ALFA(NET) 51 PI -50/+50°C Doc.no.: 180142
version 1.1
Pagina 4 van 8
12 Setting internal parameters
Next to the adjustment of the setpoint, internal settings can be made like differential, sensor offset,
setpoint range and the functions of the thermostat.
Push the DOWN key for more than 10 seconds, to enter the 'Internal Programming Menu'. In the left
display the upper- and lower-segment are blinking.
With the UP and DOWN keys the required parameter can be selected (see the parameter table).
If the required parameter is selected, the value can be read-out by pushing the SET key. Pushing the
UP or DOWN key to change the value of this parameter.
If after 20 seconds no key is pushed, the ALFA(NET) 51 PI changes to the normal operation mode.
12.1 Parameters ALFA(NET) 51 PI
Para-
meter
Description Parameter Range Default
value
01 Function Relay 1 1 = Cool
2 = Heat
3 = Alarm
1..3 1
02 Function Relay 2 same as parm. P01 1..3 2
03 Function Relay 3 same as parm. P01 1..3 3
04 Function PI-output 1 = Cool
2 = Heat
3 = Cool and Heat
1..3 1
05 Offset temperature sensor (Calibration) -15 .. +15.0°C 0.0
06 Offset PI -15 .. +15.0°C 0.0
07 P-band setting 0.0 .. 20.0°C 5.0
08 I-time setting (I-action not active at
P08 = 0 of P04 = 3)
0 .. 99 Minutes 0 (= off)
10 Switch-on stage two 0 = Temp, 1 = Time 0
11 Switch-on stage three 0 = Temp, 1 =Time 0
12 Switch-on delay stage two 0 .. 99 Minutes 0
13 Switch-on delay stage three 0 .. 99 Minutes 0
14 Switching differential relay 1 * 0.1 .. 15.0°C 0.5
15 Switching offset relay 1 * -15.0 .. +15.0°C 0.0
16 Switching differential relay 2 * 0.1 .. 15.0°C 0.5
17 Switching offset relay 2 * -15 .. +15.0°C 0.0
18 Switching differential relay 3 * 0.1 .. 15.0°C 0.5
19 Switching offset relay 3 * -15 .. +15.0°C 0.0
20 Switch-on delay cooling 0 .. 99 0
21 Switch-off delay cooling 0 .. 99 0
22 Parameter 20/21 in seconds or minutes 0 = Sec, 1=Min 0
23 Minimum on-time cooling 0 .. 99 Minutes 0
24 Minimum off-time cooling 0 .. 99 Minutes 0
25 Minimum adjustable setpoint -50 .. +50.0°C -50.0
26 Maximum adjustable setpoint -50 .. +50.0°C +50.0
27 Readout in whole degrees 0 = No, 1 =Yes 0