steam output of the unit, in addition to if the unit is
derated either via UCP1 or `Rated Output’
4-1-1-2 Not available at this
level This item will not be displayed the next available menu item being displayed
will be 4-1-1-3
4-1-1-3 Rated Output Displays the maximum operating capacity of the unit (which may be less
than the unit capacity up to 50% by fitting an alternative value UCP1)
4-1-1-4 Unit Type Displays the unit type i.e. “LE” or “LEP”
4-1-1-5 SW Version Displays the software version fitted in the control PCB
4-1-1-6 Nominal Voltage Displays the nominal supply voltage – as set during the initial unit “setup “.
4-1-1-7 Num Electrodes Displays the number of electrodes fitted to each cylinder.
4-1-1-8 Num of turns Displays the number of times the electrode cable passes through the
current sensing transformer or “toroid “
4-1-1-9 Steam Units Displays whether the steam output is measured in kg/h or lbs/h
4-1-1-10 Control Input Displays the selected control signal – set during initial unit “setup”
4-1-1-11 Slaves Attached Displays the number of slave units attached to the network
4-1-1-12 Num Cylinders Displays the total number of cylinders attached to the system or network
4-1-1-13 VOS Algorithm Displays the selected algorithm which is used by Vapac Operating System
either “VOS 4” or “VOS 6” the standard setting is “VOS 6”
4-1-1-14 Water Economy Displays whether water economy is “enabled” or “disabled”
4-1-2-1 Cyl Capacity Displays the maximum amount of steam that the cylinder is designed to
produce
4-1-2-2 Cylinder Type Displays whether the cylinder is “LE” or “LEP”. i.e. if the cylinder power is
modulated by SSR’s (close control) or not (comfort control)
4-1-2-3 Period drain int Displays the time interval between periodic drains – “0” indicates that
periodic drains have not been selected. Periodic drains can be set to
completely drain the cylinder at timed intervals which can assist unit
operation under certain conditions
4-1-2-4 Drain options Displays whether the unit is set to stop or resume automatic operation once
the periodic drain cycle is complete
4-1-2-5 Period flush int Displays the time interval between periodic flushes – “0” again indicates
that periodic flushes have not been selected. Periodic flushes can be set to
completely drain the cylinder then re-fill with fresh water and finally drain the
cylinder again to flush the cylinder at timed intervals. This can again assist
unit operation under certain conditions
4-1-2-6 Flush options Displays whether the unit is set to stop or resume automatic operation once
the periodic flush cycle is complete
4-1-3-1 to 4-1-3-6 The cylinder information options are repeated for cylinder 2 (if fitted)
4-2 to 4-9-3-6 The unit and cylinder information options are repeated for slave units 1 to 9
if fitted to the system. NB the maximum number of cylinders on any system
is 10

16
NB The adjust menu will only appear at the “Service Engineer” Level if a
“Sensing Head” is used as the control signal, as the only adjustments
available at this level are associated with “Sensing Head” control.
5-1 Master Vapac Selects the master vapac adjust parameters
5-1-1 Unit Selects the “unit” parameters.
5-1-1-1 Set point Selects the “set point”, use the up/down keys to adjust the controller set
point up or down
5-1-1-2 Prop band Selects the “proportional band”, use the arrow keys to set the
proportional band that is appropriate for the site control system
5-1-1-3 RH Offset Selects RH Offset, allows the displayed “Space RH” & controller set-point
to be “offset” to “calibrate” the sensing head to external monitoring
equipment
6-1 Master Vapac Selects the master vapac adjust parameters
6-1-1 Unit Allows the “Unit” to be serviced..
6-1-2 Cylinder 1 Allows the “Cylinder 1” to be serviced
6-1-3 Cylinder 2 Allows cylinder 2 (if fitted) to be serviced
6-1-1-1 Constant Output Allows the unit to be run at an (adjustable) preset level independently
from the control signal
6-1-1-2 Quick Start Allows the unit to get up to duty quicker by running at 100% demand until
the cylinder has reached full current
6-1-1-3 Run Output Allows the run relay to be switched “manually”, to check external wiring to
the remote indications
6-1-1-4 Fault Output Allows the fault relay to be switched “manually”, to check external wiring
to the remote indications
6-1-1-5 Not available at this level This item will not be displayed the next available menu item being
displayed will be 6.1.1.7
6-1-1-6 Not available at this level This item will not be displayed the next available menu item being
displayed will be 6.1.1.7
LE 7.4 5
Info
Adjust
LE 7.4 6
Adjust
Service

17
6-1-1-7 Store Runtimes Commits the current run hours to FLASH memory.
6-1-2-1 Const Output Allows the cylinder to be run at an (adjustable) preset level independently
from the control signal
6-1-2-2 Manual Drain Instigates a drain, as if holding down the manual drain switch, it can be
used to prove the automatic drain is functioning or to drain the cylinder
without holding the drain switch down
6-1-2-3 Auto Flush Instigates an automatic flush, where the cylinder is filled with water and
then fully drained a number of times. This is particularly useful when
initially commissioning a unit which has a long run of new copper pipe in
the feed supply, to “flush any impurities / flux from the water supply
6-1-2-4 Reset Run Hours This re-sets the cylinder hours run to zero – usually done when the
cylinder is changed
6-1-2-5 Manual Control When this option is selected, automatic control of the feed valve and
drain pump is suspended, allowing the following two options to be used
6-1-2-6 Feed Valve This allows the feed valve to be manually switched “on” & “off” to prove
the feed valve is operating correctly
6-1-2-7 Drain Pump This allows the drain pump to be manually switched “on” & “off” to prove
the drain pump is operating correctly
6-1-3-1 to 6-1-3-7 The above cylinder options are repeated for cylinder 2 (if fitted)
6-2 to 6-9-3 The above service options are repeated for slave units 1 to 9 (if
applicable)
7-1 Master Vapac Selects the master vapac adjust parameters
7-1-1 Unit Selects the “unit” parameters.
7-1-1-1 Fault Output Allows the “fault” alarm signal to be set to either “Continuous” or
“Pulsed.
7-1-1-2 Fault run scope Allows the run & fault alarms to show either the “Master” or “Network”
status. This defaults to “Network” as standard. i.e. the run signal will
show if the network is operating and the fault indication will be made if
any of the slaves are in a fault condition
7-1-1-3 to
7-1-1-29 Not available at this level These items will not be displayed the next available menu item being
displayed will be 7.1.1.30
7-1-1-30 Cyl Min Run Specifies the minimum period of time that a cylinder will run
7-1-1-31 Cyl Hold On Specifies the period of time a cylinder will continue to run after the
demand signal has been removed.
LE 7.4 7
Service
Engineering

Vapac Humidity Control Ltd reserve the right to change the design or specification
Of the equipment described in this manual without prior notice
Made in England by:
Vapac Humidity Control Ltd.
Printed in Great Britain.
April 2007.
Table of contents
Popular Boiler Supplies manuals by other brands

oventrop
oventrop Regumat-180 plus Installation and operating instructions for the specialised installer

NTI
NTI FTV110C instructions

QHT
QHT Direct Vent DVF-4 Rigid installation manual

Vaillant
Vaillant 0020230734 operating instructions

Immergas
Immergas 3.031186 Instruction and warning book

eta
eta eHACK operating instructions