Veeder-Root Overfill Alarm User manual

Installation Guide
Overfill Alarm
Manual No: 576013-589 Revision: F

Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages
in connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication
may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.
DAMAGE CLAIMS / LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a
complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the
inspection and sign the description. Refuse only the damaged product, not the entire shipment.
Veeder-Root must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms
and Conditions.
VEEDER-ROOT’S PREFERRED CARRIER
1. Contact Veeder-Root Customer Service at 800-873-3313 with the specific part numbers and quantities that were missing
or received damaged.
2. Fax signed Bill of Lading (BOL) to Veeder-Root Customer Service at 800-234-5350.
3. Veeder-Root will file the claim with the carrier and replace the damaged/missing product at no charge to the customer.
Customer Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1. It is the customer’s responsibility to file a claim with their carrier.
2. Customer may submit a replacement purchase order. Customer is responsible for all charges and freight associated with
replacement order. Customer Service will work with production facility to have the replacement product shipped as soon as
possible.
3. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking
fee.
4. Veeder-Root will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy” pages in the
"Policies and Literature" section of the Veeder-Root North American Environmental Products price list. Veeder-Root will not
accept any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
©Veeder-Root 2022. All rights reserved.

Table of Contents
iii
Introduction
Compatible Consoles ........................................................................................................1
Related Manuals ...............................................................................................................1
Contractor Certification Requirements ..............................................................................1
Safety Symbols .................................................................................................................2
Safety Warnings ...............................................................................................................3
Mounting Instructions
Overfill Alarm and Acknowledgment Switch Dimensions ..................................................4
Mounting Instructions ........................................................................................................5
Overfill Alarm ............................................................................................................5
Acknowledgment Switch...........................................................................................5
Wiring Instructions
Wiring Overfill Alarm with Acknowledgment Switch ..........................................................6
Wiring Overfill Alarm without Acknowledgment Switch .....................................................7
Enclosure Grounding ........................................................................................................7
Setup and Test
Setting Overfill Alarm Horn Delay Time ............................................................................9
Testing the Overfill Alarm with the Acknowledgment Switch ............................................9
Setting the Overfill Alarm Horn’s Volume Level ................................................................9
Testing the Overfill Alarm with the Console ......................................................................9
Testing Overfill Alarm W/o Acknowledgment Switch..............................................10
Testing Overfill Alarm With Acknowledgment Switch .............................................10
Figures
Figure 1. Overfill Alarm Mounting Dimensions .......................................................4
Figure 2. Acknowledgment Switch Mounting Dimensions .....................................5
Figure 3. Overfill Alarm/Acknowledgment Switch wiring connections ....................6
Figure 4. Overfill Alarm only wiring connections ....................................................7
Figure 5. Overfill Alarm Ground Wire Termination .................................................8
Figure 6. Overfill Alarm Test Jumper Console Connection ....................................9
Tables
Table 1. Console Connections ...............................................................................8

1
Introduction
This manual contains installation procedures for the Veeder-Root Overfill Alarm and Acknowledgment (Ack)
Switch.
The Overfill Alarm unit contains:
• Red flashing light
• Alarm horn
The Acknowledgment Switch unit contains:
• ACKNOWLEGED light
• RESET push button
• TEST push button
Compatible Consoles
• TLS-3XX/4XX Series
• TLS-IB
• TLS-50
• TLS-HLD
• TLS2
Related Manuals
Depending on your installed console, you should reference the appropriate manuals below, to connect/setup the
Overfill Alarm:
576013-879 TLS-3XX Series Site Prep Manual 576013-623 TLS-3XX Series Setup manual
577013-608 TLS-50 Site Prep manual 577013-609 TLS-50 Setup manual
577013-756 TLS2 Site Prep manual 577013-757 TLS2 Setup manual
577013-719 TLS-IB Site Prep manual 577013-785 TLS-HLD Setup manual
577013-784 TLS-HLD Site Prep manual 577013-879 TLS-4XX Site Prep Manual
Contractor Certification Requirements
Veeder-Root requires the following minimum training certifications for contractors who will install and setup the
equipment discussed in this manual:
Service Technician Certification (Previously known as Level 2/3): Contractors holding valid Technician
Certifications are approved to perform installation checkout, startup, programming and operations training, system
tests, troubleshooting and servicing for all Veeder-Root Series Tank Monitoring Systems, including Line Leak
Detection.
TLS-3xx Technician Certification: Contractors holding valid TLS-350 Technician Certifications are approved to
perform installation checkout, startup, programming and operations training, troubleshooting and servicing for all
Veeder-Root TLS-300 or TLS-350 Series Tank Monitoring Systems, including Line Leak Detection and associated
accessories.

Introduction Safety Symbols
2
TLS-4xx Technician Certification: Contractors holding valid TLS-450 Technician Certifications are approved to
perform installation checkout, startup, programming and operations training, troubleshooting and servicing for all
Veeder-Root TLS-450 Series Tank Monitoring Systems, including Line Leak Detection and associated accessories.
All service personal on site must comply with all recommended safety practices identified by OSHA and your
employer.
Review and comply with all the safety warnings in this and any related documents, and any other Federal, State or
Local requirements.
Warranty Registrations may only be submitted by selected Distributors.
Safety Symbols
The following safety symbols are used throughout this manual to alert you to important safety hazards and precautions.
EXPLOSIVE
Fuels and their vapors are extremely explo-
sive if ignited.
FLAMMABLE
Fuels and their vapors are extremely flammable.
ELECTRICITY
High voltage exists in, and is supplied to, the
device. A potential shock hazard exists.
TURN POWER OFF
Live power to a device creates a potential shock
hazard. Turn Off power to the device and associ-
ated accessories when servicing the unit.
NOTICE is used to address practices not
related to physical injury.
READ ALL RELATED MANUALS
Knowledge of all related procedures before you
begin work is important. Read and understand all
manuals thoroughly. If you do not understand a
procedure, ask someone who does.

Introduction Safety Warnings
3
Safety Warnings
WARNING
This product is to be installed in systems operating near locations
where highly combustible fuels or vapors may be present.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND
SAFETY PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY,
ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH.
Fire or explosion resulting in serious injury or death could result if the
Overfill Alarm and Ack switch units are installed in a volatile,
combustible or explosive (Class I, Division I and Division II)
atmosphere.
Explosion could occur if alarm wires share tank monitor or console
probe or sensor wire conduits or wiring troughs. Do not run Overfill
Alarm and Ack Switch wires with console probe and sensor wires.
1. Read and follow all instructions in this manual, including all
safety warnings.
2. Comply with all applicable codes including: the National
Electrical Code; federal, state, and local codes; and other
applicable safety codes.
3. Do not alter or modify any component or substitute components
in this kit.

4
Mounting Instructions
Overfill Alarm and Acknowledgment Switch Dimensions
Figure 1 shows the Overfill Alarm mounting dimensions and Figure 2 shows the Acknowledgment Switch
mounting dimensions.
Figure 1. Overfill Alarm Mounting Dimensions
VEEDER-ROOT
0.313'' (8 mm) dia.
4 holes
2 ''
(50.8 mm)
1/2 ''
conduit
connector
1.6 ''
(40.6 mm)
4 ''
(101 mm)
6'' (152.4 mm)
8'' (203 mm)
6'' (152.4 mm)
10.3 ''
(261.9 mm)
Hinge
side
Red Flashing Light
Horn volume
adjustment screw
(1/16'' Hex Hd)

Mounting Instructions Mounting Instructions
5
Figure 2. Acknowledgment Switch Mounting Dimensions
Mounting Instructions
Overfill Alarm
1. Select a mounting location where the Overfill Alarm can be seen and heard clearly from the area where the
fuel tanks are filled. In addition, consider the ease of routing interconnection conduit.
2. Locate and mark mounting holes using the hole pattern in Figure 1.
3. Mount the Overfill Alarm using the four mounting tabs on the housing.
Acknowledgment Switch
1. Select a mounting location where the Acknowledgment Switch can be easily activated by the tank truck driver.
In addition, consider the ease of routing interconnection conduit.
2. Locate and mark mounting holes using the hole pattern in Figure 2.
3. Mount the Acknowledgment Switch using the four mounting tabs on the housing.
4. Install conduit between the Acknowledgment Switch, Overfill Alarm, and TLS Console.
RESET
ACKNOWLEDGE
VEEDER-ROOT
2'' (50.8 mm)
4.3'' (109.5 mm)
2'' (50.8 mm)
6.75"
(171.5 mm)
1.4 ''
(35.6 mm)
1/2 ''
conduit
connector
3'' (76.2 mm)
1'' (25.4 mm)
Hinge
side
TEST button
(on side)
0.313'' (8 mm) dia.
4 holes

6
Wiring Instructions
Wire used for this installation must have a temperature rating of at least 90°C. be either 14 or
16 AWG, and be color coded. Splicing alarm power with TLS Console power will cause
improper operation of the monitor.
Wiring Overfill Alarm with Acknowledgment Switch
1. Pull two wires from the switch to the Overfill Alarm.
2. Pull two wires for line and neutral from the switch to the power panel.
3. Pull one wire from the switch to the TLS Console for connection to the alarm relay.
4. Pull one wire for line from the alarm relay in the TLS Console to the power panel.
5. Turn power Off and connect wiring according to the wiring diagram in Figure 3 and Table 1.
Figure 3. Overfill Alarm/Acknowledgment Switch wiring connections
1234 56
To power panel
LN
123
To Console Relay -
See Console Connection
Table in this manual
Ack Switch
(cover open)
Overfill Alarm
(cover open)
Customer supplied
junction box
Horn Time
Delay Relay
NOTICE
MAKE GROUND CONNECTION IN
ACCORDANCE WITH LOCAL CODES.

Wiring Instructions Wiring Overfill Alarm without Acknowledgment Switch
7
Wiring Overfill Alarm without Acknowledgment Switch
1. Pull one wire for neutral from the Overfill Alarm to the power panel.
2. Pull one wire from the Overfill Alarm to the console for connection to the alarm relay.
3. Pull one wire for line from the alarm relay in the console to the power panel.
4. Turn power Off and connect wiring according to the wiring diagram in Figure 4 and Table 1.
Figure 4. Overfill Alarm only wiring connections
Enclosure Grounding
There are two separate methods for grounding the Overfill Alarm. Ensure that the ground connection is made in
accordance with all local codes.
If using a properly grounded rigid metal conduit or equivalent to enclose the external wiring for the Overfill Alarm,
the ground hub that terminates the conduit provides an adequate grounding provision for the Overfill Alarm.
If using a ground wire within the conduit, terminate the ground wire on the grounding stud located in the bottom of
the enclosure. Ensure that a star washer is between the enclosure and the lug attached to the ground wire and
that the lug is secured in place by the included KEPS nut (see Figure 5).
To power panel
LN
123
Overfill Alarm
(cover open)
Horn Time
Delay Relay
To Console Relay -
See Console Connection
Table in this manual
Customer supplied
junction box
NOTICE
MAKE GROUND CONNECTION IN
ACCORDANCE WITH LOCAL CODES.

Wiring Instructions Enclosure Grounding
8
Figure 5. Overfill Alarm Ground Wire Termination
Table 1. Console Connections
Input
TLS2 or TLS-
IB
Connection
TLS-50 or
TLS-HLD
Connection
TLS-300
Output Relay
Connection
TLS-350
I/O Combo
Relay
Connection
TLS-350
4 Relay Output
Module
Connection
TLS-4XX
Overfill Alarm
Relay Connector
Overfill Alarm without Acknowledge Switch (see Figure 4)
Overfill Alarm terminal 2 J6, 1 J5, 1 NO NO NO NO
Line (from power panel) J6, 2 J5, 2 C C C C
Overfill Alarm with Acknowledge Switch (see Figure 3)
Ack Switch terminal 1 J6, 1 J5, 1 NO NO NO NO
Ack Switch terminal 5 (line) J6, 2 J5, 2 C C C C
Star Washer
(against enclosure)
Ground Wire
KEPS Nut

9
Setup and Test
Setting Overfill Alarm Horn Delay Time
1. Loosen the four screws that secure the Overfill Alarm cover clamps to the case. Slide the clamps away from
the retaining lip on the door. Open the door.
2. Locate the Horn Time Delay Relay (see Figure 3).
3. Adjust the time the horn remains On from 0 to 60 seconds by turning the knob on the relay to the desired
setting.
4. Close the door and tighten the four cover screws.
Testing the Overfill Alarm with the Acknowledgment Switch
Turn On power to the Overfill Alarm and Acknowledgment Switch. Depress and hold in the TEST Button on the
right side of the switch. The Overfill Alarm horn will sound immediately, and the Overfill Alarm’s red light will start
flashing. The horn will turn Off at the preset delay time you set above (0 -60 seconds). The red light will continue to
flash until the TEST button is released.
Setting the Overfill Alarm Horn’s Volume Level
1. Locate the adjustment set screw (1/16” Hex wrench) on the exterior of the Overfill Alarm’s horn cover (see
Figure 1 on page 4).
2. Turn the adjustment screw counterclockwise to increase the dB level of the horn or clockwise to decrease its
dB level.
Testing the Overfill Alarm with the Console
With the Overfill Alarm and Acknowledgment Switch (if installed) connected to the console, consult the setup
instructions for your console and perform the Output Relay setup procedure to recognize the Overfill Alarm.
1. Turn power Off to the console and the Overfill Alarm. Put a jumper between the two Overfill Alarm relay
connections in the console (see Figure 6).
Figure 6. Overfill Alarm Test Jumper Console Connection
NO
C
To
Overfill
Alarm
Console Input
Relay Terminals
Test Jumper

Setup and Test Testing the Overfill Alarm with the Console
10
Testing Overfill Alarm W/o Acknowledgment Switch
1. Reapply power. If the Overfill Alarm was wired properly, the alarm horn will sound immediately followed by the
red alarm light flashing.
2. Turn Off power to the console and to the Overfill Alarm. Remove the test jumper between the Output Relay
connections.
Testing Overfill Alarm With Acknowledgment Switch
1. Turn power Off to the console and the Overfill Alarm. Put a jumper between the two Overfill Alarm relay
connections in the console (see Figure 6).
2. Stand by the Acknowledgment Switch and have someone reapply power to the console and Overfill Alarm. If
the Overfill Alarm was wired properly, the alarm horn will sound immediately followed by the red alarm light
flashing.
3. Press the RESET button on the front of the Acknowledgment Switch. The alarm horn and red flashing light
should shut off. The ACKNOWLEDGED light on the front of the switch should be On. (Pressing the RESET
button shuts Off the alarms but does not clear the alarm. The cause of the alarm must be removed before the
ACKNOWLEDGED light will turn Off.)
4. Turn Off power to the console and to the Overfill Alarm. Remove the test jumper between the console’s
Output Relay connections.
5. Reapply power to the console and to the Overfill Alarm. The ACKNOWLEDGED light should now be Off
because the cause of the alarm (in this case, the test jumper) has been removed.