Veeder-Root TLS-3 Series User manual

TLS System Warnings & Alarms
Manual No: 577014-243 ●Revision A
Troubleshooting Guide

Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including but not
limited to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential
damages in connection with the furnishing, performance, or use of this publication.
The information contained in this publication may be subject to change without notice.
This publication contains proprietary information which is protected by copyright. All rights
reserved. No part of this publication may be photocopied, reproduced, or translated to another
language without the prior written consent of Veeder-Root.
©Veeder-Root 2016. All rights reserved.

TLS Warnings And Alarms
1
TLS Warnings And Alarms
The TLS console is constantly monitoring its probes and sensors for warning and alarm conditions, such as fuel
leaks, excessively high or low fuel levels, and equipment problems. In the Operating Mode with no warning or
alarm condition active, the TLS-3XX consoles display ‘ALL FUNCTIONS NORMAL’ and the TLS4/8601 &
TLS450PLUS/8600 consoles display ‘SYSTEM STATUS’. When a warning or alarm condition occurs, the system
displays/posts the alarm type and its location, indicating either tank, input or sensor number. Consoles with
printers generate an alarm report showing the warning or alarm type, the location and the date and time of the
warning or alarm condition that occurred. TLS4/8601 & TLS450PLUS/8600 consoles can be programmed to
email a selected address if warnings/alarms occur.
WARNINGS - These indicate that an alarm is imminent or that a system fault has occurred.
ALARMS - Alarms indicate that a potentially dangerous situation may have occurred.
WARNING! DO NOT IGNORE ALARMS! Know the alarm response procedures for your site.
When a Warning or Alarm is posted follow the procedure below to acknowledge the alarm and shut off the audible
beeper:
In-Tank Warning And Alarm Levels
TLS-3XX Consoles TLS4/8601 & TLS-450PLUS/8600 Consoles w/Display
Press the front panel red
ALARM/TEST key to
silence the alarm. The
front panel warning and
alarm lights cannot be
turned off until the cause
of the condition is cor-
rected. The warning and
alarm message(s) will
remain active. If more
than one alarm or warn-
ing exists the display will
flash the messages alter-
nately until the cause of
the alarm condition is cor-
rected.
Touch anywhere on the status/warning or status/alarm bar (shown) at the top of the touch screen
to go to the Reports > Alarms > Active screen and view the cause of the alarm. While in that
screen, touch the status bar again to acknowledge the warning/alarm and shut off the beeper.
The warning and alarm message(s) remain on the active alarm report screen until the cause of
the condition is corrected. The warning/alarm status bar will continue to display until the alarm
condition is corrected.
TLS4/8601 & TLS-450PLUS/8600 Consoles w/o Display
Touch the red ALARM RESET button on the console’s front panel to acknowledge the warning/
alarm and shut off the beeper. Warnings and alarms will remain active until the cause of the
condition is corrected.
ALARM
TEST
L 10: FUEL ALARM 0 Warning(s)
1 Alarms(s)
ALARM
RESET
Typical European Tank
SAFE WORKING CAPACITY
Maximum Product Alarm Level
Overfill Alarm Level
High Product Alarm Level
Fuel Draw
Off Level
Delivery Needed Warning Level
High Water Warning Level
Low Product Alarm Level
High Water Alarm Level
("Label" Volume)
Annular (Interstitial) Area
Full Volume
Interstitial Sensor/Header Tank

Displayed Alarm Messages
2
Displayed Alarm Messages
Common Alarm messages and a possible cause/action for the Alarms are listed in the table below. Actual Alarms
displayed by a particular console will depend upon the features installed.
Short Device IDs used in the table below:
C = 2-wire CL sensor Co = Comm device G = Groundwater sensor
H = 3-wire CL sensor I = External input L = Liquid sensor
MS = Mag sensor P = Printer Pm = Pump
Q = PLLD line R = Relay (TLS4/TLS-450PLUS), R = Receiver (TLS-3XX)
T = Tank s = Smart sensor V = Vapor sensor
Message
Short
Device ID Cause Action
Annual Test Needed Alarm Q, T System failed to perform an annual test (0.1 gph
[0.38 lph]) in the programmed number of days.
Schedule a 0.1 gph (0.38 lph) test.
Annual Test Needed Warn-
ing
Q, T System failed to perform an annual test (0.1 gph
[0.38 lph]) in the programmed number of days.
Schedule a 0.1 gph (0.38 lph) test.
Annual Line Test Fail
Alarm
Q 0.1 gph (0.38 lph) line test failure. Dispensing
halts, if programmed to do so.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Annual Leak Test Fail
Alarm
T System failed an annual in-tank leak test. Rerun in-tank leak test. If second test fails,
call for service.
Autodial Failed Alarm
(TLS4/TLS-450PLUS only)
Co System failed to connect to a remote receiver
after ‘n’ tries.
Verify the address book settings for the con-
tact are correct (i.e., modem device number,
phone number to dial), verify the receiving
device (fax or modem) is operational. Con-
tact technical support for assistance.
Cold Temperature Warning T Probe temperature drops below -4°F (-20°C). Probe returns to normal operation after
probe temperature rises above 0°F
(-17.8°C).
Continuous Handle On
Alarm
Q Handle signal has been active for a programmed
number of hours.
Call for service following the procedures
established for your site.
CSLD Rate Increase Warn-
ing
T An excessive amount of fluid leaked into the tank
during a test period.
Call for service following the procedures
established for your site.
Density Offset Warning T The console calculated density offset amount
exceeds the threshold amount: 10.012 kg/m3
(0.625 lbs/ft3).
Check the density offset values configured
for the probe. If these values are correct, the
probe float may be contaminated, and
should be replaced.
NOTE: This alarm message will continue to
display (scroll) in the System Status box
until you correct the cause of the problem.
Density Warning T Tank density is either:
• Greater than the tank density low limit plus
1.00kg/m3(0.062 lbs/ft3)
• Or is less than the tank density high limit minus
1.00 kg/m3(0.062 lbs/ft3)
Verify fluid density (retest when product
density is within the tank density low and
high limits.
Delivery Needed Warning T Product level dropped below programmed limit. Call for a delivery.

Displayed Alarm Messages
3
Email Failed Alarm
(TLS4/TLS-450PLUS only)
Co The console did not successfully send email when
configured to email.
Verify the address book settings for the con-
tact are correct (email address of recipient),
verify network connectivity is available
(Ethernet card is installed). Contact techni-
cal support for assistance.
Fuel Alarm L, G, C, H, V Fuel is present in the area being monitored by the
sensor.
Call for service following the procedures
established for your site.
Fuel Out Alarm Q Tank product level below 10-inch (25.4 cm) level -
cannot pump when active.
Schedule a delivery.
Fuel Quality Alarm T Water/phase separation may be present in tank. Test fuel at bottom of tank to ensure water/
phase separation is not present.
Generator Off I Backup generator shut down, in-tank leak testing
resumed.
None
Generator On I Backup generator switched on, in-tank leak test-
ing halted.
None
Gross Test Fail Alarm Q 3 gph (11.3 lph) line test failure. Dispensing halts,
if programmed to do so, while the alarm is active.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Gross Leak Test Fail Alarm T In-tank leak (3.0 gph [11.3 lph]) test failed. Rerun in-tank leak test. If second test fails,
call for service.
HRM Reconciliation Alarm
(HRM = Hourly Reconcilia-
tion Mode)
T Activated for a tank 90 minutes after the 24-hour
average variance has exceeded the preset HRM
limits.
Review HRM hourly diagnostics. Contact VR
Technical Support if variance cannot be
resolved.
High Liquid Alarm L Dispenser Pan/Containment Sump Sensors
Liquid reached 8" (203mm) on the dispenser pan
sensor or 10" (254mm) on the containment sump
sensor.
Immediately follow the alarm reporting pro-
cedures established for your site.
Dual-Float Differentiating Hydrostatic Sensor
A sensor in a brine-filled interstice detects an
increase in the brine level increase. Liquid is
entering the riser pipe, or in a high groundwater
area, an outer wall rupture has occurred.
Call for service following the procedures
established for your site.
H The sensor detects a high liquid level. Call for service following the procedures
established for your site.
High Product Alarm T Product level in tank rose above programmed
limit.
Do not allow additional delivery until product
is dispensed below preset limit.
High Water Alarm T Water detected in tank exceeds programmed
alarm limit.
Remove water from tank.
High Water Warning T Water detected in tank exceeds programmed
warning limit.
Remove water from tank.
Message
Short
Device ID Cause Action

Displayed Alarm Messages
4
iButton Fault Alarm
(TLS4/TLS-450PLUS only)
System
<No ID>
iButton failure.
System detected Damaged or Corrupted iButton.
The warning has been active 20 days and has
transitioned to an alarm. The alarm will be active
a maximum of 10 days. After the duration of 30
days, the user will be able to access only the fol-
lowing screens: About, Active Alarms, Alarm His-
tory, Priority Alarm, Maintenance Software and
Ethernet Communication Setup.
Replace iButton with valid one.
iButton Fault Warning
(TLS4/TLS-450PLUS only)
System
<No ID>
iButton failure.
System detected Damaged or Corrupted iButton.
Warning can be active a maximum of 20 days.
Replace iButton with valid one
Input Alarm I External device changed from programmed condi-
tion.
Check the operation of the external device.
Input Normal I (Not displayed, printed out only) External device
returned to preset condition.
None
Invalid Fuel Level T Product level is too low, causing the fuel and
water floats to be too close together.
Call for a delivery.
Leak Alarm T A static in-tank leak test failed.Rerun in-tank leak
test.
Rerun in-tank leak test.
Leak Test Active T In-tank leak test is underway. Do not dispense fuel from this tank until
message disappears.
Liquid Warning L, H Liquid reached 1” (25.4 mm) on the dispenser
pan or containment sump sensor.
Immediately follow the alarm reporting pro-
cedures established for your site.
Line Equipment Alarm Q A problem with the pressure measurement equip-
ment has been detected.
Call for service following the procedures
established for your site.
Low Liquid Alarm L The sensor in a brine-filled interstice detects a
decrease in the brine level. A hole is in the tank's
inner wall, or in low groundwater areas, a hole is
in the outer wall.
Call for service following the procedures
established for your site.
Low Pressure Alarm Q Low pump dispense pressure is detected during a
dispense. Dispensing halts if programmed to do
so.
The next handle up will restart the pump.
Low Product Alarm T Tank level dropped below the programmed limit. Call for a delivery.
Low Temperature Alarm T Probe temperature drops below -4°F (-20°C). Probe returns to normal operation after
probe temperature rises above 0°F
(- 17.8°C).
Mag Sensor Communica-
tion Alarm
MS, s Hardware failure - sensor or interconnecting wir-
ing to console.
Call for service following the procedures
established for your site.
Mag Sensor Fault Alarm MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Mag Sensor Fuel Alarm MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Mag Sensor Fuel Warning MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Message
Short
Device ID Cause Action

Displayed Alarm Messages
5
Mag Sensor High Liquid
Alarm
MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Mag Sensor High Liquid
Warning
MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Mag Sensor Install Alarm MS, s Sensor not installed in correct position. Call for service following the procedures
established for your site.
Mag Sensor Low Liquid
Alarm
MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Mag Sensor Low Liquid
Warning
MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Mag Sensor Temperature
Warning
MS, s Ambient temperature exceeded sensor’s operat-
ing range (-40 to +122°F [-40 to +50°C]).
Warning removed when temperature returns
to within sensor’s operating range.
Mag Sensor Water Alarm MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Mag Sensor Water Warn-
ing
MS, s Monitored parameter exceeded preset threshold. Call for service following the procedures
established for your site.
Maximum Product Alarm T Product level rose above the programmed limit. Stop delivery. Do not allow additional deliv-
ery until product drops below preset limit.
Missing Delivery Ticket
Warning
T Delivery Ticket information has not been entered
at the console.
Enter Delivery Ticket information.
No Dial Tone Alarm
(TLS4/TLS-450PLUS only)
Co System failed to detect an operational line after 3
tries.
This alarm must stay active until it is con-
firmed that the alarm has been reported.
No CSLD Idle Time Warn-
ing
T System has not had enough idle time over previ-
ous 24 hours to run a statistical leak detection
test.
Stop dispensing fuel from this tank until
CSLD test is complete.
Overfill Alarm T Fuel level has exceeded a programmed limit.
Potential overflow of tank may occur.
Stop delivery. Check for spillage.
Printer Out Of Paper
(TLS4/TLS-450PLUS only)
P
Paper roll is empty.
Replace the paper roll only with Veeder-Root
supplied paper rolls:
P/N 514100-456 - TLS-4/450PLUS
P/N 514100-210 - TLS-3XX
Printer Out Of Paper
(TLS-3XX only)
System
Periodic Test Fail Alarm Q 0.2 gph (0.76 lph) test failure. Dispensing halts, if
programmed to do so.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Periodic Test Needed
Alarm
Q, T A periodic in-tank leak (0.2 gph [0.76 lph]) test
has not been successfully completed within the
programmed number of days.
Schedule a 0.2 gph (0.76 lph) test.
Periodic Test Needed
Warning
Q, T A periodic in-tank leak (0.2 gph [0.76 lph]) test
has not been successfully completed within the
programmed number of days.
Schedule a 0.2 gph (0.76 lph) test.
Periodic Leak Test Fail
Alarm
T In-tank leak (0.2 gph [0.76 lph]) test failed. Dis-
pensing halts if programmed to do so.
Rerun in-tank leak test. If second test fails,
call for service.
Message
Short
Device ID Cause Action

Displayed Alarm Messages
6
Printer Error
(TLS4/TLS-450PLUS only)
P
Printer feed roller release is open.. Push the release lever to the up position.
Printer Error
(TLS-3XX only)
System
Probe Out T Hardware failure - probe or interconnecting wiring
to console.
Call for service following the procedures
established for your site.
Pump Out Alarm Pm A relay or external input has a Device Out alarm
active and the pump(s) that use that device will
not pump gas. Note that if a pump goes into
Device out, the Line it is on will go into ‘Device
Out’ as well.
Call for service following the procedures
established for your site.
Sensor Open Alarm Q Pressure sensor reading is less than -8 psi
(-55.16 kPa). Only tested while the pump is run-
ning. Dispensing halts if programmed to do so.
3 gph (11.3 lph) test must pass to clear the
alarm. Call for service following the proce-
dures established for your site.
Sensor Out Alarm L, G, C, H, V The sensor setup was performed incorrectly or a
sensor is disconnected or is not functioning prop-
erly.
Call for service following the procedures
established for your site.
Setup Data Warning All Devices Device setup data problem. Recheck device setup parameters.
Short Alarm L, G, C, H, V A short has occurred in the sensor wiring or in the
sensor.
Call for service following the procedures
established for your site.
Shutdown Q System shut down line because of failed line leak
test, or an alarm assigned to disable the line is
active.
Identify offending alarm, and refer to PLLD
alarms for corrective action.
Siphon Break Active Warn-
ing
T Siphon break valve has shut down manifold for
tank test.
Clears when tank test completes.
Sudden Loss Alarm T System detects loss of fuel during an idle period. Check for gross leak.
Water Out Alarm G Water level is below the float switch, making the
sensor ineffective.
Call for service following the procedures
established for your site.
Message
Short
Device ID Cause Action

For technical support, sales or
other assistance, please visit:
www.veeder.com