Vector SC-T Series User manual

Contact Temperature Sensor SC-T
Contact Temperature Sensor SC-T
Contact Temperature Sensor SC-T
Doc: 70-00-0215A, V1.0, 20140722 © 2012-2014 Vector Controls GmbH, Switzerland Subject to alteration
www.vectorcontrols.com
SC-T, Flying Lead Contact Temperature Sensor
Features
Thermistors and PT sensing elements to fit your system
Strap-On mounting for pipes or arched surfaces
Simple installation
Wide range of temperature probes
Including 2m (6.5ft) wire
Applications
Measure temperature for heating, ventilation and air conditioning
applications
For heating or cooling mode detection in 2-pipe systems
As frost protection sensor
Temperature sensor
The sensor measures the temperature by use of a glass packed thermistor
with a negative temperature coefficient (NTC), a platinum film (PT) or a nickel
thin layer (NI) based probe. Its resistance changes according to the
temperature. The change follows a specified curve. A summary of such curves
is printed on the back of this document. Contact our sales department for
curves or sensing elements not yet listed below.
Compensating conductor resistance
The length and type of conductors used to connect the sensor to the
measuring electronic influences the accuracy of the measurement. Especially
for elements with low resistance this has to be taken into account.
Compensation needs to be performed by the measurement electronics.
Ordering
Item Name
Probe
Definition
Cable length
SC-Tn3-2
NTC 3kΩ at 25°C (77°F)
B25/50 3935
2m, (6.5ft)
SC-Tn10-2
NTC 10kΩ at 25°C (77°F)
B25/50 3935
SC-Tn11-2
NTC 10kΩ at 25°C (77°F)
B25/50 3630
SC-Tn12-2
NTC 10kΩ at 25°C (77°F)
B25/50 3380
SC-Tn20-2
NTC 20kΩ at 25°C (77°F)
B25/50 4200
SC-Tn100-2
NTC 100kΩ at 25°C (77°F)
B25/50 4200
SC-Tp1-2
PT100
EN60751
SC-Tp2-2
PT1000
EN60751
SC-Tk5-2
NI1000
5000 ppm/K
AMS-2
Tightening strap for ½-3in pipes
AMS-3
Tightening strap for 3-6in pipes
Technical Specification
Warning! This device is intended to be used for comfort applications. Where a
device failure endangers human life and/or property, it is the responsibility of the
owner, designer and installer to add additional safety devices to prevent or detect
a system failure caused by such a device failure. The manufacturer of this device
cannot be held liable for any damage caused by such a failure.
Failure to follow specifications and local regulations may endanger life, cause
equipment damage and void warranty.
Sensing Probe
Thermistor:
Range: (Probe only)
Accuracy:
-40…0°C (-40…32°F):
0…50°C (32…122°F):
50…100°C (122…212°F):
> 100°C (> 212°F):
NTC
-70…150°C (-94…302°F)
0.5 K
0.2 K
0.5 K
1 K
Platinum-Film:
Range: (Probe only)
Accuracy
PT according EN 60751
-70…200°C (-94…392°F)
EN 60751, Class B, ask for other class
Nickel Thin Layer:
Range: (Probe only)
Accuracy
1000 Ωat 0°C, 5000 ppm/K
-60…200°C (-76…392°F)
DIN 43760
Cable
Standard
Size
Insulation material
Operating Temperature
Ratings
2 x 0.20 mm2(AWG 24)
PVC
-40…80°C (-40…176°F)
UL758, 1581/CSA C22.2 No 210.2
High temperature
Size
Insulation material
Operating temperature
Ratings
-H
2 x 0.35 mm2(AWG 22)
FEP
-60...200°C (-76…392°F)
ULR/CSA C22.2 No 210.2
Plenum rated
Size
Insulation material
Operating temperature
Ratings
-P
2 x 0.5 mm2(AWG 20)
Plenum PVC
-20…75°C (-4…167°F)
UL C(UL) PLENUM CMP OR E355847
FPLP UL
Single insulated PVC
Size
Insulation material
Operating Temperature
Ratings
-A
2 x 0.20 mm2(AWG 24)
PVC
-40…80°C (-40…176°F)
UL758,1581 CSA C22.2 No.210.2
Environment
Operation
Climatic conditions
Temperature depends on cable
type
To IEC 721-3-3
class 3K5
See above
Transport & storage
Climatic conditions
Temperature
Humidity
Mechanical conditions
To IEC 721-3-2 and IEC 721-3-1
class 3K3 and class 1K3
-40…80°C (-40…176°F)
< 95% RH non-condensing
class 2M2
Standards
conform according to
EMC Standard 89/336/EEC
EMEI Standard 73/23/EEC
EN 61 000-6-1/ EN 61 000-6-3
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
EN 60 730 –1
EN 60 730 –2 –9
Pollution Class
Normal acc. to EN 60 730,
RoHS compliant
Degree of Protection
IP65 to EN 60 529
Safety Class
III (IEC 60536)
Housing
Probe
Brass
Dimensions (Diameter x L)
Probe: ø 6 x 35 mm (ø 0.25”x 1.4”)
Contact Plate: 20x30mm (0.8” x 1.2”)
Weight (including package)
80g (2.8oz)
Wiring & Installation
Wiring Diagram
Dimensions [mm](in)
Installation
Mount the sensor on a supply or return pipe depending on application.
Make sure the maximum allowed temperature limit is not exceeded.
For better temperature transfer between sensor and medium use heat
conducting paste or heat conducting pads.
If possible place the sensor on the upper side of the pipe to prevent
permeation by condensate.
Bend the wings of the contact sensor to fit to the radius of the pipe.
Place the heat conducting pad or liquid between pipe and sensor and use the
tightening strap to fix the sensor to the pipe. Use moderate torque, do not
crush the sensor.
SC-Tn10-2A
Cable type:
default: PVC cable double insulated
-H = High temperature
-P = Plenum rated
-A = PVC cable single insulated
Cable length in Meter
Sensing Element (see below)
Sensor Type: Sensor with flying lead
20
(0.8)
35 (1.4)
30 (1.2)
6 (0.2)
SC-T
RT
Contact Temperature Sensor SC-T
Contact Temperature Sensor SC-T
Contact Temperature Sensor SC-T
Doc: 70-00-0215A, V1.0, 20140722 © 2012-2014 Vector Controls GmbH, Switzerland Subject to alteration
www.vectorcontrols.com
Resistance Table for Thermistors (NTC)
°C
°F
Tn3 [kΩ]
Tn5 [kΩ]
Tn10 [kΩ]
Tn11 [kΩ]
Tn12 [kΩ]
Tn20 [kΩ]
Tn100 [kΩ]
B25/50
3935
3470
3935
3630
3380
4200
4200
B25/85
3974
3535
3974
3687
3435
4260
4260
B25/100
3988
3526
3988
3715
3455
4285
4285
Signal type 
NTC 3k
NTC 5k
NTC 10k-2
NTC-10k-3
NTC 20k
NTC 100k
-50
-58
201,1
161,9
670,2
441,3
329,2
1711
8558
-40
-40
100,9
89,49
336,4
239,7
188,4
814,0
4095
-30
-22
53,09
54,07
177,0
135,3
111,3
415,6
2077
-20
-4
29,12
33,21
97,08
78,91
67.74
220,6
1105
-10
14
16,60
21,07
55,33
47,54
42.45
122,4
612,4
0
32
9,795
13,73
32,65
29,49
27.28
70,20
351,0
10
50
5,969
9,041
19,90
18,79
17.96
41,56
207,8
20
68
3,747
6,064
12,49
12,26
12.09
25,34
126,7
25
77
3,000
5,000
10,00
10,00
10,00
20,00
100,00
30
86
2,417
4,139
8,057
8,194
8,313
15,88
79,43
40
104
1,598
2,875
5,327
5,592
5,828
10,21
51,06
50
122
1,081
2,032
3,603
3,893
4,161
6,718
33,60
60
140
0,746
1,463
2,488
2,760
3,021
4,518
22,59
70
158
0,525
1,069
1,751
1,990
2,229
3,100
15,50
80
176
0,376
0,792
1,255
1,458
1,669
2,168
10,84
90
194
0,275
0,601
0,915
1,084
1,266
1,542
7,707
100
212
0,203
0,464
0,678
0,817
0,973
1,114
5,571
110
230
0,536
0,354
0,512
0,624
0,752
0,818
4,092
120
248
0,123
0,272
0,410
0,481
0,605
0,609
3,046
130
266
0,097
0,212
0,322
0,380
0,487
0,460
2,298
140
284
0,077
0,169
0,257
0,300
0,395
0,351
1,755
150
302
0,063
0,137
0,210
0,240
0,325
0,271
1,356
Resistance Table for Platinum Film and NI1000 Elements
°C
°F
Tp1 [Ω]
Tp2 [Ω]
Tk5 [Ω]
Tk6 [Ω]
PT100
DIN 60751
PT1000
DIN 60751
NI1000,
K=5000
NI1000
K=6180
-50
-58
80,28
803,0
790,88
742,55
-40
-40
84,27
843,0
830,84
791,31
-30
-22
88,22
882,0
871,69
841,46
-20
-4
92,16
922,0
913,48
892,96
-10
14
96,09
961,0
956,24
945,82
0
32
100,00
1000,0
1000
1000
10
50
103,90
1039,0
1044,79
1055,52
20
68
107,79
1078,0
1090,65
1111,36
30
86
111,67
1117,0
1137,62
1170,56
40
104
115,54
1155,0
1185,71
1230,11
50
122
119,40
1194,0
1234,98
1291,05
60
140
123,24
1232,0
1285,45
1353,40
70
158
127,07
1270,5
1337,15
1417,21
80
176
130,89
1309,0
1390,12
1482,50
90
194
134,70
1347,0
1444,39
1549,34
100
212
138,50
1385,0
1500,00
1617,79
110
230
142,29
1423,0
1556,98
1687,89
120
248
146,06
1460,5
1615,37
1759,72
130
266
149,80
1498,0
1675,19
1833,35
140
284
153,60
1536,0
1736,48
1908,87
150
302
157,30
1573,0
1799,27
1986,35
160
320
161,05
1610,5
1863,60
2065,89
170
338
164,75
1647,5
1929,50
2147,58
180
356
168,45
1684,5
1997,00
2231,53
190
374
172,15
1721,5
2066,15
2317,83
200
392
175,85
1758,5
2136,96
2406,60

This manual suits for next models

11

Other Vector Temperature Controllers manuals

Vector TLC-BCR-T User manual

Vector

Vector TLC-BCR-T User manual

Vector TCY-MT2-U-W2 User manual

Vector

Vector TCY-MT2-U-W2 User manual

Vector TCY-FT-U User manual

Vector

Vector TCY-FT-U User manual

Vector TCY-FT Series User manual

Vector

Vector TCY-FT Series User manual

Vector TCY-MT-U User manual

Vector

Vector TCY-MT-U User manual

Vector SRC-C1T1 User manual

Vector

Vector SRC-C1T1 User manual

Vector TCY-MT Series User manual

Vector

Vector TCY-MT Series User manual

Vector TCY-FT2-U User manual

Vector

Vector TCY-FT2-U User manual

Popular Temperature Controllers manuals by other brands

Siemens Free Energy Band RCU61U Technical instructions

Siemens

Siemens Free Energy Band RCU61U Technical instructions

Myzone Myzone2 installation manual

Myzone

Myzone Myzone2 installation manual

domat THERMASGARD HTF 50 Operating Instructions, Mounting & Installation

domat

domat THERMASGARD HTF 50 Operating Instructions, Mounting & Installation

KIOUR TOUCH LINE RSD manual

KIOUR

KIOUR TOUCH LINE RSD manual

MULTISPAN UTC-421G quick start guide

MULTISPAN

MULTISPAN UTC-421G quick start guide

oventrop Unibox TQ vario operating instructions

oventrop

oventrop Unibox TQ vario operating instructions

Vostermans Ventilation Mf Net ETD-CN Installation and operating instructions

Vostermans Ventilation

Vostermans Ventilation Mf Net ETD-CN Installation and operating instructions

Nibe HPAC 42 Installer manual

Nibe

Nibe HPAC 42 Installer manual

Satchwell MN650 Series installation instructions

Satchwell

Satchwell MN650 Series installation instructions

PPE BTC15 Operation manual

PPE

PPE BTC15 Operation manual

Johnson Controls A19D Installation Sheets Manual

Johnson Controls

Johnson Controls A19D Installation Sheets Manual

Comet LOGGER S0141 instruction manual

Comet

Comet LOGGER S0141 instruction manual

Johnson Controls T606MSP-4 installation instructions

Johnson Controls

Johnson Controls T606MSP-4 installation instructions

Ropex RESISTRON RES-415 operating instructions

Ropex

Ropex RESISTRON RES-415 operating instructions

Comelit Home 20004100 Technical manual

Comelit

Comelit Home 20004100 Technical manual

STIEBEL ELTRON SOM 9s Installation, operation, functions and options, troubleshooting

STIEBEL ELTRON

STIEBEL ELTRON SOM 9s Installation, operation, functions and options, troubleshooting

Elotech R4000 Description and operating manual

Elotech

Elotech R4000 Description and operating manual

merten PLANTEC 626008 operating instructions

merten

merten PLANTEC 626008 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.